Operating and installation instructions
M-WRG-II P-T (-F, -FC), M-WRG-II E-T (-F, -FC) ventilation units
- 24 -
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L A T I O N & H E A T R E C O V E R Y
7.1.1 Default assignment of the membrane touch pad
This section illustrates the default assignment of the individual buttons on the membrane
touch pad for the different types of unit. How the individual ventilation programs work is
described in section 10 on page 31.
7.1.1.1 M-WRG-II P-T / M-WRG-II E-T
Ventilation program
Air flow
1
Reduced ventilation (people absent)
10 m
3
/h
2
Normal ventilation (people present)
30 m
3
/h
3
Increased ventilation
50 m
3
/h
4
70 m
3
/h
5
Intensive ventilation (15 min)
100 m
3
/h
7.1.1.2 M-WRG-II P-T-F / M-WRG-II E-T-F
Ventilation program
Air flow
1
Reduced ventilation (people absent)
10 m
3
/h
2
Normal ventilation (people present)
30 m
3
/h
3
Increased ventilation
50 m
3
/h
4
Humidity control
10 - 60 m
3
/h,
infinitely-variable
5
Intensive ventilation (15 min)
100 m
3
/h
7.1.1.3 M-WRG-II P-T-FC / M-WRG-II E-T-FC
Ventilation program
Air flow
1
Reduced ventilation (people absent)
10 m
3
/h
2
Normal ventilation (people present)
30 m
3
/h
3
Increased ventilation
50 m
3
/h
4
Automatic mode (humidity and CO
2
control)
10 - 60 m
3
/h,
infinitely-variable
5
Intensive ventilation (15 min)
100 m
3
/h