„MERCOR” SA –
The company reserves the right to modify and change the document
15/18
Thermal trigger trip point
72°C +-2°C
WK1d / WK2d limit switch
NO/NC (switching contact)
5A, 230V AC
Switch trigger
3°, 87° – tolerance: +/- 2°
Limit switch operating
temperature
-25 ...+85°C
Electrical connection
X
- release: cable 0.6 m, 2x0.5 mm
2
- limit switch: cable 0.6 m, 6x0.5 mm
2
Rotation angle
92°
Movement time
Max. 2s - spring
Sense of rotation
CCW
Gear weight
1.2 kg
1.4 kg
1.4 kg
1.5 kg
1.5 kg
KW1 gear power supply:
WK1 limit switch
WK2 limit switch
Wire number: 1-2
Wire number: 3-4 – NO (normally open)
Wire number: 6-7 – NO (normally open)
Wire number: 4-5 – NC (normally closed)
Wire number: 7-8 – NC (normally closed)
Connection diagram for transformer module type MP230/24
Warning! - Location of limit switches of the mechanism was shown for the damper safety position
For proper operation of a device equipped with electrical actuators, it is recommended that the rated voltage housed
tolerance of 24V±2% or 230V±2%. Power supply devices other than listed above may cause malfunction and will not
be covered by the warranty conditions.
Release and control mechanism RST
In the RST version, the limit switches are installed inside the damper enclosure as independent subassemblies. The
fuse release can be found on the damper partition. The drive spring is installed on the damper partition.
In order to install the fuse release in the RST version:
Set the damper partition in the open position
We put the fuse cells on hooks attached to the damper body and to the partition.
We draw in and lock the hook on the damper body by tightening the nut.