1. Damper mcr DOR BxH
2. Multi-compartment smoke extract
duct – e.g. made of fire-proof boards*
3. A strip of fire-proof board along the
entire length of the BxH side*
4. Solid wall
5. Masking grille MWD (opiton)
Damper installation in solid walls with a multi-compartment horizontal ducts
5
6
4
1
2
3
1. Damper mcr DOR BxH
2. Multi-compartment smoke extract
duct – e.g. made of fire-proof
boards*
3. A strip of fire-proof board along the
entire length of the BxH side*
4. Installation hangers system
5. M10 x 20 bolt
6. Masking grille MWD (opiton)
Damper installation in a multi-compartment horizontal ducts
CAUTION
Smoke extraction ducts should be made in accordance with the ducts manufacturer’s guidelines.
The ducts must have an adequate fire resistance rating in accordance with the fire resistance rating
provided for the entire solution. Seal all connections between the damper and the ducts with the
appropriate mortar/glue/gaskets, ensuring that the fire resistance rating is maintained. The smoke
control damper in vertical fire ventilation systems may be installed across the horizontal smoke
extract duct or on the sides of the horizontal smoke extract duct or on the surface of any side of
the vertical smoke extract duct. A masking grille may terminate the system.