SwitchX®-2 18-Port QSFP FDR InfiniBand System Hardware User Manual
Rev 1.1
Mellanox Technologies
21
Figure 15: Component Air Flow
Figure 16 shows a mismatch in component airflow.
Figure 16: Component Airflow Mismatch (Wrong)
Table 10 shows the icons that indicate airflow using arrows and colors.
All components need the same colored airflow icons.
OK
!
!
OK
OK
!
!
OK
12C
OK
!
!
OK
OK
!
!
OK
12C
These air flow labels must be the same.
Red is connector side inlet to power side outlet
Blue is power side inlet to connector side outlet
OK
!
!
OK
OK
!
!
OK
12C
These air flow labels must be the same.
Any mismatch of these labels will affect the switch temperature.