background image

 

3/15 

 

CAUTION 

All previous issues of this Technical Manual expire on the date of issue hereof. 

This Technical Manual does not apply to any fans manufactured prior to this Manual's date of 

issue. 

 

1. FOREWORD__________________________________________________ 

This Technical Manual is addressed to users/operators of type mcr Pasat roof smoke exhaust fans. This 
document is intended to provide guidelines on the application, design, commissioning and operation of 
the product.  

 

 

Read  this  Technical  Manual  thoroughly  before  installing  this  equipment  at  its 
operating site and commissioning.  

 
 

 
If  the  equipment  is  found  malfunctioning  or  defective,  contact  the  manufacturer  or 
their Authorised Representative. 

 
 

 

Due  to  the  continuous  product  improvement  policy,  we  reserve  the  right  to  change 
the product design in order to improve its performance and safety.  

 
 

 

This equipment has been designed and manufactured according to the following standards: 

PN-EN 12101-3:2004  

Smoke and heat control systems.  

 

Part 3: Specification for powered smoke and heat exhaust fans.  

PN-EN ISO 12100-1:2005 

Safety of machinery. Basic concepts, general principles for design. 

 

Part 1: Basic terminology, methodology. 

PN-EN ISO 12100-2:2005 

Safety of machinery. Basic concepts, general principles for design. 

 

Part 2: Technical principles. 

PN-EN 60204-1:2001  

Safety of machinery. Electrical equipment of machines.  

 

Part 1: General requirements.  

 
The smoke exhaust fan design also meets the state of the art in technology, while assuring health and 
safety protection. 
 

 

2. MANUFACTURER'S DISCLAIMER_______________________________  

  The manufacturer shall not be liable for any consequences of non-intended use or misuse of the 

equipment. 

  DO  NOT  install  any  components  that  are  not  included  in  the  equipment  composition  or 

accessories.  

  Unauthorised modifications or alteration of this equipment is strictly prohibited.  

  Protect the equipment enclosure (casing) from mechanical damage.  

  Before  attempting  to  install  this  equipment,  verify  the  load  bearing  capacity  of  the  structural 

elements to which the equipment is to be fastened. Unreliable fastening may result in damage or 
failure of the equipment and/or be hazardous to all nearby personnel.  

  This fan is not intended for forcing air with viscous pollutants that may settle on the equipment, 

and especially on its rotor.  

Содержание mcr Pasat

Страница 1: ...ul Grzegorza z Sanoka 2 80 408 Gdańsk tel 48 58 341 42 45 tel fax 48 58 341 39 85 TECHNICAL MANUAL Roof smoke exhaust fan mcr Pasat Version Pasat 19 06 27 3 FIRE VENTILATION SYSTEMS ...

Страница 2: ...n 6 5 3 Dimensions 6 5 4 Accesories 7 6 IDENTIFICATION MARKING 9 7 INSTALLATION 9 7 1 Pre assembly inspection 9 7 2 Location and assembly 9 7 3 Electrical connections 11 7 4 Commissioning 12 8 TRANSPORT STORAGE CONDITIONS 12 9 SAFETY MANUAL 12 10 MAINTENANCE SERVICING 13 11 WARRANTY TERMS CONDITIONS 13 VENTILATOR MEASUREMENT REPORT 15 Technical Manual designations available option unavailable opti...

Страница 3: ...ISO 12100 1 2005 Safety of machinery Basic concepts general principles for design Part 1 Basic terminology methodology PN EN ISO 12100 2 2005 Safety of machinery Basic concepts general principles for design Part 2 Technical principles PN EN 60204 1 2001 Safety of machinery Electrical equipment of machines Part 1 General requirements The smoke exhaust fan design also meets the state of the art in t...

Страница 4: ...tion of persons from the area on fire protect the building structure and its furnishing from high temperature facilitate fire fighting and inhibit spreading of fire to adjacent fire zones The available versions include single functional with single speed motors two functional i e for general and fire ventilation and with two speed motors The fans can be installed outdoors on suitable consoles roof...

Страница 5: ...0o C for 120 minutes Class F600 fire resistance at 600o C for 60 minutes 4 3 Versions Single speed single functional fans Two speed two functional fans 5 DESIGN AND OPERATING PRINCIPLE 5 1 Design ______________________________________________________________________ 1 Fan base 2 Cooling duct 3 External housing 4 Motor housing 5 Inlet port 6 Motor base 7 Radial rotor 8 Electric box service switch o...

Страница 6: ...________________________________________ The single functional fans do not run in standby When 3 phase voltage is present on the electric box terminals the fan is started and running The two functional fans run at low speed RPM to handle general ventilation under normal conditions When the fan receives an alarm signal it automatically starts running with the second speed which is higher than the f...

Страница 7: ...It acts as a vibration damper It is also used to compensate for thermal elongation The fan integrated in a ventilation system should feature the flexible joint on the suction side Type KD flexible joint Fan Type Type D mm A mm B mm L mm C nxd mm m kg mcr Pasat 35 KD 31 315 385 356 150 45 8x9 6 1 0 mcr Pasat 35 KD 35 355 425 395 150 45 8x9 6 1 1 mcr Pasat 40 KD 40 400 470 438 150 30 12x9 6 1 3 mcr ...

Страница 8: ...heat losses when the fan is in standstill The automatic non return damper is intended for vertical installation with the damper blade axis is horizontal The damper needs precise levelling to operate correctly Type KS V automatic non return damper Fan Type Type D mm A mm B mm L mm C nxd mm m kg mcr Pasat 31 KS V 31 315 385 356 220 45 8x9 6 5 7 mcr Pasat 35 KS V 35 355 425 395 240 45 8x9 6 6 6 mcr P...

Страница 9: ..._________________________________________ Locate the mcr Pasat smoke exhaust fan outdoor and beyond the fire zone The equipment installation orientation must be horizontal i e with the motor axis in the vertical at a minimum height of 250 mm above the roof plane Prior to installation verify the load bearing capacity of the roof structure on which the equipment is to be located Prepare and secure a...

Страница 10: ...ust fan or other components of the assembly The ventilation duct must be supported by independent bearing slings Secure the smoke exhaust fan suction intake with type SO safety mesh When installing the smoke exhaust fan secure the installation site and all involved structures and prepare passage and access ways for all personnel not involved in the installation The smoke exhaust fan must be assure...

Страница 11: ... inadvertent shutdown of the smoke exhaust fan with the sole exception of the fan dedicated service switch with remote indication of current circuit switching The smoke exhaust fan control cabinets must be powered directly from mail switchboards with guaranteed uninterrupted power supply even if the entire building is cut off from the power grid If a main fireman s switch is installed to isolate p...

Страница 12: ...ases corrosive vapours and other aggressive chemical emissions detrimental to insulation parts and structural components of the fan and or its motor the maximum relative humidity is 80 at 20 C the ambient temperature does not exceed the range of 20ºC to 40 ºC no vibrations are present 9 SAFETY MANUAL________________________________________________ Read and understand this Technical Manual before c...

Страница 13: ...85 from 8 AM to 4 PM Mo Fri 11 WARRANTY TERMS CONDITIONS ___________________________ 1 MERCOR SA grants 12 months of warranty for the equipment quality from the date of purchase unless the sales contract states otherwise 2 Submit each warranty claim to MERCOR SA in 7 days from the date of discovery of a warranty eligible defect 3 Submit warranty claims by calling at tel 48 58 341 42 45 by fax 48 5...

Страница 14: ...ressive external influence specifically chemical or biological in nature or when the origin of which is related to the production processing or activity carried out within the facility protected by the equipment or in its direct vicinity Wearing parts and consumables e g gaskets seals unless they have defects of workmanship and or material Damage caused by improper transport handling unloading and...

Страница 15: ...f the equipment MEASUREMENT RESULTS A U1 V1 W1 U2 V2 W2 NOTES Full name of the measuring technician Date measured Signature Return this Report immediately after completion of measurements to MERCOR SA Fire Ventilation Systems Ul Grzegorza z Sanoka 2 80 408 Gdańsk and not later than in 8 weeks from the date of equipment purchase equivalent to the date of the VAT sales invoice THE EQUIPMENT WARRANTY...