NOTICE
► Observe the following recommendations when using flexible pipes to avoid unnec
-
essary pressure losses in the pipes.
—
Always connect two flexible pipes to the flexible pipe connection.
—
As far as possible, use flexible pipes with a diameter of 75 mm.
—
The total length of each flexible pipe should not exceed 10 m.
—
Minimise the number of bends in the flexible pipes.
—
Run the two flexible pipes of a flexible pipe connection in parallel to one another.
The minimum distance between the flexible pipes must not be less than 3x the
pipe diameter.
Fig. 17 contains a planning example for
running a flat duct and the flexible pipes.
Always run 2 flexible pipes in the supply
air or extract air room.
NOTICE
The dimensions of the wall channels
for the flat ducts are:
— 125 mm wide
— 85 mm deep
The dimensions of the wall channels
for the flexible pipes are:
— 170 mm wide
— 85 mm deep
8.4
Chasing out channels for
connecting cables
►
Chase out a channel for the mains
and control cables (item 1 in Fig. 18).
NOTICE
The wall channel in Fig. 18 is shown
by way of example. An alternative wall
channel is shown as dashed lines
(item 2 in Fig. 18). For the subsequent
electrical installation work, we recom-
mend running the mains and control
cables from the left at the wall break-
through.
Fig. 17:
Planning example for running flat ductwork
and flexible pipes
min. 300
min. 3x
pipe
diameter
Fig. 18: Chasing out channels for connecting cables