background image

If the tester fails to indicate a tripped RCD then the tester should be 
returned for a full calibration.

- Record the reading on the record card. 

To reset the test box press the [reset] button in the yellow panel.

 
7.6 

Conducting a 5I @ 180° Test

To do a 180° 5I test set the tester to 180° 5I mode and perform the 
test. The unit will trip and disconnect power. The [Tripped] and  
[5 I TEST] LEDs will light. The trip time should be a nominal 20 ms. 
If the tester fails to indicate a tripped RCD then the tester should be 
returned for a full calibration.

- Record the reading on the record card. 

To reset the test box press the [reset] button in the yellow panel.

 
7.7 

Conducting 10 mA, 30 mA and 100 mA tests

The test sequence can be repeated for the 10 mA, 30 mA and  
100 mA tests by selecting the appropriate current setting on the RCD 
and loop test select switch and repeating the tests as described in 
sections 7.2 to 7.6.

NOTE

: RCD Protection

In order to protect the current sense circuit the RCD simulator is 
protected by a 500 mA fuse. If the fuse blows then the earth pin of 
the RCD and loop supply socket will float. If an RCD test is attempted 
the fuse blown LED will light. Note that this will only illuminate if the 
test instrument does not inhibit testing if the correct voltages are not 
present, or the test instrument provides sufficient leakage to light the 
LED when connected. 

8.  

Fuse replacement

The MTB77671/2 is protected by two x 500 mA (F) fuses and a 7 A 
fuse in the RCD plug. Fuse failure is indicated by either the 230 V 
AC LED failing to light or the [Fuse Blown] LED lighting. In the event 
of a fuse failing, fuses must be replaced with the same fuse type. 
Disconnect the test box from the mains supply. Disconnect any test 
instruments from the test box. Remove the failed fuse from the fuse 
holder and replace with an identical fuse:
Fuse Type:  

500 mA (F) 20 mm

   7 

BS1362

Содержание MTB7671

Страница 1: ...M MTB7671 2 Test box User Guide...

Страница 2: ...Safety Legislation requires them to carry out valid risk assessments of all electrical work so as to identify potential sources of electrical danger and risk of electrical injury such as inadvertent...

Страница 3: ...out supply Fuse Fuse RCD and loop test supply socket Continuity and insulation test select switch Continuity and insulation connection sockets Supply check indicators RCD and loop test select switch...

Страница 4: ...ed and the supply LEDs on the MTB7671 2 will be on To test the RCD plug lightly press the button on the top Test button The red indicator bars should disappear and the supply LEDs on the MTB7671 2 go...

Страница 5: ...this test Record the reading on the record card NOTE If in either of the tests listed above the LEDs fail to light the test instrument under test should be returned for a full calibration 4 3 0 5 Test...

Страница 6: ...reading on the record card 5 2 Voltage load test 500 V Set the continuity and insulation test select switch to 500 V and per form an insulation test with the test instrument set to 500 V output If the...

Страница 7: ...s accuracy Record the reading on the record card 5 5 90 M Test Set the continuity and insulation test select switch to 90 M and perform an insulation check using the tester This connects a 90 M 3 resi...

Страница 8: ...a high current loop test Record the reading on the record card 6 3 Conducting a 180 loop test Set the RCD and loop select switch to Loop 180 and perform a loop test using the tester Check that the lo...

Страница 9: ...I mode and perform the test The test box will trip and disconnect power The Tripped LED will light The trip time should be a nominal 40 ms If the tester fails to indicate a tripped RCD then the tester...

Страница 10: ...ect switch and repeating the tests as described in sections 7 2 to 7 6 NOTE RCD Protection In order to protect the current sense circuit the RCD simulator is protected by a 500 mA fuse If the fuse blo...

Страница 11: ...Pass Fail indication Threshold limits 2 Insulation test voltages 250 V 25 max 500 V 25 max 1 kV 25 max 250 V 25 500 V 25 1 kV 25 Pass Fail indication Threshold limits 2 Insulation test resistances 0 2...

Страница 12: ...2 2 kg EMC In accordance with IEC 61326 1 Operation Safety Meets the requirements of IEC61010 1 Refer to safety warnings supplied Environment Conditions The MTB7671 2 is intended for indoor use only C...

Страница 13: ...is necessary to retun an instrument for repair a Returns Authorisation number must first be obtained by contacting one of the addresses shown You will be asked to provide key information such as the i...

Страница 14: ...SW 2125 Australia T 61 0 2 9659 2005 F 61 0 2 9659 2201 E ausales megger com Megger Limited 110 Milner Avenue Unit 1 Scarborough Ontario M1S 3R2 Canada T 1 416 298 9688 Canada only T 1 416 298 6770 F...

Отзывы: