SVERKER 750/780

Relay Test Sets

PSS750

Phase selector switch PSS750

The Phase Selector Switch PSS750 is specifically designed to work 

with SVERKER 750/780 when testing three-phase relays. It is 

connected between SVERKER 750/780 and the relay inputs and 

allows the user to easily select which phase to test.
The PSS750 handles both the current and voltage sources and 

single-phase or phase-phase testing can be selected. Together 

with the output-input switching the unit also contains a variable 

resistor that can be used together with the built-in capacitor in 

SVERKER 750/780. This feature gives the user the possibility to 

create a variable phase shift at a decreased amplitude of the test 

voltage.
The design is passive which makes it very general. You may for 

example use any of  the inputs for current or voltage as long as you 

do not exceed the specification. It is also possible to connect the 

measuring inputs of  the SVERKER 750/780 to the PSS750 and 

use the switch for selecting measurement signals.
The PSS750 simplifies phase switching, selecting type of fault, 

phase reversing and gives a possibility to create a variable phase 

shift..

Specifications PSS750

Specifications are valid at nominal input voltage and an ambient 
temperature of +25°C, (77°F). Specifications are subject to 
change without notice.

Max input voltage

 250 V AC / 3 A

Max input current

6 A / 250 V AC

Max resistor loading

200 V AC / 200 mA (0.5 A during 
5 seconds)

Dimensions

200 x 120 x 85 mm  
(7.9” x 4.7” x 3.3”)

Weight

1.3 kg (2.9 lbs)

Application example with PSS750

IMPORTANT! 
Read the User’s manual before using the instrument

1.  Connect the current and voltage outputs of 

SVERKER 750/780 to the PSS750 inputs.

2.  Connect the current and voltage inputs of  the relay to the 

PSS750 outputs.

3.  Select which phase to test and type of test (phase-to-ground or 

phase-phase) with the selector switch.

4.  Proceed with the test for each phase and fault type.
5.  To create a phase shift, connect the 10 µF capacitor in 

SVERKER 750/780 in series between the voltage output and 

the PSS750 input, and connect the variable resistor in parallel 

with the PSS750 input.

6.  Set the SVERKER 750/780 for phase (and impedance) mea-

surement. Connect the voltage measurement input to the 

PSS750 input.

7.  Start the test with the resistor in maximum position. Gradu-

ally decreasing the resistor gives increasing phase shift in the 

voltage signal. The test voltage/impedance will decrease at the 

same time so an adjustment of the test current might be neces-

sary to get the correct impedance. Please observe that the phase 

shift depends on the input resistance and may vary between 

different relays. Some relays may also have a low voltage lim-

it where the relay will not operate. For additional 180 degrees 

phase shift use the phase reversal switch.

Содержание SVERKER 750

Страница 1: ...and the PC software SVERKER Win Since the compact SVERKER weighs only 18 kg 39 lbs it s easy to move from site to site Two or more SVERKER units can also be synchronized which allows the user to opera...

Страница 2: ...780 1 Connect as shown in the diagram 2 Select stop conditions dry or wet contact 3 Select HOLD to freeze the current reading 4 Press button SEL A until you get a red light at the built in ammeter No...

Страница 3: ...ME Starts generation and timing simultaneously Used to test over relays means cur rent voltage or some other entity Generation contin ues a until the protective relay equipment operates and stops the...

Страница 4: ...he entire test is finished you can save everything as a data file Later you can print out the test results You save time by not having to write your report in the field All report writing can be done...

Страница 5: ...9 99 s 10 ms 10 ms 0 01 100 0 999 9 s 100 ms 100 ms 0 01 For the OFF TIME start condition in INT mode 1 ms shall be ad ded to the above measurement error Range Resolution Inaccuracy 0 0 999 9 cycles 0...

Страница 6: ...1 V 2 Output AC 20 A setting Output voltage min Load time Idle non load 26 V Continuous 5 A 25 V Continuous 10 A 22 V Continuous 20 A 18 V 2 min 10 A setting Idle non load 52 V Continuous 3 A 50 V Co...

Страница 7: ...change without notice Max input voltage 250 V AC 3 A Max input current 6 A 250 V AC Max resistor loading 200 V AC 200 mA 0 5 A during 5 seconds Dimensions 200 x 120 x 85 mm 7 9 x 4 7 x 3 3 Weight 1 3...

Страница 8: ...Language English French German Russian Swedish 230 V Mains voltage CD 12394 SVERKER 750 Incl Test lead set GA 00030 and Transport case GD 00182 Language Bulgarian English French German Swedish 230 V M...

Отзывы: