
85-03-01109
FV42
Page
63
Zero Rise Horizontal Termination
The FV42 Fireplace must be installed by a qualified Mendota approved serviceperson.
A maximum horizontal run of 12” is allowed if a 9” vertical starter section and one 90° elbow is connected directly to this
fireplace’s flue starter collar. The horizontal centerline of the 90
º
elbow will be 46
⅜
” up from the floor level of this fireplace.
See, MASTER VENTING CHART and Figures, below.
Use "fixed" pipe sections in place of adjustable pipe sections
wherever possible.
Always maintain 1" clearance from vent pipe sides and bottom
to combustibles, 3" clearance on top of pipe on horizontal runs
and on top of horizontal discharge elbows. Do not fill air spaces
with insulation or other material.
Position fireplace in desired location. See guidelines on proper
vent cap placement on the exterior of home. Check to
determine if wall studs are in the way when venting system is
attached. If this is the case, you may want to adjust the
fireplace location or modify the exterior wall framing to allow
the vent system to penetrate the wall.
Measure from the floor level of the fireplace up 46-3/8” inches
[add ¼” rise for every foot of horizontal run] and mark wall
directly at the center of where the vent pipe will penetrate the
exterior wall.
Cut and frame a 10-3/4" wide x 10-3/4" high opening in the
wall. The hole must be positioned so the vent system will run
level or have a ¼" rise per foot of run AND be perpendicular to
the wall.
The height of the opening must be located to meet all local and national building codes. Do not allow the termination to be
easily blocked or obstructed. If wall being penetrated is non-combustible material, i.e. masonry block, brick, etc., a 9-inch
diameter hole is acceptable.
Attach the 9” straight section to the fireplace starter adapter. Attach a 90° elbow to the top of the 9” vertical starter section
and rotate and lock in position. Attach a horizontal section to the 90° elbow. Be sure all vent component connections are in
their fully twist-locked position and are leak-proof.
The length of the horizontal piece that fits through the wall will be determined by the location of the fireplace relative to the
wall. For a normal installation where this fireplace is installed directly against an exterior wall constructed using 2x4 lumber or
2x6 lumber, only a 6” horizontal section is required.
There
must be a minimum
of 1" air space clearance to combustibles from all vent components (3" above horizontal runs and
horizontal discharge elbows).
A wall thimble must always be used when penetrating combustible wall materials.
From the exterior of the home, slide the horizontal vent cap over the end of the horizontal pipe and tightly secure the cap to
the wall with screws. Seal with a high-quality caulking.
NOTE:
Combustible wall thickness must be 4" to 8" maximum
NOTE:
Vent Cap should not be recessed into wall or siding.
Figure 4-18 VENT CENTERLINE
Содержание FV42
Страница 15: ...85 03 01109 FV42 Page 15 Figure 3 11 Figure 3 10...
Страница 87: ...85 03 01109 FV42 Page 87 Gas Train Assembly Parts Figure 6 5 Gas Train Assembly Parts...
Страница 88: ...85 03 01109 FV42 Page 88 Burners Figure 6 6 Burners...
Страница 95: ......
Страница 96: ...Johnson Gas Appliance Company 520 E Avenue NW Cedar Rapids Iowa 52405 Mendota Warranty Registration...