Note
The machine complies with IEC 61000-3-12 provided that the short circuit power
S
SC
at the point where the customer's system connects to the public grid is greater
than or equal to
1.4
MVA
. The installer or machine operator is responsible for en-
suring that this machine is only connected at a connection point with an
S
SC
value
greater than or equal to
1.4 MVA.
If necessary, they must consult the grid operator
first.
MEIKO offers a line choke as a retrofit component for customers who do not have
the necessary short circuit power at the connection point.
Other dangers
Danger of death by electric shock: contact with live electrical parts can lead to seri-
ous injury or death.
Who may connect it?
The dishwashing machine must be connected by a (MEIKO authorised) electrician in
accordance with the locally applicable norms and regulations.
Local earth wire system
The electrical safety of this machine is only ensured if it is connected to a properly
installed protective conductor system. It is very important to verify this fundamental
safety feature. If in doubt, have the building wiring checked by an electrician.
Voltage and frequency
The machine may only be operated with the data provided on the descriptive plaque
(see page 16).
Power cable/fixed connection:
Recommended connection with protective equipotential bonding
The machine and accessory appliances are intended for permanent connection to
the locally available power supply and the locally available protective equipotential
bonding and have been tested for the market accordingly.
A 5-pole terminal strip (L1, L2, L3, N, PE) must be used for connection to a three-
phase current.
Electricity supply without a neutral wire (N): when connecting to three-phase current,
use a 4-pole clamping strip (L1, L2, L3, PE).
Wire colours: live wire L1 = black/1, L2 = brown/2, L3 = grey/3, neutral wire N =
blue/4, earth wire PE = green-yellow
Alternative connection without protective equipotential bonding
The operator can decide at his/her own discretion and under his/her own responsi-
bility to connect the electricity supply using customer resources in collaboration with
an electrician company:
1. Fixed connection without protective equipotential bonding
2. Plug connection according to EN 60309 (CEE plug connection)
Additional necessary measures for personal protection:
Machines with integrated frequency converters must have an RCD/FI circuit breaker
(type B) max. 30 mA sensitive to all types of current installed rather than a residual
current operated circuit breaker type A.