![Megmeet MTC-04-NT Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/megmeet/mtc-04-nt/mtc-04-nt_user-manual_1765695041.webp)
41
er
No alarm
0
No alarm
Turn off the alarm function
Basic
alarm
1
High limit
Alarm when the measured value (PV) is
larger than the alarm setting
Input scope
2
Low limit
Alarm when the measured value (PV) is
smaller than the alarm setting
Input scope
3
Deviation high
Alarm when the deviation value (measure
value-setting value) is larger than the
alarm setting
± input width
4
Deviation low
Alarm when the deviation value (measure
value-set value) is smaller than the alarm
setting
± input width
5
Deviation
high/low
Alarm when the absolute value of
deviation (| measured value - setting
value |) is larger than the alarm setting
value
± input width
6
Band
Alarm when the absolute value of
deviation (| measured value - setting
value |) is smaller than the alarm setting
value
± input width
Waiting
for
alarm
7
Wait with the
high limit alarm
If the measured value is larger than the
alarm setting value, the measured value
will be ignored when the power is turn on
Input scope
8
Wait with the low
limit alarm
If the measured value is smaller than the
alarm setting value, the measured value
will be ignored when the power is turn on
Input scope
9
Wait with the
deviation
high
alarm
If the deviation value (measured value -
set value) is larger than the alarm setting
value, the measured value will be ignored
when the power is turn on
± input width
10
Wait with the
deviation
low
alarm
If the deviation value (measured value -
set value) is smaller than the alarm
setting value, the measured value will be
ignored when the power is switched on
± input width
11
Wait with the
deviation
high
/low alarm
Alarm when the absolute value of
deviation (| measured value - setting
value |) is larger than the alarm setting
value, but the measured value will be
ignored when the power is switched on
± input width
Wait
for
the
second
alarm
12
Wait again with
the
deviation
high limit alarm
Alarm when the deviation (measured
value-set value) is greater than the alarm
set value, but the measured value will be
ignored when the power is turned on and
the set value changes
± input width