1.3 ELECTRICAL CONNECTIONS

CAUTION: POWER MUST BE OFF WHILE WIRING CONNECTIONS ARE BEING MADE. 
CAUTION: Do not exceed the specified supply voltage rating. Permanent damage not covered by the warranty
may result.
CAUTION: To maintain type 4X rating of the enclosure, 1/2 NPT conduit fittings must have a UL type 4X out-
door rating.

Note: 

Installation must be made in accordance with local codes and regulations. When fishing wire through the conduit

connection do not allow the wire to touch or press on components on the boards. Damage to the circuitry may result.

Electrical connections are made to the removable terminal blocks inside the enclosure. Remove the top back cover, do
not remove bottom cover. Feed stripped and tinned leads through the conduit opening and connect them as shown in
Figure 3. The EDA provides two 1/2˝ NPT female ports for conduit connection. The conduit connections must be made
such that condensation is not allowed to enter the sensor housing. If necessary install a conduit breather drain in a sep-
arate conduit body to prevent buildup of moisture. It is recommended that shielded twisted pair wire be used for the
transmitter output option if the potential exists for interference from external noise sources. When replacing top back
cover tighten screws to 2 ±.25 in. lbs. 

Figure 3: Wiring 

An  external  power  supply  of  12-28
VDC/AC  with  minimum  current  capability
of 200 mA must be used to power the unit.
The power supply connection is not polari-
ty  sensitive  so  the  positive  and  negative
connections may be made to either termi-
nal of CONN9 terminal block.
For voltage output option, connect the volt-
age receiver (-) to terminal 1 and voltage
receiver (+) to terminal 2 of the CONN10
terminal  block.  For  current  output  option,
connect the current receiver (-) to terminal
3 and current receiver (+) to terminal 4 of
CONN10 terminal block. DO NOT APPLY
EXTERNAL  POWER  TO  CONN10  TER-
MINALS  -  PERMANENT  DAMAGE  NOT
COVERED  BY  WARRANTY  WILL
RESULT.

Loads can be connected to connectors CONN7 and CONN8 terminal blocks based on the Control settings:

• For single set point mode (

CtrL-1SP

), connect the Load to 

SP1

relay (CONN7).

•  For two set points mode (

CtrL-2SP

), connect the Load1 to 

SP1

relay (CONN7) and

Load2 to 

SP2

relay (CONN8).

• For single set point and alarm mode (

CtrL-SPAL

), connect the Load1 to 

SP1

relay

(CONN7) and Load2 to

ALARM 

relay (CONN8).

Wiring

An external switch or circuit breaker should be added to during the installation as a disconnecting device. The switch
or circuit breaker must meet the requirements of IEC 60947-1 and IEC 60947-3, shall disconnect all current carrying
conductors, and shall not interrupt the protective earth ground. The disconnecting switch or circuit breaker must be
marked or labeled with the symbols “I” for on and “O” for off, per IEC 60417-5007 & IEC 60417-5008 and shall be
marked as “Disconnecting Device”. Do not position the PLS in a space where it is difficult to operate the disconnecting
device that provides power. 300V @ 90°C 18 AWG/0.75 mm

2

wiring with PVC or equivalent insulation with 94-V0 or FV-

0 flammability rating is recommended for the switch outputs and power. Terminal blocks rated for 16-22 solid or strand-
ed copper conductor. 6 lb in is suggested tightening torque.

5

SP1

RELAY

5A 250 VAC FOR LOADS USING 120/240 VAC POWER

1A 32 VDC FOR LOADS USING 30 VDC POWER

375 mA 250 VAC

LOAD 1

LOAD 2

LINE

INPUT

12 TO 30 VDC/AC

POWER

SP2 OR ALARM

RELAY

Description

Direct current
Alternating current
Protective conductor terminal
On (supply)
Off (supply)

Symbol

Explanation of Symbols:

~

Publication

IEC 50417 - 5031
IEC 50417 - 5032
IEC 50417 - 5019
IEC 50417 - 5007
IEC 50417 - 5008

 

  

As a permanently installed piece of equipment, a power disconnect switch, circuit breaker, or other
approved disconnect device must be installed in close proximity to the installed board and within

easy reach of the operator. This disconnect device must include a label indicating its function as a mains disconnect. A
circuit breaker or fuse device is recommended (see Figure 3).

WARNING

Remote Site Products  -  1-888-532-2706  -  www.remotesiteproducts.com

http://www.remotesiteproducts.com/p-14328-Dwyer-Mercoid-EDAW-N1E1-06T0-Pressure-Controller.aspx

Содержание EDA series

Страница 1: ... Instructions DWYER INSTRUMENTS INC Phone 219 879 8000 www dwyer inst com P O BOX 373 MICHIGAN CITY IN 46360 U S A Fax 219 872 9057 e mail info dwyer inst com Remote Site Products 1 888 532 2706 www remotesiteproducts com http www remotesiteproducts com p 14328 Dwyer Mercoid EDAW N1E1 06T0 Pressure C ...

Страница 2: ...8 Alternation Lead Lag Operation 8 Programming Chart 9 11 Main Menu Selections 12 Menus and Values 12 18 Security Menu 12 Operation Menu 13 Output Menu 14 15 Display Menu 16 Advanced Menu 16 Test Menu 17 Failsafe Menu 17 Diagnostic Error Messages 18 Warranty Information 18 Remote Site Products 1 888 532 2706 www remotesiteproducts com http www remotesiteproducts com p 14328 Dwyer Mercoid EDAW N1E1...

Страница 3: ...32 115 09 1 25 40 3 1 16 77 89 27 32 21 43 1 59 64 26 16 2X 5 16 7 93 3 15 32 88 11 1 5 8 41 28 40 88 3X 1 8 3 18 1 2 FEMALE NPT CONDUIT ENTRY Remote Site Products 1 888 532 2706 www remotesiteproducts com http www remotesiteproducts com p 14328 Dwyer Mercoid EDAW N1E1 06T0 Pressure C ...

Страница 4: ... Weatherproof type 4X IP65 IP65 not evaluated by UL Unit is rated weatherproof but if unit is panel mounted panel will not maintain 4X rating Warm Up Time 10 seconds Mounting Orientation Any position Weight 1 18 lbs 535 g Installation Category II transient over voltage Pollution Degree 2 Altitude Limit 6560 ft 2000 m max Environment Intended for indoor and outdoor use Humidity 0 to 95 RH up to 104...

Страница 5: ...s the E key to edit an item s value the upper display will flash EDIT and the lower display will blink When the user presses the E key to then save the edit to the value the upper display will flash SAVE and the lower display will stop blinking Example Series Housing Process Connection Electrical Connection Range Transmitter Output Options EDA EDA W N1 B1 A1 E1 01 02 03 04 05 06 07 08 09 10 11 12 ...

Страница 6: ... mount the unit into the A 370 mounting bracket See the Dwyer catalog or website for ordering details also shown in Figure 1 The unit can also be directly surface mounted as shown in Figure 2 with the proper panel cutout for the conduit entrances Support the pressure connection hex with a wrench if attaching a fitting to the unit in the case of panel or flush mounting so that the pressure connecti...

Страница 7: ...nected to connectors CONN7 and CONN8 terminal blocks based on the Control settings For single set point mode CtrL 1SP connect the Load to SP1 relay CONN7 For two set points mode CtrL 2SP connect the Load1 to SP1 relay CONN7 and Load2 to SP2 relay CONN8 For single set point and alarm mode CtrL SPAL connect the Load1 to SP1 relay CONN7 and Load2 to ALARM relay CONN8 Wiring An external switch or circ...

Страница 8: ...nctions Key Functions HOME POSITION FUNCTION MAIN MENU FUNCTION ITEM FUNCTION Enter into items Peak Valley resets display to present value Remote Site Products 1 888 532 2706 www remotesiteproducts com http www remotesiteproducts com p 14328 Dwyer Mercoid EDAW N1E1 06T0 Pressure C ...

Страница 9: ... the desired relay turn off point In the above graph an instrument with a 100 psi range would have the SP1 relay turn ON at 80 psi and OFF at 40 psi SP1H sets the relay turn ON point and SP1L sets the relay turn OFF point The hot key provides direct access to the Set Point and Alarm settings The Set Point and Alarm settings that are displayed are based upon the Control CtrL menu item Remote Site P...

Страница 10: ...SP2H and SP2L control relay 2 pump 2 There is no alternating function If lead lag feature is turned on then the relays will alternate with set points SP1H and SP1L to SP2H and SP2L with every cycle of set points The Last relay turned off will be last relay turned on with the next cycle On the first cycle on increase of pressure assuming direct acting the SP1 relay pump 1 will come on and then on f...

Страница 11: ...2 3 PROGRAMMING CHART MENU MAP HOME MAIN MENUS ITEMS SETTINGS Remote Site Products 1 888 532 2706 www remotesiteproducts com http www remotesiteproducts com p 14328 Dwyer Mercoid EDAW N1E1 06T0 Pressure C ...

Страница 12: ...TEMS PRESENT WHEN CtrL SET TO 1SP 2SP OR SPAL ITEMS PRESENT WHEN CtrL SET TO 2SP ITEMS PRESENT WHEN CtrL SET TO SPAL Remote Site Products 1 888 532 2706 www remotesiteproducts com http www remotesiteproducts com p 14328 Dwyer Mercoid EDAW N1E1 06T0 Pressure C ...

Страница 13: ...11 HOME SEE PAGE 17 MAIN MENUS ITEMS SETTINGS Remote Site Products 1 888 532 2706 www remotesiteproducts com http www remotesiteproducts com p 14328 Dwyer Mercoid EDAW N1E1 06T0 Pressure C ...

Страница 14: ...smitter output function FAIL Failsafe Menu Set the relay and transmitter outputs to certain preset values when failsafe conditions occur Error codes will show on the display indicating the problem User chooses if relay is de energized energized or no action taken With transmitter option user chooses an output of 3 6 mA 22 mA or no action taken Menus and Values SECr Security Menu SECr When the secu...

Страница 15: ... is less than 5 of full scale bCLt Backlight ON Backlight always on OFF Backlight always off 30 Backlight stays on for 30 minutes 10 Backlight stays on for 10 minutes 5 Backlight stays on for 5 minutes 2 Backlight stays on for 2 minutes PSI 14 70 20 00 60 0 100 0 150 0 300 0 600 1000 1500 3000 6000 8000 KG CM2 1 033 1 406 4 22 7 03 10 55 21 09 42 2 70 3 105 5 210 9 422 562 BAR 1 013 1 379 4 14 6 8...

Страница 16: ... only activated when CtrL is set to 2SP 2SP SP2 Set Point 2 Reverse or Direct Acting DIR Direct Relay turns on with increasing pressure REV Reverse Relay turns on with decreasing pressure DEL2 SP2 Set Point 2 time delay Sets the amount of time a set point condition must be continuously met before the set point condition is recognized The DEL2 delay is adjustable from 0 60 seconds LEd2 SP2 Set Poin...

Страница 17: ...m only LOW Low alarm only HILO For a high and low guard band type alarm Share the same relay output Alarm Adjustment Alarm settings are dependent upon the selected alarm type The EDA pressure controller alarm may be configured as a High Alarm Low Alarm or High Low Alarm Alarm settings may be set to anywhere within the range of the instrument The dead bands of the alarms are fixed at 1 of full scal...

Страница 18: ...r the 4 mA output May be set from 2 below minimum scale up to POH POH Process Output High Set to the desired display reading for the 20 mA output May be set from POL to 2 above maximum scale CAL ZERO Zero Calibration DO NOT apply any pressure when performing this function With the display reading CAL ZERO press the E key The upper display will blink Press the E key again to complete the zeroing of...

Страница 19: ...on The NO contacts will be closed and the NC contacts will be opened NORM No change applied to the relay upon failsafe condition OUtP sets the transmitter output option failsafe condition for a unit with the output option of 4 to 20 mA 0 5 VDC 0 10 VDC 1 5 VDC or 1 6 VDC See below chart of transmitter output action according to output signal type OUtP Transmitter Output Failsafe Condition LOW Tran...

Страница 20: ...s and Conditions of Sales in our catalog and on our website Contact customer service to receive a Return Goods Authorization number before shipping the product back for repair Be sure to include a brief descrip tion of the problem plus any additional application notes Display Err1 Err2 Err3 Err4 Err5 Meaning Low temperature limit A temperature below 0 F has been applied to the sensor High temperat...

Отзывы: