IMPORTANT VENTING CONFIGURATION NOTES 

See Figure 11 [MASTER FLUE VENTING REQUIREMENTS CHART AND TABLE FOR LPG APPLICATIONS]. 

HIGH ALTITUDE INSTALLATION INFORMATION

: Prior to installing at altitudes higher than 7500, please contact the 

Mendota technical service department for specific venting requirements and venting restrictions. 

MAXIMUM HORIZONTAL RUN 

Maximum Horizontal Run allowed is 32 feet if a vertical starter section that is between 4 feet to 10 feet is connected di-
rectly to this firepla

ce’s flue starter collar and no more than one (1) 90 degree elbow is used.  

Maximum Horizontal Run allowed is 6” if an 18” vertical starter section is connected directly to this fireplace’s flue starter 
collar. 

MAXIMUM VENT SYSTEM LENGTH 

Combined total length of all straight pipe sections in the vent system shall be less than 42 feet. 
Combined total length of all straight pipe sections in the vent system shall be less than 42 feet when using three (3) 90-
degree elbows or equivalent and terminating the vent 

system horizontally in Zone “B”. 

Combined total length of all straight pipe sections in the vent system shall be less than 42 feet when using four (4) 90-
degree elbows or equivalent and terminating vertically. 

HOW TO CALCULATE THE VENT SYSTEM LENGTHS 

For calculation purposes and usage of charts in this manual, simply add the lengths of all individual straight pipe sections. 
For example: if you use two 2-foot lengths and one 4-foot length, the total vent system length will be 2+2+4 = 8 feet. 

USING 90

0

 ELBOWS 

IN ZONE “B” 

The ML47 Fireplace by MENDOTA allows maximum flexibility in the use of 90

o

 elbows in the vent system.  The length of 

the first straight vertical section directly connected to the fireplace’s starter collar determines the maximum horizontal run 
and the number of 90

0

 elbows allowed for this fireplace. 

For vent systems that provide a starting vertical section that is 4 feet or longer, you may connect up to 32 feet of horizon-
tal pipe.  For each 90

o

 elbow installed after the first 90

o

 elbow on top of the first 4 ft. section connected to the starter color 

of this fireplace, reduce maximum allowed horizontal run by 4 feet. 

USING 90

o

 

ELBBOWS IN ZONE “A”. 

For vent systems that provide a starting vertical section less than 4 feet, the following rules apply: 
a. You must use the Master Flue Venting Requirements Chart. See Zone “A” below the 4’ vertical run line. 
b. A single 90

º

 vertical-to-horizontal elbow is already calculated into the allowable maximum 32' horizontal run. The Vent-

ing Requirements Chart (Figure 11) assumes that for all horizontal runs calculated, one 90

0

 elbow is used within the vent-

ing system. 

Each additional 90

º

 elbow reduces the maximum horizontal distance by 4'.

 

c. If you plan to use more than one 90

0

 elbow within the vent system, first use the Venting Requirements Chart (Figure 13) 

and calculate the maximum horizontal run you are allowed based on the first vertical section connected directly to the fire-
place.  From this maximum horizontal run calculated, subtract 4 feet for each additional 90

0

 elbow you will use. 

Example 1:

  Assume you are using a 3 feet long starter vertical section.  This should allow, per figure 13, 19 feet of hori-

zontal run.  If you want to use three 90

0

 elbows, subtract 8 feet for two elbows from the 19 feet maximum allowed [4 feet 

for each elbow after the first elbow].  This yields 11 feet as the maximum horizontal run that you are allowed to install us-
ing the 3 foot vertical starter section. 

CAUTION:

  If a vertical-to-horizontal discharge elbow or a horizontal-to-horizontal discharge elbow is enclosed within a 

wall, floor or ceiling, a top air space clearance of 3" must be maintained above the elbow body. 

USING 45-DEGREE ELBOWS 

Two 45-degree elbows may be used in place of one 90-degree elbow. On 45-degree runs, one foot of diagonal pipe is 
equal to 8-1/2 inches horizontal run and 8-1/2 inches vertical run.  Two 45-degree elbows may be connected directly to 
the vent starter adapter on this fireplace to create an offset to provide the required clearances to combustible framing or 
sheathing materials. 
Two 45-degree elbows may be connected directly to the top of this fireplace to create a horizontal offset.  20 feet maxi-
mum horizontal run allowed with this offset configuration only if the first vertical section connected directly to the last 45-
degree elbow is more than 4 feet long.  For maximum allowable horizontal distances with the 45-degree offsets, see the 
Master Venting Configuration Chart. 

Note: 

 Each horizontally positioned 45

º

 elbow reduces the maximum horizontal distance by 1½ '. 

SUPPORT:

  Horizontal runs of pipe will require one vent support for every 3 ft. of pipe. 

 

Содержание ML47-PF2

Страница 1: ...Installation and service must be performed by a qualified installer service agency or the gas sup plier WARNING Do NOT use this appliance if any part has been under water Immediately call a qualified...

Страница 2: ...l appareil et remplacer toute partie du syst me de contr le et toute commande qui ont t plong s dans l lau In the Commonwealth of Massachusetts Installation must be performed by a licensed plumber or...

Страница 3: ...nstaller une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou un po le installez une barri re de s curit cette mesure emp chera les tout petits les jeune...

Страница 4: ...20 RAISED HEIGHT INSTALLATION OF ML47 21 How to determine the proper installed height of this fireplace 21 INSTALLATION OF FLAT PANEL TV ON TOP OF ML47 22 ENAMEL PANORAMIC LINER AND FLOOR PLATE INSTA...

Страница 5: ...ENTS 44 LOCATION OF MASTER SWITCH AND SYNC SWITCH 45 Remote Control Transmitter Functions 46 REMOTE TRANSMITTER OPERATING INSTRUCTIONS 47 FIRST TIME PILOT LIGHTING INSTRUCTIONS 49 IPI STANDING PILOT S...

Страница 6: ...e Building Code A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust v...

Страница 7: ...SIONS OVERALL APPLIANCE DIMENSIONS AND FEATURES Removable Cover Plate for Plumbing Electrical Access before unit is placed inside framed cavity Replace Lower Cover Plate before sliding unit into frame...

Страница 8: ...em 120VAC 2 Amps Dedicated Hot Power only No switches Fan Speed Controls or Light Dimmers are allowed in the same AC supply circuit Optional fans are controlled using re mote control ACCENT LIGHT SYST...

Страница 9: ...T TO FLOOR 0in 0mm GLASS EDGE TO ADJACENT SIDEWALL 16in 406 mm UNIT TO ENCLOSURE SIDEWALL 1 2in 13mm VENT PIPE TOP TO COMBUSTIBLES 3in 76mm UNIT TO ENCLOSURE BACK WALL 1 2in 13mm VENT PIPE SIDES TO CO...

Страница 10: ...be required due to excessive lint from carpeting bedding material carbon build up etc It is imperative that control com partments burners and circulating air passageways of the appliance be kept clean...

Страница 11: ...4 1 4 39 19 1 2 6 1 1 1 6 7 5 1 6 8 6 5 5 1 6 4 1 1 1 6 4 1 2 1 1 1 0 9 8 7 6 3 5 1 6 2 1 1 1 6 2 1 5 1 6 1 1 1 6 1 2 3 4 5 0 0 A P P R O V E D M A N TE L P R O FILE D IS TA N C E FR O M FIR E P LA C...

Страница 12: ...n Air Opening note that the Top of the convection air opening is 30 inches up from the floor level of this fireplace WARNING Make proper use of this chart Do not compromise the specifications containe...

Страница 13: ...front surface of the visible glass door and if perpendicular to the front sur face of the glass door must be located a minimum of 16 from the side edge of the visible glass door Figure 2 Clearances to...

Страница 14: ...nd ceiling fan are desired Selecting Appliance Location When selecting a location for your appliance it is important to consider the required clearances to adjacent side walls Figure 3 Planning Instal...

Страница 15: ...for the requirements of local building codes Local building codes MUST be adhered to Chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems T...

Страница 16: ...temporary guides and are to be used to position the finishing materi al s edges adjacent to the top sides and bottom convection air gap around the glass frame Use the Inner Guide if you installing onl...

Страница 17: ...ace s rectangle profile must extend out from the face surface of this fireplace 1 inch if the 19 1 2 framing depth is used and the Inner or Outer Finishing Guides are utlizied A MAXIMUM THICKNESS OF 2...

Страница 18: ...fety Screen For the Traditions Front use the inner guides or use your selection of Metallic tile edging Willowbrook Front Only The Willowbrook Front is approximately the overall size of the viewing gl...

Страница 19: ...the rough framing depth and the Outer Adjustable Framing Brackets With Final Finishing Material mounted behind the Grace by using the inner guides the Grace can be mounted only as close as the Final...

Страница 20: ...th the Grace Front s visible sur face if the Final Finishing Material is less than and the Adjustable Framing Brackets are employed properly Final Finishing Material mounted outside the Grace Front us...

Страница 21: ...t cap spanning 36 wide centered over the vent cap and spanning the full depth of the sof fit spaced 1 down from the soffit surface using tubular spacers or stacked washers This metal shield allows you...

Страница 22: ...bottom edge of the TV cavity as much as possible beyond the 18 minimum requirement Higher up means a cooler TV You MUST create a recessed 5 deep cavi ty to house the TV NEVER mount any TV above this...

Страница 23: ...r Mocha Metallic and Silver Metallic attractive colors You must select one col ored Panoramic Panel Kit and install it before any test firing of this appliance The specific color kits and its correspo...

Страница 24: ...ingle gang box with the height of other AC outlets that are installed in the same room as this appliance WARNING DO NOT STAPLE the 6 DC Power Inlet Harness to the wall studs COVER PLATES Two cover pla...

Страница 25: ...stalled at a minimum of 14 above the heat outlet 39 up from the floor level of this fireplace and no more than 8 out from wall at that height Non combustible marble brick stone etc mantels can be inst...

Страница 26: ...PIPE LENGTH FEET SCHEDULE 40 PIPE INSIDE DIA TUBING TYPE L OUTSIDE DIA NAT L P NAT L P 0 10 1 2 1 3 cm 3 8 1 0 cm 1 2 1 3 cm 3 8 1 0 cm 10 40 1 2 1 3 cm 1 2 1 3 cm 5 8 1 6 cm 1 2 1 3 cm 40 100 1 2 1 3...

Страница 27: ...his table GAS PRESSURE REQUIREMENTS NOTE For altitudes above 2 000 feet some variations in air shutter settings may be required Figure 6 Gas Valve Pressure Test Ports Manifold pressure must be taken a...

Страница 28: ...the 30 minutes of burn time Write the reading here Final Gas Meter Reading _______________ Calculate the following FINAL GAS METER READING INITIAL GAS METER READING Subtract Initial Gas Meter from Fin...

Страница 29: ...n prepare the rough opening using framing dimensions Be sure to also prepare opening to allow for co axial vent 2 Check to make certain all venting requirements and locations are being followed 3 This...

Страница 30: ...e its own separate vent system Common vent systems are prohibited To assure proper venting performance of this high performance Mendota Direct Vent Fireplace it is critical that all brands of vent pip...

Страница 31: ...terminal 18 47 cm min K Clearance to a mechanical air supply inlet 6 feet 1 8 m minimum E Clearance to unventilated soffit 18 min 46 cm min L Clearance above paved side walk or a paved driveway locat...

Страница 32: ...DESCRIPTION 1 6 or 7 PIPE DuraVent 6 Amerivent 7 2 12 VENT STACK 3 24 VENT STACK 4 36 VENT STACK 5 48 VENT STACK 6 90 GALVANIZED ELBOW 45 GALVANIZED ELBOW 7 ADJUSTABLE WALL THIMBLE not shown 8 ATTIC I...

Страница 33: ...is 4 In Zone A 32 feet maximum horizontal run allowed with a 4 feet starter section for NG and 27 feet maximum horizontal for LPG If the starter vertical section is less than 4 feet use the chart and...

Страница 34: ...ertical section less than 4 feet the following rules apply a You must use the Master Flue Venting Requirements Chart See Zone A below the 4 vertical run line b A single 90 vertical to horizontal elbow...

Страница 35: ...E T R IP L E 9 0 E L B O W S H O R IZ O N T A L T E R M IN A T IO N V E R T IC A L R IS E T R IP L E 9 0 E L B O W S V E R T IC A L T E R M IN A T IO N T H R E E H O R IZ O N T A L D IS C H A R G E 9...

Страница 36: ...x 10 3 4 high opening in the wall The hole must be positioned so the vent system will run level or have a rise per foot of run AND be perpendicular to the wall The height of the opening must be locate...

Страница 37: ...netrate the outside wall See Figure 13 Be sure all vent components are properly twist locked and leak proof Be sure 1000 sealant is used in the inner pipe joints of all pipe sections manufactured by S...

Страница 38: ...ft 30 in 9 ft 36 in 15 ft 42 in 21 1 2 ft 48 in 28 ft 4 ft 10 ft 28 ft 10 ft 40 ft Varies V1 min H1 H2 max V2 MAX 24 in 2 ft 10 ft 30 in 9 ft 10 ft 36 in 15 ft 10 ft 42 in 21 1 2 ft 10 ft 48 in 28 ft...

Страница 39: ...oints DuraVent only are sealed and are leak proof Maintain 1 airspace clearances to combustibles 2 above horizontal runs Cut a 10 x 10 opening in the roof centered in the small drilled hole placed in...

Страница 40: ...e V1 min H max V2 max 18 in 6 in 38 1 2 ft 24 in 6 ft 34 ft 30 in 13 ft 27 ft 36 in 19 ft 21 ft 42 in 25 1 2 ft 14 1 2 ft 48 in 32 ft 10 ft 4 ft 10 ft 32 ft Varies 10 ft 40 ft Varies Varies Figure 19...

Страница 41: ...starter section connected directly to the top of this fire place Prerequisite 3 For vertical starter sections less than 4 feet tall you must reduce 6 feet off the maximum horizontal run allowed per F...

Страница 42: ...bs that protrude downward on the bot tom left and right corners of glass frame Identify a rec tangle slot on the bottom right and left corners of firebox opening sides Carefully line up the bottom cor...

Страница 43: ...Check Off List see above must be completed Check for gas leaks and gas pressures prior to installing facing materials Install fresh batteries in remote transmitter Follow Initializing the System for...

Страница 44: ...burner media are positioned properly For Natural Gas applications air shutter shall be 1 8 open For LPG applications start with air shutter open to 3 8 After burner has been properly installed and ope...

Страница 45: ...actuate the two switches The Master Switch must be ON for the pilot flame and burner flames to activate The SYNC switch is to be used initially when mating the remote transmitter with the receiver lo...

Страница 46: ...o F above the Set Point Temperature To increase the Set Point Tem perature Press the UP button until the desired temperature is displayed in the SET POINT TEMPERATURE window The fan will turn on 5 mi...

Страница 47: ...guish If in Standing Pilot Mode the pilot light will remain ON Note If in SMART model the flame height function is not available for manual adjustment In SMART mode the flame height regulates automati...

Страница 48: ...d the number of ignitions of the appliance the number of changes to the room thermostat set point etc When the Transmitter batteries are low a Battery Icon will appear on the LCD display of the Transm...

Страница 49: ...oor WARNING NEVER IGNITE MAIN BURNERS WITH GLASS DOOR REMOVED OR OPEN Doing so will lead to damage to pilot flame sensor and spark electrode wire leads Press the ON OFF button on Transmitter to ON All...

Страница 50: ...ot light then uses the pilot light to ig nite the main burners The pilot light can be set in the CPI Standing Pilot mode to allow the pilot light to remain on indef initely by setting the Remote Trans...

Страница 51: ...he pilot light flame Use the IPI mode instead during summer months CLEANING VIEWING GLASS The viewing glass should be cleaned periodically Exterior glass surface may be cleaned with cleaner as desired...

Страница 52: ...y C Periodically check to verify that the vent system and vent cap are open and free of blockage D Before re installing glass have qualified service person check the operation of the pilot and cycle t...

Страница 53: ...r plate remove main burner Locate two access plates on the left and right side of firebox floor See diagrams below Unscrew seven outer screws and lift entire left or right cover plate assem bly which...

Страница 54: ...ce and the Valve Pressure Regulator This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requirements of...

Страница 55: ...lator in place Tighten down 3 Remove the Burner Locate and Identify the Burner Orifice Spud The Orifice Spud can be removed and installed using a hex wrench WARNING Make certain to Secure the Brass fi...

Страница 56: ...or failure to use only parts specifically ap proved with this appliance may result in property damage or personal injury AVERTISSEMENT Risque de dommages ou de blessures si les pi ces ne sont pas inst...

Страница 57: ...mended that all gas plumbing joints factory installed and field installed are checked for leaks Figure 21 Pressure Test Port PILOT FLAME AND MAIN BURNER RELATIONSHIP VERIFICATION Prior to completing...

Страница 58: ...ou are derating this appliance at a high altitude also attach the High Altitude Deration Label supplied in the Owner s Manual Packet to this same surface Prior to attaching the labels fill in all the...

Страница 59: ...ALVE ASSEMBLY REPLACEMENT PARTS LIST ITEM QTY PART NUMBER DESCRIPTION 1 1 05 04 00062 Pilot Assembly 2 2 65 14 00180 ORIFICE 1 8 3 1 HA 90 00004 Proflame Valve Assembly with fittings 4 1 55 02 00070 T...

Страница 60: ...ical Code Caution Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and danger ous operation and Verify proper operation after servicing Attention Au mome...

Страница 61: ...nts are available through Johnson Gas Appliance Company Con tact your dealer for more detailed ordering information Figure 24 GLASS FRAME ASSEMBLY HA 90 00102 REPLACEMENT PARTS LIST ITEM PART NUMBER D...

Страница 62: ...ound on the rating plate which is located in the air gap below the glass frame near the center When contacting your dealer for any cleaning service or warranty service always provide the Model Number...

Страница 63: ...63 P a g e THIS PAGE LEFT BLANK INTENTIONALLY...

Страница 64: ...64 P a g e THIS PAGE LEFT BLANK INTENTIONALLY...

Страница 65: ...ocked and leak proof Check minimum and maximum vertical horizontal and vent runs 1000 sealant must be used on inner joints at adjustable pipe sections CHECK FOR PROPER CLEARANCES TO COMBUSTIBLES VENT...

Страница 66: ...66 P a g e TAPE SHUT JOHNSON GAS APPLIANCE COMPANY 520 E AVENUE N W CEDAR RAPIDS IA 52405 POSTAGE NEEDED...

Страница 67: ...ases that have not received prior written approval from Mendota NOTE Minor warping of certain parts or discoloration is normal and is not a defect covered by this warranty Major warping of parts can b...

Страница 68: ...68 P a g e Johnson Gas Appliance Company 520 E Avenue N W Cedar Rapids IA 52405 Mendota Hearth Division WEBPAGE www johnsongas com or www mendotahearth com 85 03 00923...

Отзывы: