The heater must be positioned in  a special heater room,  compatible  with  a boiler  room, and 
generally in such a way that the cold air is not taken from fire hazardous rooms. In addition to 
a  fire  damper,  the  hot  air  duct  must  be  fitted  with  an  over-pressure  grating,  which  stops 
airflow in the direction of the heater.  
 
In such mechanically ventilated rooms where some hot steam and gas occurs and where there 
generally  is  not  any  handling  and  technical  use  of  burning  fluids,  such  as  garages,  service 
station halls, and repair shops, the heater can be in the heated room, if it is positioned at least 
2 m off the floor and the cold air is not taken from lower than that. The combustion air must 
be taken from the outside or from at least 2 m off the floor.  
 
For inspection and maintenance purposes, a ladder and a maintenance platform (if necessary) 
must be available, if it is not possible to perform inspections and maintenance works on the 
floor level.  
 
If the heater is used in paint shops, the positioning of the heater must be in accordance with 
the standard SFS 3358, regardless of its scope of application.  
 
 

Fixed heater’s flue  

 
The  flue  of  a  fixed  heater  must  be  in  accordance  with  the  rules  and  regulations  regarding 
flues.  
 
The flue must be fitted  with  a cover of such structure that no over-pressure can form  in  the 
flue, and it must be possible to open the cover easily for cleaning the flue, unless the flue can 
be cleaned from underneath.  
 

THE FUEL TANKS OF OIL-HEATED DEVICES  

 
The oil tank as well as the suction and return pipe should be in accordance with the oil heating 
equipment decree and any regulations based on it. 
 
In equipment covered by the scope of application of this regulation, the following can also be 
used as fuel tanks: mobile oil tanks or detachable tanks which can be fitted with a pump. The 
tank must be positioned within at least 3 m from the burner. The oil pipes must be metal oil 
pipes,  or  steel-enforced  oil  pipes,  or  oil  pipes  intended  for  moving  oil.  When  using,  the  oil 
pipes must be attached to the oil tank so that they would not come loose. 
 

INSTALLATION AND MAINTENANCE 

 
When installing and performing maintenance on these spray oil burner devices, the oil heating 
equipment decree is followed, so these devices can only be installed by authorised installation 
and maintenance companies. 
 
Maintenance  on  the  oil  heating  devices  of  mobile  heaters,  except  adjustment  and  safety 
devices, can be performed by the person responsible for the use of the devices. 
 
 

Содержание EKI 125

Страница 1: ...tie 59 21900 Yl ne Ph 02 275 4444 mepu mepu com www mepu com EKI 30 125 INSTALLATION AND USER MANUAL GEBRAUCHS UND INSTALLATIONSANLEITUNG MEPU OY Myn m entie 59 FIN 21900 YL NE ph 02 275 4444 www mepu...

Страница 2: ...i 30 125 Revisiohistoria Revisio Tekij P iv ys Muutos 0 1 Jarkko Marttila 24 2 2011 Dokumentti luotu 2 0 Jarkko Marttila 17 4 2012 Ilme muutettu ja ce p ivitetty 1 2012 Jarkko Marttila 1 6 2012 K nnet...

Страница 3: ...oning 3 1 3 Starting 4 1 4 Stopping 4 1 5 Malfunction 4 1 6 The location of the devices 4 2 Deutsch 6 2 1 Installation 6 2 2 Platzierung 6 2 3 Inbetriebsetzung 7 2 4 Abschaltung 7 2 5 St rung 7 2 6 Ge...

Страница 4: ...If the heater is positioned in a warehouse or a factory it has to be surrounded by a safety rail made of steel pipe or other suitable material with the pipe diameter being at least 50 mm and the thic...

Страница 5: ...g according to the burner s user manual or call your nearest Oilon maintenance company 1 6 The location of the devices Using a fixed heater in a non fire hazard or non explosive room It is usually pos...

Страница 6: ...he flue of a fixed heater must be in accordance with the rules and regulations regarding flues The flue must be fitted with a cover of such structure that no over pressure can form in the flue and it...

Страница 7: ...der aus Stahlrohren oder einem entsprechenden Material befinden dessen Rohrdurchmesser mindestens 50 mm und dessen Wandst rke mindestens 2 mm betragen Das Schutzgel nder muss in einer Entfernung von 1...

Страница 8: ...tur des Hochofens unter 40 C sinkt 2 5 St rung Lesen Sie im Betriebshandbuch des Brenners die m gliche Fehlerdiagnose nach oder rufen Sie den n chsten Oilon Service an 2 6 Gebrauchsorte der Ger te und...

Страница 9: ...destens 2 m H he ausgehend von der Bodenebene genommen werden F r die berpr fung und die Wartung des Warmluftentwicklers m ssen eine Leiter und bei Bedarf eine Wartungsebene zur Verf gung stehen wenn...

Страница 10: ...er Verordnung entsprechend mit einem Spr h l Brenner ausgestattet worden sind wird die Verordnung f r lheizger te befolgt so dass die Apparaturen nur von bewilligten Installations und Wartungsbetriebe...

Страница 11: ...M 300 1300 1000 3200 2000 4000 2000 7000 Height mm H he mm 1135 1380 1760 2310 Width mm Breite mm 388 437 652 975 Depth mm Tiefe mm 567 778 1030 1115 Weight kg Gewicht kg 65 115 250 315 Filter Filter...

Страница 12: ...1 6 2012 Ver 1 0 11 Eki 30 125...

Отзывы: