
85-03-01110
FV36
Page
24
Clearances to Combustible Side Walls
The minimum distance required from the side edge of the visible glass to a combustible side wall is 16
”
. Combustible side walls,
mantel corbels, mantel legs and other combustible walls and decorative objects must fall behind a 45-degree line extending
outward from the side edges of the visible glass unless such objects are more than 16
” away from the visible side edges of the
Figure 3-18 Side Wall Clearances.
If the required clearance cannot be m et to a pre-existing combustible side wall, an NFPA approved clearance
reduction shield, metal or ceramic board, must be added to the side wall.
Horizontal Clearance Reduction by 66%
NPFA 211 Approved
: Install 20-gauge or heavier steel
s
hield that provides at least a 1”
active airspace, on the
combustible wall surface. To provide for active airflow,
install at least 1” metal or ceramic standoffs or spacers
between the metal shield and the combustible surface
being protected. The bottom and top edges of the cavity
between the metal shield and the combustible surface
must be left open. The steel shield must be a minimum of
12”
larger in each direction than the surface area of the
source of heat; or if the surface being protected is smaller
than surface area of the source of heat, this shield must be
larger than the combustible surface in each direction.
By using this method of protection, if the required
horizontal clearance was 16
”
, the resulting clearance will
be reduced by 66% to 5-3/8
” between the heat source and
the metal shield.
Horizontal Clearance Reduction by 50%
NPFA 211 Approved
: Install an R-1 rated ceramic board or R-1 rated mineral board on the wall you are attempting to protect.
by using this method of protection, if the required horizontal clearance was 16
”
, the resulting clearance will be reduced by 50%
to 8
” between the heat source and the
R-1 Rated wall board.
Figure 3-18 Side Wall Clearances
Содержание FullView AA-11-02980 FV36
Страница 15: ...85 03 01110 FV36 Page 15 Figure 3 11 Figure 3 10...
Страница 23: ...85 03 01110 FV36 Page 23 Clearance from Appliance Side Walls Figure 3 17 CLEARANCE TO BODY...
Страница 95: ......
Страница 96: ...Johnson Gas Appliance Company 520 E Avenue NW Cedar Rapids Iowa 52405 Mendota Warranty Registration...