NOTICE:

 In order to maintain the IP protection 

provided by DB models in custom installations, 

watertight seals should be used under the heads of 

the four mounting bolts and they must be retained 

by a lock washer and nut on the inside of the box or 

panel. Alternatively, four blind holes may be drilled 

and threaded to accommodate the mounting screws, 

provided that the hole depth is sufficient to achieve 

adequate gasket compression.

  OPERATION

WARNING

DANGER

CAUTION

NOTICE

ADVERTENCIA

DANGER

CAUTION

AVISO

To ensure safe and reliable operation, 

MELTRIC plugs and receptacles must be used 

in accordance with their assigned ratings.

MELTRIC plugs and receptacles can only be used in 

conjunction with mating receptacles or plugs manu-

factured by MELTRIC or another licensed producer of 

products bearing the 

 

technology trademark.

MELTRIC plugs & receptacles are designed with 

different keying arrangements, so that only plugs and 

receptacles with compatible contact configurations 

and electrical ratings will mate with each other.

Connection

First remove the lid on the receptacle by turning the 

locking ring fully counterclockwise. The lid can then 

be removed. For convenience it remains attached to 

the receptacle by a wire. 

To insert the plug into a receptacle, the arrow on the 

plug casing is aligned with the left end of the viewing 

window on the receptacle, Figure  1 .  Push the plug 

partially into the receptacle until it hits a stop then 

rotate slightly clockwise. The plug is now in the rest 

position with circuit open.

Push the plug straight into the receptacle until it is 

held in place by the locking ring Figure  2 . The 

electrical connection is now made as indicated by the 

red color in the viewing window. IP67 watertightness 

is achieved by fully rotating the locking ring in the 

clockwise direction until the protruding lockout tab 

completely clears the window shroud.

Disconnection

To break the connection, turn the locking ring fully 

counterclockwise.  This will break the circuit and 

eject the plug straight out to the rest or off position.  

The plug contacts are deenergized at this point.  To 

remove the plug, rotate it counterclockwise (about 

10°) until it can be withdrawn from the receptacle, 

Figure  3 . Insert the lid and rotate the locking ring 

fully clockwise to provide IP67 protection to the 

receptacle, Figure  4 .  

To attempt another engage-

ment after disconnection, the plug must be 

returned to its rest position.

Achieving Ratings & Watertightness

Rated ingress protection is achieved when the 

plug and receptacle are mated and the locking 

ring is fully rotated in the clockwise direction. It can 

also be achieved by the receptacle when the lid is 

inserted and the locking ring is fully rotated in the 

clockwise direction.  

 

NOTICE: 

Proper steps must be taken to maintain 

watertightness at NPT fittings on the plug handles 

or at the junction box. Use of a sealer tape is 

recommended.

Lockout Provisions

All DB plugs and receptacles are provided with 

lockout provisions. 

 

Plug Lockout

To prevent the DB plug from being inserted into any 

DB receptacle place a padlock or a safety lockout 

through the hole provided.

 

Receptacle Lockout

Insert the lid and fully rotate the locking ring clock-

wise. A padlock or safety lockout can then be inserted 

in the hole on the locking ring. 

 

Locking Plug and Receptacle in Closed Position

WARNING

DANGER

CAUTION

NOTICE

ADVERTENCIA

DANGER

CAUTION

AVISO

Deenergize electrical power to the receptacle 

prior to punching out the knockout hole on the  

receptacle locking ring.

To lock the plug and receptacle in the closed position 

a knock-out hole located on the receptacle locking 

ring must first be opened with the help of a 1/4” 

punch. When the plug and receptacle are engaged 

and the locking ring is fully rotated then the lockout 

hole will have cleared the window shroud and a 

padlock or safety lockout can be inserted.

 

Locking Plug and Receptacle in the Open or 

Parked Position

When the plug is in the rest or off position the lockout 

holes on the locking ring and plug can be aligned. 

Insert a safety lockout device through both holes to 

lock the unit in the parked position. 

  MAINTENANCE

Before inspecting, repairing, 

or maintaining MELTRIC prod-

ucts, disconnect electrical power to the receptacle to 

eliminate the risk of electrical shock.
MELTRIC products require little on-going mainte-

nance.  However, it is a good practice to periodically 

perform the following general inspections:

   •  Check the mounting screws for tightness.
  •  Verify that the weight of the cable is supported  

    by the strain relief mechanism and not by the 

    terminal connections.
  •  Check the IP gaskets for wear and resiliency.   

    Replace as required.

  •  Verify the electrical continuity of the ground circuit.
  •  Check the contact surfaces for cleanliness 

    and pitting.

Use a clean cloth to rub off deposits of dust or sim-

ilar foreign materials on the contacts and the plug 

interiors. Sprays should not be used, as they tend to 

collect dirt. If any significant pitting of the contacts 

or other serious damage is observed, the device 

should be replaced.

  MANUFACTURER’S RESPONSIBILITY

MELTRIC’s responsibility is strictly limited to the 

repair or replacement of any product that does not 

conform to the warranty specified in the purchase 

contract.  MELTRIC shall not be liable for any pen-

alties or consequential damages associated with the 

loss of production, work, profit or any financial loss 

incurred by the customer.
MELTRIC Corporation shall not be held liable when 

its products are used in conjunction with products 

not bearing the 

 

technology trademark.  The 

use of MELTRIC products in conjunction with mating 

devices that are not marked with the 

 

tech-

nology trademark shall void all warranties on the product.

MELTRIC Corporation is an ISO 9001 certified 

company.  Its products are designed, manufactured 

and rated in accordance with applicable UL, CSA and 

IEC standards.  MELTRIC designs and manufactures 

its products in accordance with Marechal keying 

standards established to ensure intermatablility with 

similarly rated products manufactured by Marechal 

Electric Group.

1

3

4

5

6

2

1

2

3

4

1

3

4

5

6

2

1

2

3

4

Table 6 - Custom Mounting Dimensions

 

 ‘A’  

 

‘B’

Model 

Inches   mm  Inches   mm

DB30 

2.17   55 

2.17   55

DB60 

2.68   68 

2.59   66

DB100 

3.35   85 

3.2    81

Lockout

Holes

Locking

Ring

Lockout

Hole

INSDB J

WARNING

DANGER

CAUTION

NOTICE

ADVERTENCIA

DANGER

CAUTION

AVISO

Содержание DB Series

Страница 1: ...ck out the termi nal screws on the receptacle or inlet far enough but not completely to allow the conductors to pass Then insert the conductors fully into the proper terminal The terminal screws should not be over tightened Appropriate tools and tighten ing torques are indicated in Table 5 Table 5 Terminal Screw Tightening Torques Device Torque Required Screwdriver Flathead type in lbs N m DB30 30...

Страница 2: ...into any DB receptacle place a padlock or a safety lockout through the hole provided Receptacle Lockout Insert the lid and fully rotate the locking ring clock wise A padlock or safety lockout can then be inserted in the hole on the locking ring Locking Plug and Receptacle in Closed Position Deenergize electrical power to the receptacle prior to punching out the knockout hole on the receptacle lock...

Страница 3: ...1 2 12 DB60 60A 13 16 20 5 8 15 DB100 100A 1 3 8 35 1 3 16 30 4 Les bornes de raccordement sont dotées de ressorts pour empêcher la formation d un jeu causée par le déplacement des brins des câbles les vibrations et les cycles thermiques MISE EN GARDE Dévissez partiellement les bornes de raccordement de la prise juste assez pour permettre le passage des conducteurs Insérez complètement chaque cond...

Страница 4: ... jonction L utilisation d un ruban d étanchéité est recommandée Cadenassage Toutes les fiches et prises DB sont munies de dispositifs de cadenassage Cadenassage de la fiche Pour éviter d insérer une fiche DB dans une prise placez un cadenas ou un verrou de sûreté dans le trou prévu à cet effet Trou de cadenassage Cadenassage de la prise Fermez le couvercle et tournez complètement la bague en sens ...

Страница 5: ...la tornillería adecuada Ensamble la clavija o tomacorriente al cable como se indican en las instrucciones de ensamble descritas a continuación AVISO Se recomienda el uso de cintas selladoras para las cuerdas para impedir el ingreso de agua en las uniones y juntas del tubo conduit NPT Ensamble de las Clavijas o Conectores Cuando se ensamblen clavijas o tomacorrientes a las manijas con empaque multi...

Страница 6: ...instale un candado o bloqueo de seguridad en el orificio proporcionado Bloqueo del Tomacorriente Inserte la tapa y gire completamente el aro de cierre hacia la derecha Un candado o bloqueo deseguridad pueden ser insertados por el orificio en el aro de cierre Bloqueando el Tomacorriente y Clavija en Posición de Cerrada Verifica que el tomacorriente no está energizado Antes de abrir el orificio tipo...

Отзывы: