15
The following alarm function menu items are activated when
CtrL
is set to
SPAL
:
DELA
Alarm Delay
Sets the amount of time an alarm condition must be continuously met before the alarm condition is
recognized. The alarm delay is adjustable from 0 - 60 seconds.
LEdA
Alarm Lamps
OFF
The
ALLO
LED or
ALHI
LED on the front panel turns OFF when the alarm relay
turns OFF. The
ALLO
LED or
ALHI
LED on the front panel turns ON when the
alarm relay turns ON.
ON
The
ALLO
LED or
ALHI
LED on the front panel turns ON when the alarm relay
turns OFF. The
ALLO
LED or
ALHI
LED on the front panel turns OFF when the
alarm relay turns ON.
AL
Alarm Type (see Alarm Adjustment below)
HIGH
High alarm only.
LOW
Low alarm only.
HILO
For a high and low guard band type alarm. Share the same relay output.
Alarm Adjustment
Alarm settings are dependent upon the selected alarm type. The EDA pressure controller alarm may be configured
as a High Alarm, Low Alarm, or High/Low Alarm. Alarm settings may be set to anywhere within the range of the
instrument. The dead bands of the alarms are fixed at 1% of full scale.
ALrE
Alarm Reset
AUTO
Automatic reset.
HOLD
Manual reset. An alarm is reset by pressing the
RST
key on the front panel.
ALiH
Low Alarm Inhibit
OFF
Alarm inhibit is off.
ON
Alarm inhibit is on.
Note:
If
ALiH
is selected ON, a low alarm condition is suspended upon power up until the process value passes
through the alarm set point once.