background image

ZM-AH02E

DELTA 4000 

21

3 TESTING POWER SYSTEM COMPONENTS

the result of the low phase being wound around the center 

leg of  a three-legged core. The reluctance of the magnetic 

circuit is less for the center leg of the core resulting in a 

lower charging current.

Shunt reactors

When electrical energy is transmitted at extra high voltages, 

special problems arise that require the installation of large 

compensating devices to regulate the over-voltage condi-

tions and to guarantee stability. Among these devices are 

shunt reactors. Shunt reactors are composed of  a large coil 

placed inside a tank and immersed in oil. They can be single 

phase units or three phases in one tank. In both cases each 

phase has its own neutral bushing.

Test connections

 

For all tests, the line and neutral bushings for 
corresponding phases must remain shorted.

Test procedure

 

Record test results on the test form for Miscellaneous 
Equipment Capacitance and Power Factor Tests.

 

Test voltages are at 10kV. If 10kV exceeds the insulation 
rating, test at or slightly below the insulation rating.

 

For single phase units only one overall ground test is 
performed in the GST mode.

Test results

Power factor and capacitance results should be recorded in 

the same manner as for oil filled power transformers. Tem

-

perature correction should be to the top oil temperature. 

Compare test results to previous tests or tests on similar 

units. Additional bushing tests should be performed if  test 

results are suspect.

Potential transformers

Potential transformers are installed on power systems for 

the purpose of  stepping down the voltage for the operation 

of  instruments such as Volt-meters, Watt-meters and relays 

for various protective purposes. Typically the secondary 

voltage of  potential transformers is 120 V, so power factor 

testing is performed on the primary winding. Potential 

transformers are typically single phase with either single or 

two bushing primaries. Single bushing primaries have one 

end of  the high voltage winding connected to ground. Sec-

ondary windings are normally three wire and dual identical 

secondary windings are common.

Test connections

Ensure that the potential transformer is disconnected from 

the primary source before testing begins. 

1] 

Remove any fusing on the secondary circuits to 
prevent any type of back-feeding to the secondary.

2] 

Ground one leg of each secondary winding for all 
tests on two primary bushing transformers, for 
dual secondary transformers it is typically X1 and 
Y1.

3] 

Ensure that the case of the potential transformer 
is securely grounded to a system ground before 

testing begins, this also includes testing of spare 
transformers.

Test procedure

Ensure the test set is securely grounded.

1] 

Record all tests results. Power factor tests should 
be corrected to ambient temperature.

2] 

Compare test results to prior tests on the same or 
similar equipment.

Current transformers

Current transformers are used for stepping down primary 

current for Ampere-meters, Watt-meters and for relaying. 

Typical secondary current rating is 5 A. Current transform-

ers have ratings for high voltage and extra high voltage 

application. The higher voltage classifications can be oiled 

filled, dry type or porcelain construction. Tests on two 

bushing primary currents transformers are performed 

by shorting the primary winding, grounding all second-

ary windings and test in the GST mode. Some current 

transformers in the high voltage classifications have test 

taps similar to bushings. Tests can be performed on units 

equipped with a test tap for the C

insulation and the C

tap insulation. Assure that the unit under test is grounded 

before testing. Record all test results and correct the power 

factor readings to the ambient temperature at the time of 

the test.

Voltage regulators

Regulators are generally induction or step-by- step. The 

induction regulator is a special type of transformer, built 

like an induction motor with a coil-wound secondary, which 

is used for varying the voltage delivered to a synchronous 

converter or an ac feeder system. The step-by-step regulator 

is a stationary transformer provided with a large number of  

secondary taps and equipped with a switching mechanism 

for joining any desired pair of  these taps to the delivery 

circuit. Voltage regulators may be single or three phase. 

Single phase regulators consist of three bushings identified 

as S (Source), L (Load) and SL (Neutral). The windings in 

the regulator cannot be effectively separated, so one overall 

power factor test is performed. All the bushings are shorted 

together and tested in the GST-GND test mode. 

Tests should be conducted with the tap changer moved to 

some position off  of  neutral. Additional Hot Collar tests 

may be conducted on bushings of suspect units. Excitation 

tests may also be performed by energizing terminal L with 

the high voltage lead and the low voltage lead on SL in the 

UST position. Terminal S should be left floating. Power 

factor results should be corrected to top oil temperature on 

regulators just taken out of  service. Ambient temperature 

should be used for those that have been out of service for 

any length of  time. Power factor results should be compare 

to previous tests on the same equipment or similar tests on 

similar units.

Содержание DELTA 4000

Страница 1: ...WWW MEGGER COM Reference Manual Applications Guide DELTA4000 12 kV Insulation Diagnostic System ZM AH02E Advanced Test Equipment Rentals www atecorp com 800 404 ATEC 2832 Established 1981...

Страница 2: ......

Страница 3: ...f this document However the information contained in this manual is subject to change without notice and does not represent a commitment on the part of Megger Sweden AB Any attached hardware schematic...

Страница 4: ...nsformer excitation current tests 19 Shunt reactors 21 Potential transformers 21 Current transformers 21 Voltage regulators 21 Dry type transformers 22 Bushings 22 Introduction 22 Definitions 22 Bushi...

Страница 5: ...ZM AH02E DELTA4000 5...

Страница 6: ...HV terminal and the current is measured at the LV terminal Voltage and current are accurately measured in amplitude and phase and CHL capacitance dissipation factor power loss etc are calculated and d...

Страница 7: ...phase angle q q 90 It is more convenient to use the dielectric loss angle d where d 90 q For low power factor insulation Ic and I are substantially of the same mag nitude since the loss component Ir...

Страница 8: ...internal measure ment connections UST Ungrounded specimen testing Test mode Measure Ground Guard UST R Red Blue UST B Blue Red UST RB Red and Blue GST Grounded specimen testing Test mode Measure Grou...

Страница 9: ...ZM AH02E DELTA4000 9 1 Introduction...

Страница 10: ...lar types of insulation used Changes in the normal capacitance of an insulation material indicate such abnormal conditions as the presence of a moisture layer short circuits or open circuits in the ca...

Страница 11: ...factor values Typical power factor values 20 C New Old Warning alert limit Power trans formers oil insulated 0 2 0 4 0 3 0 5 0 5 Bushings 0 2 0 3 0 3 0 5 0 5 IEEE 62 1995 states The power factors reco...

Страница 12: ...ielectric loss which in turn causes a further rise in temperature etc thermal runaway It is important to determine the dissipation factor tempera ture characteristics of the insulation under test Othe...

Страница 13: ...may be contaminated enough to cause a signifi cant error Surfaces of potheads bushings and insulators should be clean and dry when making a measurement It should be noted that a straight line plot of...

Страница 14: ...to the test specimen Other sources for interference may be corona discharges espe cially at high humidity and is some cases DC fluctuations in the grounding system Trouble from magnetic fields encoun...

Страница 15: ...ZM AH02E DELTA4000 15 2 Interpretation of measurements...

Страница 16: ...its from each other and it can increase or decrease the apparent value of a capacitor an inductor or a resistor Furthermore the transformer enables us to transmit electrical energy over great distance...

Страница 17: ...applying any voltage on the transformer make sure that all bushing current transformers are shorted out 4 Never perform electrical tests of any kind on a unit under vacuum Flashovers can occur at volt...

Страница 18: ...additional tests of the tertiary winding In some cases transformers are constructed so that the inter windings are shielded by a grounded electrostatic shield or a concentric winding arrangement This...

Страница 19: ...e Subscripts are test num bers H High voltage winding L Low voltage winding T Tertiary winding G Ground Autotransformers In the design of an autotransformer the secondary winding is actually part of t...

Страница 20: ...nd on wye connected transformers Also note that in many cases the maximum applied voltage is limited by the maximum current output Test voltage must always be the same as prior tests if any comparison...

Страница 21: ...tial transformer is securely grounded to a system ground before testing begins this also includes testing of spare transformers Test procedure Ensure the test set is securely grounded 1 Record all tes...

Страница 22: ...handle high electrical stress they could be subjected to mechanical stresses affiliated with connectors and bus support as well Although a bushing may be thought of as somewhat of a simple device its...

Страница 23: ...e the space between the core and the insulating envelope being filled with oil Resin bonded paper insulated bushing A bushing in which the internal insulation consists of a core wound from resin coate...

Страница 24: ...ual inspection Power factor Tan delta test Hot collar test Dete rioration of cemented joints Moisture enters Oil and or gas leaks Filler leaks out Visual inspection Power factor Tan delta test Hot col...

Страница 25: ...e plate voltage rating of the bushing under test If 10kV exceeds the rating of the bushing test at or slightly below the voltage rating 3 Proceed with the test and record the results 4 Identify each s...

Страница 26: ...5kV to prevent inadvertent damage to the insulation An excessive voltage may puncture the insulation and render the tap useless Some bushings do not have a power factor or capacitance tap or an isola...

Страница 27: ...y and Surface Leakage if tests are made under unfavorable weather conditions Test connections GST Connect a ground wire between the test set and the host apparatus for the bushing under test 1 Install...

Страница 28: ...rminal in that phase should be guarded It is also desirable to test samples of the liquid insulation Oil circuit breakers Oil circuit breakers are composed of a steel tank filled with insulating oil A...

Страница 29: ...uld be recorded on the test form Enter all the nameplate information of the oil circuit breaker Identify each set of readings with the bushing se rial number Record manufacturer type or model and othe...

Страница 30: ...loss indexes without the unit being defec tive or deteriorated The losses in an oil circuit breaker are different between an open circuit test and a closed circuit test because the voltage stress on t...

Страница 31: ...rounded Test procedure Tests are performed at 10kV or a voltage suitable for the insulation rating 1 All tests are conducted with the breaker in the open position 2 Identify each set of readings with...

Страница 32: ...s High capacitance s compared to similar tests may be the result of short circuited sections in one or more of the grading capacitors Vacuum circuit breakers These circuit breakers operate on a differ...

Страница 33: ...voltage or slightly above rated voltage The tip up value is obtained by subtracting the value of the dissipation factor measured at the lower test voltage from that measured at the higher test voltage...

Страница 34: ...t at the winding surface Avoid prolonged exposure to high humidity conditions before testing because such exposure may result in moisture absorption in the insulating materials It is desirable to make...

Страница 35: ...s such as thyrite autovalve etc This material has a resistance that decreases dramatically with increasing volt age Arresters are effectively switching devices that serve as an insulator under normal...

Страница 36: ...dependent non linear may be built into an arrester Except for the specific purpose of investigation surface leak age the exposed insulation surface of an arrester should be clean and dry to prevent le...

Страница 37: ...ate contact is made with the critical areas of the insulation Pe troleum jelly or Dow Corning 4 insulating grease applied at the interface surface often helps to obtain better physical contact It may...

Страница 38: ...imen Test The capacitance value from this test is C1 Figure 14 TTR Capacitor measurement The second step of the procedure is to connect the test set and the HV TTR Capacitor to the transformer winding...

Страница 39: ...ZM AH02E DELTA4000 39 3 Testing power system components that no temperature change has occurred and the trans former ratio determined by this method is correct...

Страница 40: ...nce 14 H High Voltage turns ratio measurements 38 Hot collar test 27 Humidity 13 I IEEE 62 1995 power factor values 11 Insulating envelope 23 Internal insulation 23 Interpretation of measurements 10 I...

Страница 41: ...nnections 36 Surge lightning arresters 35 T Temperature 12 Testing power system components 16 Three winding transformers 18 Transformer excitation current tests 19 Transformers 16 Two winding transfor...

Страница 42: ...eactors IEEE New York 1995 2 US Bureau of Reclamation Transformer Diagnos tics Facility instructions standards and techniques Vol 3 31 2003 3 US Bureau of Reclamation Testing and Mainte nance of High...

Страница 43: ...ZM AH02E DELTA4000 43...

Страница 44: ...TYPES S SI SM TYPE U 0 32 0 1 09 0 93 1 00 1 18 1 26 1 02 1 33 8 1 09 0 94 1 00 1 17 1 25 1 02 2 35 6 1 09 0 95 1 00 1 16 1 24 1 02 3 37 4 1 09 0 96 1 00 1 15 1 22 1 02 4 39 2 1 09 0 97 1 00 1 15 1 2...

Страница 45: ...59 0 1 00 0 95 1 12 1 03 16 60 8 1 00 17 62 6 1 00 18 64 4 1 00 19 66 2 1 00 20 68 0 1 00 1 00 1 00 1 00 21 69 8 1 00 22 71 6 1 00 23 73 4 1 00 24 75 2 1 00 25 77 0 1 00 1 04 0 89 0 97 26 78 8 1 00 2...

Страница 46: ...46 DELTA4000 ZM AH02E...

Страница 47: ...ZM AH02E DELTA4000 47...

Страница 48: ...d Dover CT17 9EN England T 44 0 1304 502101 F 44 0 1304 207342 E UKsales megger com Other Technical Sales Offices Dallas USA Toronto CANADA Trappes FRANCE Oberursel GERMANY Oberkulm SWITZERLAND Johann...

Отзывы: