ETN24-SUPER-SH-F
Owner’s manual & Technnician Settings
Pg. 7
Fault input - Door switch / window contact (Normally open)
The contact is Voltage free (2 terminals), normally open (active when close).
When the contact closes, “EC” will appear on display.
When activated, the thermostat will turn OFF or switch to economy mode (see
technician settings).
In Economy mode, the thermostat will use predefined set point temperatures,
selected by technician, instead of the set point selected by the occupant.
If ‘OFF’ was selected, the thermostat will turn off and “EC” and “Off” will appear
on display.
Fault input
alarm
Lock thermostat buttons
Make sure the set point temperature is not 50
°F.
Press and hold the [Mode] button for 5 seconds to lock the
thermostats buttons – “Lc” will appear on display.
Press and hold the [Mode] button again to release.
Note: When locked, the display will alternate between “Lc” and
room temperature.
Locked