DIP switch S2 settings (Left DIP switch)
Contact (Window contact / Door switch) operation
Use DIP Switch S2.5 to select between temperature display options as follows:
Set point temperature only:
S2.5 – ON
Room and Set point:
S2.5 – OFF
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec
.
com
ETN24-SUPER-SH-F
Owner’s manual & Technnician Settings
Pg. 4
Internal/External sensor
Use DIP Switches S2.1, S2.2 and S2.3 to select
between Internal (default) and External sensor
configuration as follows:
Internal sensor: S2.1, S2.3 – ON,
S2.2 – OFF
External sensor: S2.1, S2.3 – OFF, S2.2 – ON
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Internal
sensor
External
sensor
ON
1 2 3 4 5 6
Cool only (without heaters) or Cool and heat (Heaters and compressors) configuration
Use DIP Switch S2.4 to select cool – heat configuration
Cool only:
S2.4 – OFF
Cool and heat:
S2.4 – ON
ON
1 2 3 4 5 6
Cool only
Cool and Heat
ON
1 2 3 4 5 6
Temperature display
ON
1 2 3 4 5 6
Set point only
Room and Set
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
S2
S1
S2
S2
S2
S2
S2
S2
S2
S2
Use DIP Switch S2.6 to choose the way the thermostat behaves when the contact is
triggered (closed)
Switch to economy mode:
S2.6 – ON
Turn unit OFF:
S2.6 – OFF
Note: Economy mode set points are set by technician – refer to technician settings.
Economy
Outputs OFF