AVTM21-415Ja Rev. A June 2005
4.
With voltage control set for 15 kV output, set stabilizer to
"IN". Voltage should drop to about 13.5 kV.
5.
Follow the shutdown procedure given in Section 8.
6.
Connect the high voltage output to ground.
7.
Set the voltmeter range to 7.5 kV and the megohmmeter
range to X1, stabilizer "OUT".
8.
Operate the set and very carefully turn up the voltage
control.
Note that the megohmmeter moves to full deflection.
9.
After reaching full scale on the X1 megohm range,
advance the voltage control to 25: either or both circuit
breakers must trip in 20 seconds or less with a supply
voltage of 117 volts or more. If the supply voltage is
between 105 and 117 the time for tripping may be as long
as 40 seconds.
10.
Shut down as described in Section 8.
Содержание ATEC 210415 Series
Страница 2: ...15 kV Megohmmeter Test Set Catalog No 210415 Series M...
Страница 9: ...M 2 AVTM21 415Ja Rev A June 2005 Figure 1 15 kV Megohmmeter Test Set Catalog No 210415...
Страница 13: ...M 6 AVTM21 415Ja Rev A June 2005 M...
Страница 19: ...M 12 AVTM21 415Ja Rev A June 2005 M...
Страница 23: ...M 16 AVTM21 415Ja Rev A June 2005 Figure 2 Schematic Diagram of the 15 kV Megohmmeter...
Страница 30: ...SETTING UP 23 AVTM21 415Ja Rev A June 2005 Figure 4 Testing in a Substation...
Страница 32: ...SETTING UP 25 AVTM21 415Ja Rev A June 2005 Figure 6 Testing Transformer Terminals...
Страница 33: ...M 26 AVTM21 415Ja Rev A June 2005 Figure 7 DC Motor Test Setup Figure 8 Generator Test Setup...
Страница 47: ...M 40 AVTM21 415Ja Rev A June 2005 M...
Страница 53: ...M 46 AVTM21 415Ja Rev A June 2005 M...
Страница 57: ...M 50 AVTM21 415Ja Rev A June 2005 M...
Страница 73: ...M 66 AVTM21 415Ja Rev A June 2005 Figure 15A Interior View Figure 15B Interior View...
Страница 75: ...M 68 AVTM21 415Ja Rev A June 2005 M...
Страница 81: ...M 74 AVTM21 415Ja Rev A June 2005 M...
Страница 82: ...M 2621 Van Buren Avenue Norristown PA 19403 1 800 723 2861 ext 8578 megger com...