AVTMMIT30-EN Rev E02 June 2009
19
7
OPERATION
When the test set and apparatus to be tested are
set up as indicated in Section 6, the equipment
can be energized and the required tests run by
following the steps given below.
Note:
Before operating the test set, read Section 2 of
this manual and ensure that all appropriate
safety precautions are observed.
TEST PROCEDURE
1.
Complete connection procedure as outlined in
Section 6.
2.
Remove all safety grounds from the apparatus
to be tested
3.
Close the mains switch, the power indicator
will illuminate.
4.
Set the overcurrent trip to the desired trip
level.
5.
Set the ionization volume to the desired level.