5 | 

P a g e

 

 

Specific Requirements for the Common Wealth of Massachusetts 

The information in this section applies to all installations performed in the Common Wealth of Massachusetts only. 

a) 

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure 
used in whole or in part for residential purposes and where the side wall exhaust vent termination is less than 
seven (7) feet above grade, the following requirements shall be satisfied: 

1.  If there is no carbon monoxide detector with an alarm already installed in compliance with the most cur-

rent edition of NFPA 720, NFPA 70 and the Massachusetts State Building code in the residential unit 
served by the side wall horizontally vented gas fueled equipment, a battery operated carbon monoxide 
detector with an alarm shall be installed in compliance with the most current edition of NFPA 720. NFPA 
70 and the Massachusetts State Building Code. 

2.  In addition to the above requirements, if there is not one already present, a carbon monoxide detector 

with an alarm and a battery backup shall be installed and located in accordance with the installation re-
quirements supplied with the detector on the floor level where the gas equipment is installed.  The carbon 
monoxide detector with an alarm shall comply with 527 CMR, ANSI/UL 2034 Standards or CSA 6.19 and 
the most current edition of NFPA 720.  In the event that the requirements of this subdivision cannot be 
met at the time of the completion of the installation of the equipment, the installer shall have a period of 
thirty (30) days to comply with this requirement; provided, however, that during said thirty (30) day period, 
a battery operated carbon monoxide detector with an alarm shall be installed in compliance with the most 
current edition of NFPA 720, NFPA 70 and the Massachusetts State Building Code.  In the event that the 
side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the carbon 
monoxide detector may be installed on the next adjacent habitable floor level.  Such detector may be a 
battery operated carbon monoxide detector with an alarm and shall be installed in compliance with the 
most current edition of NFPA 720, NFPA 70 and the Massachusetts State Building Code. 

3.  A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a min-

imum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally 
vented gas fueled heating appliance or equipment.  The sign shall read, in print size no less than one-half 
(1/2) inch in size, “GAS VENT DIRECTLY BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS” 

4.  A final inspection by the state or local gas inspector of the side wall horizontally vented equipment shall 

not be performed until proof is provided that the state or local electrical inspector having jurisdiction has 
granted a permit for installation of carbon monoxide detectors and alarms as required above. 

 

(b) 

EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2) (a) 1 through 4: 

1.  The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current 

edition of NFPA 54 as adopted by the Board; and 

2.  Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure sepa-

rate from the dwelling, building or structure used in whole or in part for residential purposes. 

(c)  

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting 
system design or venting system components with the equipment, the instructions for installation of the 
equipment and the venting system shall include: 
1.  A complete parts list for the venting system design or venting system; and 

2.  Detailed instructions for the installation of the venting system design or the venting system components. 

(d) When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not 

provide the parts for venting the flue gases, but identifies “special venting systems”, the following shall be sa-
tisfied: 

1.  The referenced “special venting system” instructions shall be included with the appliance or equipment in-
stallation instructions; and 

2.  The “special venting systems” shall be Product Approved by the Board, and the instructions for that sys-
tem shall include a parts list and detailed installation instructions. 

(e) 

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equip-
ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall 
remain with the appliance or equipment at the completion of the installation. 

Содержание FV41-M

Страница 1: ...ation and service must be performed by a qualified installer service agency or the gas suppli er WARNING Do NOT use this appliance if any part has been under water Immediately call a qualified service...

Страница 2: ...de gas indiqu s sur la plaque signal tique Ne pas l utiliser avec d autres gas sauf si un kitde conversion certifi est install SAFETY AND WARNING INFORMATION READ and UNDERSTAND all instructions caref...

Страница 3: ...rri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou un po le installez une barri re de s curit cette mesure emp chera les tout petits les jeunes en fants et t...

Страница 4: ...UIREMENTS 19 GENERAL INSTALLATION INSTRUCTIONS 20 GENERAL FLUE VENTING INSTRUCTIONS 21 EXTERIOR VENT LOCATIONS AND RESTRICTIONS 22 FLUE VENTING COMPONENTS IDENTIFICATION 23 FV41 M MASTER FLUE VENTING...

Страница 5: ...Building Code 3 A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a min imum height of eight 8 feet above grade directly in line with the exhaust...

Страница 6: ...LET CONTROLS HARNESSES EXIT GAS SUPPLY INLET 1 2 MNPT GAS TRAIN IGNITION SYSTEM RH BLOWER INSPECTION COVER LH FRAMING ATTACH BRACKETS LH LIFT HANDLE RH FRAMING ATTACH BRACKETS RH BLOWER INSPECTION COV...

Страница 7: ...LES 1in 25mm UNIT BOTTOM TO ENCLOSURE CEILING 48 1 2in 123 cm VENT PIPE BOTTOM TO COMBUSTIBLES 1in 25mm UNIT BOTTOM TO ROOM CEILING 72 in 1829 mm 8 MANTLE ABOVE DISCHARGE AIR OPENING 18 in 457 mm MINI...

Страница 8: ...onal service person More frequent cleaning may be required due to excessive lint from carpeting bedding material carbon build up etc It is imperative that control com partments burners and circulating...

Страница 9: ...TEL 48 ADJACENT WALLS A wall perpendicular to and in front of this fireplace s glass door surface must be at least 16 inches from the side edges of the facing guide A wall at 45 to the glass surface a...

Страница 10: ...ace Face the combustible mantel may pro trude outward at a Distance up From Floor Level of this Fireplace If you prefer to take measurements from the Top of the Convection Air Opening note that the To...

Страница 11: ...11 P a g e CLEARANCES TO COMBUSTIBLES FROM APPLIANCE SURFACES Figure 2 Clearances to Combustibles 0 CLEARANCE FROM TOP STANDOFFS 1 2 CLEARANCE FROM BACK 1 2 CLEARANCE FROM SIDES...

Страница 12: ...surfaces extending full width and depth of this fireplace An R 1 Rated Hearth Protection Pad 1 1 2 Thick Maximum is required unless this fireplace is elevated For every 1 this fireplace is elevated y...

Страница 13: ...ST be adhered to Chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems The chase should not break the outside building envelope in any manne...

Страница 14: ...not needed or may be permanently attached using 1 8 rivets that are supplied with this fireplace Inner Guide Identify the Inner Finishing Guides Top Left and Right These guides should be used as a gu...

Страница 15: ...rface Install 1 2 thick drywall on framing members so that its outer surface is flush with the front face of this fireplace Attach Marble or Granite slabs to face of unit and to drywall surface using...

Страница 16: ...floor level and the ceiling All hearth pads must be non combustible metal brick stone or mineral fiberboard Do not use any combustible material to protect the floor in front of this fireplace For the...

Страница 17: ...of the hearth protector may be reduced by 2 inches If fireplace is raised off the floor 6 or more no hearth protector is required HEATING PERFORMANCE With its high heat output this Mendota Fireplace w...

Страница 18: ...ny pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 PSIG 3 5 kPa A proper gas line diameter must be selected to run from the supply regulator to the Firepla...

Страница 19: ...is not sufficient to add the Gas Fireplace an additional inches to inches regulator must be installed for the Fireplace EXCEPTION Some codes allow 2 PSI 1 4KPA supplies to enter the residence in whic...

Страница 20: ...ements and locations are being followed 3 This Fireplace is designed for installation into rough framing NOTE FRAMING MATERIAL ABOVE FIREPLACE MUST MAINTAIN CORRECT CLEARANCE TO FIREPLACE AND VENT PIP...

Страница 21: ...its own separate vent system Common vent systems are prohibited To assure proper venting performance of this high performance Mendota Direct Vent Fireplace it is critical that all brands of vent pipe...

Страница 22: ...K Clearance to a mechanical air supply inlet 6 feet 1 8 m minimum E Clearance to unventilated soffit 24 min 60 cm min L Clearance above paved side walk or a paved driveway located on public property 7...

Страница 23: ...EM DESCRIPTION 1 6 or 7 PIPE DuraVent 6 Amerivent 7 2 12 VENT STACK 3 24 VENT STACK 4 36 VENT STACK 5 48 VENT STACK 6 90 GALVANIZED ELBOW 45 GALVANIZED ELBOW 7 ADJUSTABLE WALL THIMBLE 8 ATTIC INSULATI...

Страница 24: ...feet maximum hori zontal run allowed with a 4 feet starter section If the starter vertical section is less than 4 feet use the chart and reduce 3 feet for every 90 0 elbow in stalled after the first 9...

Страница 25: ...systems that provide a starting vertical section less than 4 feet the following rules apply a You must use the Master Flue Venting Requirements Chart See Zone A below the 4 vertical run line b A sing...

Страница 26: ...L TERMINATION VERTICAL RISE TRIPLE 90 ELBOWS HORIZONTAL TERMINATION VERTICAL RISE TRIPLE 90 ELBOWS VERTICAL TERMINATION THREE HORIZONTAL DISCHARGE 90 ELBOWS APPROVED w RESTRICTIONS STRAIGHT UP VERTICA...

Страница 27: ...enetrate the exterior wall 3 Cut and frame a 10 3 4 wide x 10 3 4 high opening in the wall The hole must be positioned so the vent system will run level or have a rise per foot of run AND be perpendic...

Страница 28: ...will pass through any ceilings and will penetrate the outside wall Since vent pipe sections overlap we suggest pre assembling and measuring the total vent pipe run so you can more accurately locate t...

Страница 29: ...29 P a g e Figure 19 Figure 20 APPROVED...

Страница 30: ...nts DuraVent only are sealed and are leak proof Maintain 1 airspace clearances to combustibles 2 above horizontal runs Cut a 10 x 10 opening in the roof centered in the small drilled hole placed in th...

Страница 31: ...31 P a g e Figure 21 1 2 3 4 5 13 15 9 10 11 12 50 FEET MAX...

Страница 32: ...fireplace and its venting system Through this effort Mendota has been able to certify the use of Four 90 0 elbows The use of Four 90 0 elbows must meet some minimum prerequisites Prerequisite 1 The v...

Страница 33: ...ree bottom tabs in glass frame bottom with slots in glass clips on firebox bottom Insert tabs into slots and center tabs in slots left to right 2 Center Glass Frame over Firebox left to right 3 After...

Страница 34: ...leaks and gas pressures prior to installing facing materials Install fresh batteries in Wall Receiver and remote transmitter Follow Initializing the Sys tem for the first time instructions to synchro...

Страница 35: ...i cations start with air shutter open to 3 8 After burner has been properly installed and operated for 20 minutes small additional adjustments to the air shutter may be ne cessary for final flame appe...

Страница 36: ...ss should be cleaned periodically Exterior glass surface may be cleaned with cleaner as desired To clean interior surface of glass use soap and water CAUTION Do not use oven cleaner to clean glass Cle...

Страница 37: ...eplace if necessary D Periodically check to verify that the vent system and vent cap are open and free of blockage E Before re installing glass have qualified service person check the operation of the...

Страница 38: ...Remove Screws and lift out Burner Airbox Remove 8 screws and remove left side blower mount plate Main Orifice Pilot Hood Valve Pressure Regulator This conversion kit shall be installed by a qualified...

Страница 39: ...wn 5 Remove the Burner Locate and Identify the Burner Orifice Spud The Orifice Spuds can be removed and installed using a deep well socket and ratchet WARNING Make certain to Secure the Brass fit ting...

Страница 40: ...or failure to use only parts specifically ap proved with this appliance may result in property damage or personal injury AVERTISSEMENT Risque de dommages ou de blessures si les pi ces ne sont pas inst...

Страница 41: ...or gas leaks with soap and water solution at all plumbing joints prior to placing this appliance into operation It is recom mended that all gas plumbing joints factory installed and field installed ar...

Страница 42: ...u are derating this appliance at a high altitude also attach the High Altitude Deration Label supplied in the Owner s Manual Packet to this same surface Prior to attaching the labels fill in all the i...

Страница 43: ...Flex CF Coupler 3 1 05 04 00050 SIT Pilot Assembly 4 2 65 14 00038 ORIFICE 38 5 1 05 02 00344 885 PROFLAME SIT VALVE 6 1 65 07 00753 Elbow 90 Deg 3 8 Flared Tube X 3 8 NPT Male Brass 7 1 65 07 00012 B...

Страница 44: ...an Electrical Code Caution Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and danger ous operation and Verify proper operation after servicing Attentio...

Страница 45: ...ts individual components are available through Johnson Gas Appliance Company Contact your dealer for more de tailed ordering information GLASS FRAME ASSEMBLY HA 78 00103 REPLACEMENT PARTS LIST ITEM PA...

Страница 46: ...be found on the rating plate which is located inside the right side controls access door When contacting your dealer for any cleaning service or warranty service always provide the Model Number Seria...

Страница 47: ...runs 1000 sealant must be used on inner joints at adjustable pipe sections CHECK FOR PROPER CLEARANCES TO COMBUSTIBLES VENT LOCATIONS Per Manual INSTALL PROPER SIZE GAS LINES CHECK FOR GAS LEAKS Per M...

Страница 48: ...48 P a g e NOTES...

Страница 49: ...49 P a g e TAPE SHUT JOHNSON GAS APPLIANCE COMPANY 520 E AVENUE N W CEDAR RAPIDS IA 52405 POSTAGE NEEDED...

Страница 50: ...formance of any part of this limited warranty Mendota has the right to investigate and inspect the exact original Fireplace and entire installation without any alterations or tampering in the event a...

Страница 51: ...51 P a g e Johnson Gas Appliance Company 520 E Avenue N W Cedar Rapids IA 52405 Mendota Hearth Division WEBPAGE www johnsongas com or www mendotahearth com...

Отзывы: