background image

38

DELTA 4000 

ZM-AH02E

3 TESTING POWER SYSTEM COMPONENTS

High-Voltage turns-ratio 

measurements

Ratio measurements on HV transformers are commonly 

made using low voltage instruments designed specifically 

for that purpose. Those test instruments apply a relatively 

low voltage (<100V) to either the primary or the secondary 

of  the transformer. The resultant voltage is measured and 

the voltage ratio is calculated automatically by the test set. 
Occasionally there are instances when it is desired to 

perform higher voltage ratio tests for diagnostic purposes. 

Using a power factor test set like the Delta4000, voltages of  

up to 12kV can be applied to a transformer winding, gener-

ating a higher turn-to-turn stress on the winding under test. 

It is believed that higher voltage stress on a winding may 

break down weak turn-to-turn insulation and help detect 

faults that might be overlooked by low voltage test equip-

ment. It is important to recognize that the voltage rating 

of  the winding being energized must not be exceeded or 

damage to good insulation may result.

Test procedure

Determining the ratio of  a transformer using the HV TTR 

Capacitor involves taking a capacitance measurement of the 

HV TTR Capacitor by itself, then taking another measure-

ment with the capacitor connected to the low-voltage wind-

ing of  the transformer. The ratio of  the capacitance values 

is equal to the voltage ratio of  the transformer windings. 

The figures below will help explain the procedure.

Figure 1 shows the connection used for accurately deter-

mining the capacitance value of  the HV TTR Capacitor. 

The instrument HV output lead is connected to one side of 

the capacitor, and a LV measuring lead is connected to the 

other side. Both connections must be isolated from ground, 

and the test set measuring configuration should be UST 

(Ungrounded Specimen Test). The capacitance value from 

this test is C1.

Figure 14: TTR Capacitor measurement

The second step of  the procedure is to connect the test set 

and the HV TTR Capacitor to the transformer winding to 

be tested. Figure 2 shows this connection on a single-phase 

transformer. The test set output is connected to one end 

of  the high voltage winding. The other side of  the winding 

must be grounded. The HV TTR Capacitor is connected to 

one end of  the low voltage winding, and is then connected 

to the measuring lead of the test set. The other side of  the 

low voltage winding is grounded as well.

Figure 15: Single-phase transformer

The test set measuring configuration should again be UST. 

The value of  capacitance from this measurement will be 

identified as C2. NOTE: The polarity of  the winding con

-

nections should be made per the polarity markings shown 

on the nameplate of  the transformer.
Once the values of  C1 and C2 have been established, the 

ratio (N) of  the transformer (for the tap connection being 

measured) is determined as;

N = C1 / C2

The procedure for testing a three-phase transformer is 

the same as that for single-phase. Figure 3 shows a typi-

cal three-phase configuration (Δ-Δ). As in the previous 

example, connect the HV output lead to the high voltage 

winding, and the capacitor plus low voltage measuring lead 

to the low voltage winding.

Figure 16: Three-phase Delta-Delta transformer

The test set measuring configuration should again be UST. 

The capacitance reading obtained from this measurement is 

also identified as C2. Calculate the transformer ratio using 

the same formula as the previous example.
For further example, Figure 4 is provided to show a three-

phase delta-wye transformer winding and the connections 

that are required.

Figure 17: Three-phase Delta-Wye transformer

Temperature considerations

Due to the design of HV TTR Capacitors, their capacitance 

value may be sensitive to changes in temperature. Once the 

value of  C1 is obtained, it is recommended to promptly 

take the C2 measurement without delay. This will ensure 

Содержание DELTA 4000

Страница 1: ...WWW MEGGER COM Reference Manual Applications Guide DELTA4000 12 kV Insulation Diagnostic System ZM AH02E Advanced Test Equipment Rentals www atecorp com 800 404 ATEC 2832 Established 1981...

Страница 2: ......

Страница 3: ...f this document However the information contained in this manual is subject to change without notice and does not represent a commitment on the part of Megger Sweden AB Any attached hardware schematic...

Страница 4: ...nsformer excitation current tests 19 Shunt reactors 21 Potential transformers 21 Current transformers 21 Voltage regulators 21 Dry type transformers 22 Bushings 22 Introduction 22 Definitions 22 Bushi...

Страница 5: ...ZM AH02E DELTA4000 5...

Страница 6: ...HV terminal and the current is measured at the LV terminal Voltage and current are accurately measured in amplitude and phase and CHL capacitance dissipation factor power loss etc are calculated and d...

Страница 7: ...phase angle q q 90 It is more convenient to use the dielectric loss angle d where d 90 q For low power factor insulation Ic and I are substantially of the same mag nitude since the loss component Ir...

Страница 8: ...internal measure ment connections UST Ungrounded specimen testing Test mode Measure Ground Guard UST R Red Blue UST B Blue Red UST RB Red and Blue GST Grounded specimen testing Test mode Measure Grou...

Страница 9: ...ZM AH02E DELTA4000 9 1 Introduction...

Страница 10: ...lar types of insulation used Changes in the normal capacitance of an insulation material indicate such abnormal conditions as the presence of a moisture layer short circuits or open circuits in the ca...

Страница 11: ...factor values Typical power factor values 20 C New Old Warning alert limit Power trans formers oil insulated 0 2 0 4 0 3 0 5 0 5 Bushings 0 2 0 3 0 3 0 5 0 5 IEEE 62 1995 states The power factors reco...

Страница 12: ...ielectric loss which in turn causes a further rise in temperature etc thermal runaway It is important to determine the dissipation factor tempera ture characteristics of the insulation under test Othe...

Страница 13: ...may be contaminated enough to cause a signifi cant error Surfaces of potheads bushings and insulators should be clean and dry when making a measurement It should be noted that a straight line plot of...

Страница 14: ...to the test specimen Other sources for interference may be corona discharges espe cially at high humidity and is some cases DC fluctuations in the grounding system Trouble from magnetic fields encoun...

Страница 15: ...ZM AH02E DELTA4000 15 2 Interpretation of measurements...

Страница 16: ...its from each other and it can increase or decrease the apparent value of a capacitor an inductor or a resistor Furthermore the transformer enables us to transmit electrical energy over great distance...

Страница 17: ...applying any voltage on the transformer make sure that all bushing current transformers are shorted out 4 Never perform electrical tests of any kind on a unit under vacuum Flashovers can occur at volt...

Страница 18: ...additional tests of the tertiary winding In some cases transformers are constructed so that the inter windings are shielded by a grounded electrostatic shield or a concentric winding arrangement This...

Страница 19: ...e Subscripts are test num bers H High voltage winding L Low voltage winding T Tertiary winding G Ground Autotransformers In the design of an autotransformer the secondary winding is actually part of t...

Страница 20: ...nd on wye connected transformers Also note that in many cases the maximum applied voltage is limited by the maximum current output Test voltage must always be the same as prior tests if any comparison...

Страница 21: ...tial transformer is securely grounded to a system ground before testing begins this also includes testing of spare transformers Test procedure Ensure the test set is securely grounded 1 Record all tes...

Страница 22: ...handle high electrical stress they could be subjected to mechanical stresses affiliated with connectors and bus support as well Although a bushing may be thought of as somewhat of a simple device its...

Страница 23: ...e the space between the core and the insulating envelope being filled with oil Resin bonded paper insulated bushing A bushing in which the internal insulation consists of a core wound from resin coate...

Страница 24: ...ual inspection Power factor Tan delta test Hot collar test Dete rioration of cemented joints Moisture enters Oil and or gas leaks Filler leaks out Visual inspection Power factor Tan delta test Hot col...

Страница 25: ...e plate voltage rating of the bushing under test If 10kV exceeds the rating of the bushing test at or slightly below the voltage rating 3 Proceed with the test and record the results 4 Identify each s...

Страница 26: ...5kV to prevent inadvertent damage to the insulation An excessive voltage may puncture the insulation and render the tap useless Some bushings do not have a power factor or capacitance tap or an isola...

Страница 27: ...y and Surface Leakage if tests are made under unfavorable weather conditions Test connections GST Connect a ground wire between the test set and the host apparatus for the bushing under test 1 Install...

Страница 28: ...rminal in that phase should be guarded It is also desirable to test samples of the liquid insulation Oil circuit breakers Oil circuit breakers are composed of a steel tank filled with insulating oil A...

Страница 29: ...uld be recorded on the test form Enter all the nameplate information of the oil circuit breaker Identify each set of readings with the bushing se rial number Record manufacturer type or model and othe...

Страница 30: ...loss indexes without the unit being defec tive or deteriorated The losses in an oil circuit breaker are different between an open circuit test and a closed circuit test because the voltage stress on t...

Страница 31: ...rounded Test procedure Tests are performed at 10kV or a voltage suitable for the insulation rating 1 All tests are conducted with the breaker in the open position 2 Identify each set of readings with...

Страница 32: ...s High capacitance s compared to similar tests may be the result of short circuited sections in one or more of the grading capacitors Vacuum circuit breakers These circuit breakers operate on a differ...

Страница 33: ...voltage or slightly above rated voltage The tip up value is obtained by subtracting the value of the dissipation factor measured at the lower test voltage from that measured at the higher test voltage...

Страница 34: ...t at the winding surface Avoid prolonged exposure to high humidity conditions before testing because such exposure may result in moisture absorption in the insulating materials It is desirable to make...

Страница 35: ...s such as thyrite autovalve etc This material has a resistance that decreases dramatically with increasing volt age Arresters are effectively switching devices that serve as an insulator under normal...

Страница 36: ...dependent non linear may be built into an arrester Except for the specific purpose of investigation surface leak age the exposed insulation surface of an arrester should be clean and dry to prevent le...

Страница 37: ...ate contact is made with the critical areas of the insulation Pe troleum jelly or Dow Corning 4 insulating grease applied at the interface surface often helps to obtain better physical contact It may...

Страница 38: ...imen Test The capacitance value from this test is C1 Figure 14 TTR Capacitor measurement The second step of the procedure is to connect the test set and the HV TTR Capacitor to the transformer winding...

Страница 39: ...ZM AH02E DELTA4000 39 3 Testing power system components that no temperature change has occurred and the trans former ratio determined by this method is correct...

Страница 40: ...nce 14 H High Voltage turns ratio measurements 38 Hot collar test 27 Humidity 13 I IEEE 62 1995 power factor values 11 Insulating envelope 23 Internal insulation 23 Interpretation of measurements 10 I...

Страница 41: ...nnections 36 Surge lightning arresters 35 T Temperature 12 Testing power system components 16 Three winding transformers 18 Transformer excitation current tests 19 Transformers 16 Two winding transfor...

Страница 42: ...eactors IEEE New York 1995 2 US Bureau of Reclamation Transformer Diagnos tics Facility instructions standards and techniques Vol 3 31 2003 3 US Bureau of Reclamation Testing and Mainte nance of High...

Страница 43: ...ZM AH02E DELTA4000 43...

Страница 44: ...TYPES S SI SM TYPE U 0 32 0 1 09 0 93 1 00 1 18 1 26 1 02 1 33 8 1 09 0 94 1 00 1 17 1 25 1 02 2 35 6 1 09 0 95 1 00 1 16 1 24 1 02 3 37 4 1 09 0 96 1 00 1 15 1 22 1 02 4 39 2 1 09 0 97 1 00 1 15 1 2...

Страница 45: ...59 0 1 00 0 95 1 12 1 03 16 60 8 1 00 17 62 6 1 00 18 64 4 1 00 19 66 2 1 00 20 68 0 1 00 1 00 1 00 1 00 21 69 8 1 00 22 71 6 1 00 23 73 4 1 00 24 75 2 1 00 25 77 0 1 00 1 04 0 89 0 97 26 78 8 1 00 2...

Страница 46: ...46 DELTA4000 ZM AH02E...

Страница 47: ...ZM AH02E DELTA4000 47...

Страница 48: ...d Dover CT17 9EN England T 44 0 1304 502101 F 44 0 1304 207342 E UKsales megger com Other Technical Sales Offices Dallas USA Toronto CANADA Trappes FRANCE Oberursel GERMANY Oberkulm SWITZERLAND Johann...

Отзывы: