DIP switch S2 settings (Left DIP switch)

Contact (Window contact / Door switch) operation

Use DIP Switch S2.5 to select between temperature display options as follows:
Set point temperature only:

S2.5 – ON

Room and Set point:

S2.5 – OFF

Tel: (856) 2882882

Tel: +972-3-9626462

Fax: +972-3-9626620

support@meitavtec

.

com

ETN24-SUPER-SH-F

Owner’s manual & Technnician Settings

Pg. 4

Internal/External sensor

Use DIP Switches S2.1, S2.2 and S2.3 to select 
between Internal (default) and External sensor 
configuration as follows:

Internal sensor: S2.1, S2.3 – ON, 

S2.2 – OFF  

External sensor: S2.1, S2.3 – OFF,  S2.2 – ON 

ON

1 2 3 4 5 6

ON

1 2 3 4 5 6

ON

1 2 3 4 5 6

Internal 

sensor

External 

sensor

ON

1 2 3 4 5 6

Cool only (without heaters) or Cool and heat (Heaters and compressors) configuration

Use DIP Switch S2.4 to select cool – heat configuration

Cool only:

S2.4 – OFF

Cool and heat:

S2.4 – ON

ON

1 2 3 4 5 6

Cool only

Cool and Heat

ON

1 2 3 4 5 6

Temperature display

ON

1 2 3 4 5 6

Set point only

Room and Set

ON

1 2 3 4 5 6

ON

1 2 3 4 5 6

ON

1 2 3 4 5 6

S2

S1

S2

S2

S2

S2

S2

S2

S2

S2

Use DIP Switch S2.6 to choose the way the thermostat behaves when the contact is 
triggered (closed)
Switch to economy mode:

S2.6 – ON

Turn unit OFF:

S2.6 – OFF

Note: Economy mode set points are set by technician – refer to technician settings.

Economy

Outputs OFF

Содержание ETN24-SUPER-SH-F

Страница 1: ... 1 For 3 speed configuration Press and hold the Fan button 5 sec to turn Auto fan ON or OFF When ON the fan will work on demand for cooling or heating When OFF the fan will work continuously Note Auto fan cannot be selected in Fan only mode For 1 speed configuration Press the Fan button to turn Auto fan ON or OFF When ON the fan will work on demand for cooling or heating When OFF the fan will work...

Страница 2: ...main board before installing the unit The standard height to install this unit is 1 5 meter 5 feet from the floor Installation procedure A Separate the front panel from back panel by pressing the tongue located in the top of the unit and pull the back panel out B Line the back panel up against the wall or flat surface Install three screws as required C Make electrical connections as shown on enclo...

Страница 3: ... stg Comp 2 2nd stg Fan low Fan high Comp 1 External sensor option Y1 G G1 0 Y2 T Y3 G3 IN 0 W2 G2 C R W1 Cool and heat configurations with 1 or 3 fan speeds Fan Terminals Terminals Select your configuration set by DIP switches S1 2 and S2 4 Y1 G G1 0 Y2 T Y3 G3 IN 0 W2 G2 C R W1 Note If only one compressor is being used connect it to Y1 1st stage cool If two compressors are being used connect the...

Страница 4: ...al sensor S2 1 S2 3 OFF S2 2 ON ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 Internal sensor External sensor ON 1 2 3 4 5 6 Cool only without heaters or Cool and heat Heaters and compressors configuration Use DIP Switch S2 4 to select cool heat configuration Cool only S2 4 OFF Cool and heat S2 4 ON ON 1 2 3 4 5 6 Cool only Cool and Heat ON 1 2 3 4 5 6 Temperature display ON 1 2 3 4 5 6 Set point o...

Страница 5: ...pressor time delay Use DIP Switches S1 3 to enable disable the 3 minutes compressor time delay as follows 3 Minutes delay S1 3 OFF No delay S1 3 ON ON 1 2 3 4 5 6 3 Minutes delay No delay ON 1 2 3 4 5 6 Important Switches 4 and 6 are not in use and must remain OFF S1 S1 Heater type Use DIP Switches S1 5 to select heater type as follows Electrical heater S1 4 OFF Oil Gas heater S1 4 ON Note In Heat...

Страница 6: ... Cool Heat F F Cool Limit Heat Offset F F Temperature set point for cooling in economy mode Press the Mode button again Cool and Aux will flash Use the and buttons to adjust the temperature limit for cooling in economy mode Range 52 95 F Default 95 F Temperature aet point for heating in economy mode Press the Mode button again heat and Aux will flash Use the and buttons to adjust the temperature l...

Страница 7: ...ee technician settings In Economy mode the thermostat will use predefined set point temperatures selected by technician instead of the set point selected by the occupant If OFF was selected the thermostat will turn off and EC and Off will appear on display Fault input alarm Lock thermostat buttons Make sure the set point temperature is not 50 F Press and hold the Mode button for 5 seconds to lock ...

Страница 8: ...Tel 856 2882882 Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com www meitavtec com ...

Отзывы: