mcr FID S/… c/P
single-plane fire dampers
„MERCOR” SA –
The company reserves the right to modify and change the document
11/18
6.4. ELECTRICAL CONNECTIONS
After correct embedding of the damper, if it has control elements or other elements that require connecting the
electrical installation, connect the lines of this installation to the damper. Below we can see the connection diagrams
and the basic electrical data of the release and control mechanisms supplied with the mcr FID S/... c/P dampers.
Electric actuators – electrical specification
Actuator type
Location of the damper isolation partition
- Belimo BFL series
- Belimo BFN series
- Belimo BF series
Open isolation partition – actuator indication: 90
Closed isolation partition – actuator indication: 0
- Belimo serii BE
- Belimo serii BLE
- Belimo serii BEE
- Belimo serii BEN
Open isolation partition – actuator indication: 0
Closed isolation partition – actuator indication: 90
Technical specifications
BF 24, BF24-T, BF24-
TN
BF230, BF230-T,
BF230-TN
Power supply
AC 24V 50/60Hz DC
24V
AC 220-240V 50/60 Hz
Power demand:
- for spring tensioning
7 W
8,5 W
- for spring holding
2 W
3 W
Sizing (apparent power)
10 VA
11 VA
Appliance class
III
II
Ingress protection rating
IP 54
IP 54
Auxiliary circuit breaker:
2xSPDT
6 (3) A, 250V
2xSPDT
3 A, 250V~
- activation position [degrees]
5°, 80°
5°, 80°
Torque:
- motor
18 Nm
18 Nm
- spring
12 Nm
12 Nm
Cable connection:
- motor (L = 0.9 m)
2x0,75 mm
2
2x0,75 mm
2
- auxiliary circuit breaker
6x0,75 mm
2
6x0,75 mm
2
Movement time: (0-90°)
- motor
120 s
120 s
- return spring
16 s
16 s
Operating temperature range
- 30 ...+50°C
- 30 ...+50°C
Sound pressure level:
- motor
max 45 dB (A)
max 45 dB (A)
- spring
~ 63 dB (A)
~ 63 dB (A)
Technical specifications -
Actuators
BE24,
BE24-ST
BE230
BLE24 ,
BLE24-ST
BLE230
Power supply
AC 24V 50/60Hz
DC 24 V
AC 220-240V 50/60 Hz
AC 24V 50/60Hz
DC 24V
AC 220-240V 50/60 Hz
Power demand:
- for spring tensioning
12 W
8 W
7.5 W
5 W
- for spring holding
0,5W
0,5 W
0,5 W
1 W
Sizing (apparent power)
18 VA
15 VA
9 VA
12 VA
Appliance class
III
II
III
II
Ingress protection rating
IP 54
IP 54
IP 54
IP 54
Auxiliary circuit breaker:
2xSPDT
6(3) A, 250V
2xSPDT
6(3) A, 250V
2xSPDT
3A, AC 250V
2xSPDT
3A, AC 250V
- activation position [degrees]
3°, 87°
3°, 87°
3°, 87°
3°, 87°
Torque:
- motor
40 Nm
40 Nm
15 Nm
15 Nm
- locking
50 Nm
50 Nm
20 Nm
20 Nm
Cable connection:
- motor (L = 0.9 m)
3x0,75 mm2
3x0,75 mm2
3x0,75 mm2
3x0,75 mm2
- auxiliary circuit breaker
6x0,75 mm2
6x0,75 mm2
6x0,75 mm2
6x0,75 mm2
Movement time: (0-90°)
60s
60 s
30 s
30 s
- motor
Operating temperature range
- 30 ...+50°C
- 30 ...+50°C
- 30 ...+50°C
- 30 ...+50°C
Sound pressure level:
- motor
max 62 dB (A)
max 62 dB (A)
max 62 dB (A)
max 62 dB (A)
Technical specifications -
Actuators
BEE24,
BEE24-ST
BEE230
BEN24,
BEN24-ST
BEN230
Power supply
AC 24V 50/60Hz
AC 220-240V 50/60 Hz
AC 24V 50/60Hz
AC 220-240V 50/60 Hz