mcr OMEGA pro
Power and Control Panel
„MERCOR” S.A. –
The company reserves the right to modify and amend this document without notice.
4/28
Fig. 1. Diagram of mcr OMEGA pro interface connectivity
The mcr OMEGA pro Power and Control Panel features an integrated fire equipment power supply unit
type mcr OMEGA pro or mcr OMEGA prof (with load transfer switching). The power section of the mcr
OMEGA pro Power and Control Panel meets the standard EN 12101-10:2005+AC:2007 "Smoke and heat
control systems
– Part 10: Power supplies" and EN 54-4:1997+AC:1999+A1:2002+A2:2006 "Fire
detection and fire alarm systems
– Part 4: Power supply equipment". The mcr OMEGA pro Power and
Control Panel can be installed in multiple non-distributed enclosures that should be bolted together. The
Power Supply Unit and the mcr OMEGA pro Power and Control Panel must be installed in the same
enclosure.
Power and Control Panel capabilities:
Manual alarm tripping with manual smoke venting controls;
Automatic fire detection with smoke detectors;
Fire Alarm System output handling;
Fire Alarm relay;
System fault data relay;
Alarm resetting and smoke damper closing;
Operating status monitoring for interfaced devices;
Manual smoke damper opening for building ventilation;
Automatic smoke damper closing if open and venting air (if connected to a weather control station
with a rain and wind sensor);
Interface connectivity with visualization HMI systems and building management systems (BMS) over
Modbus RTU (RS485): see the data communication parameters in the respective instruction manual.
These capabilities of the mcr OMEGA pro Power and Control Panel can be enabled depending on the
building design and fire scenario requirements; hence all functionalities can be enabled or any combination
thereof.