6. Technician Settings
To offset the Room temperature readings- when needed:
•
Adjust the set-point temperature for cooling to 10
°
C.
•
Wait until display returns to normal.
•
Press and hold the “Select” button (5 sec.) –“Offs” and the OFFSET temperature will
appear on display (a number between –6…+6). The offset is used to calibrate the
measured Room temperature- when needed.
•
Adjust the Offset for Room temperature readings using the “+” and “-“ buttons
between –6
°
C and +6
°
C (default = 0
°
C).
•
Press the “Select” button again to return to normal display.