Installation considerations
INSTALLATION OF A SPEEDSYS300 ODS301
3.2.6 Electrical connections
For the SpeedSys300 ODS301 module, electrical connections are established via removable
screw-terminal connectors. Each connector (entire pluggable terminal block), containing four
clamps/contacts can be removed by pushing against the connector tab (see
and inserting screw-terminal connectors
A suitable screwdriver should be used to loosen and tighten the screws before and after
inserting the wire into the clamps/contacts of each connector.
provides detailed information on the specifications of the SpeedSys300 ODS301
module’s screw-terminal connectors.
The module’s housing and connectors use mechanical key-coding to prevent incorrect
connector insertion, for a system that is simple to operate and use.
A general wiring diagram illustrating the required grounding and shielding for most interfaces
in a typical application in an EMC/ESD uncontrolled area is shown in
.
3.2.7 Installations in hazardous areas
NOTE:
Knowledge of the installation of field wiring and protective earth (PE),
instrument earth (IE) and intrinsically safe earth (IS) is required.
The SpeedSys300 ODS301 module’s sensor / input channel interfaces (proximity, electronic
and magnetic) are galvanically separated in order to allow a direct connection to a sensor /
measurement chain installed in a potentially explosive atmosphere (hazardous area),
eliminating the need for additional external safety barriers such as Zeners. See also
3.2.8 Sensor / input channel interface circuitry
To support installations in hazardous areas, the SpeedSys300 ODS301 module’s connectors
can be divided into two groups:
•
Ex connectors, located on the top of the module.
NOTE:
The SpeedSys300 ODS301 module’s Ex connectors are identifiable by their
blue colour.
•
Non-Ex connectors, located on the bottom of the module.
Table 3-13:
Specifications of SpeedSys300 ODS301 module’s screw-terminal connectors
SpeedSys300 ODS301
screw-terminal connectors
Parameter
Value
Electrical connections:
•
IEC
•
CSA/UL
320 V / 10 A
300 V / 10 A / 26 to 12 AWG
Clamping range
0.13 to 3.31 mm
2
/ 26 to 14 AWG
Tightening torque
0.4 to 0.6 N•m (0.30 to 0.44 lb-ft)