1 INTRODUCTION
Connections for UST/GST
Configurations
DELTA 4000 supports two basic groups of operation, GST
and UST mode. GST stands for grounded specimen test
while UST stands for ungrounded specimen test. Within
the two groups the test set can be operated in seven test
modes as summarized in Table 1.1. Measurements are
always made between the high-voltage lead and the lead/
connection in the measure column.
Table 1.1
DELTA 4000 test modes and internal measure-
ment connections
UST: Ungrounded specimen testing
Test mode
Measure
Ground
Guard
UST-R
Red
Blue
–
UST-B
Blue
Red
–
UST-RB
Red and Blue
–
–
GST: Grounded specimen testing
Test mode
Measure
Ground
Guard
GST-GND
Ground
Red and Blue
–
GSTg-R
Ground
Blue
Red
GSTg-B
Ground
Red
Blue
GSTg-RB
Ground
–
Red and Blue
In UST test mode, Ground and Guard are internally
connected. Internally the Red and Blue leads are either
connected to be measured or connected to Ground (and
Guard).
In GST test modes the current returning from Ground is
measured. Internally the Red and Blue leads are either con-
nected to Ground or Guard to be included in or excluded
from the measurement.