Commissioning of solar controller
Programming Menu (Fig 25)
All adjustable parameters can be checked in this menu and,
if necessary, changed. The default factory setting will usually
give efficient and problem free operation. However we
recommend the following parameters marked * must be left
at the default settings. Any change to our recommended
settings will invalidate the warranty.
For more information or guidance please contact the
Technical Enquiries.
27
© Baxi Heating UK 2012
11.0
Commissioning of solar controller
11.4
Menu “Programming”
1.All adjustable parameters can be checked in this menu and, if
necessary, changed. The default factory setting will usually give
efficient and problem free operation. However Baxi recommend
the following parameters marked * must be left at the default
settings. Any change to the Baxi recommended settings will
invalidate the warranty.
2. For more information or guidance please contact the Technical
Enquiries.
Press or to scroll
up or down to the required sub function.
The icon will flash, press to
select the function. Reset by pressing
or for
increase/decrease values. Press
and appears,
press to confirm and
disappears.
ok?
ok?
13:21
Time
0:00 - 23:59
12:00
dT max
7K
Min
100
Storage tank
Maximum permissible
temperature
40 °C
Meaning
dT
10 K
3 - 40K
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Storage tank
switch-off differential (dToff)
2 - 35K
Adjustment of pump rotational
speed.
100% = rotational speed
regulation set to 'off'
7K
1 - 30K
Switch-on temperature for
Heating/Cooling function
Hysteresis for Heating/Cooling
function
10K
30% - 100%
Value range
20 - 90°C
Typical
adjustment
3 - 40K
7K
3K
15 - 65°C
Indication
dT min
3 K
dT max
7 K
max
65 °C
65°C*
MAX
Storage tank
switch-on differential (dTon)
100%
40°C
2
2 - 35K
3K
min
00:00
1(2,3)
Timeframe 1(2,3): Start
0:00 - 23:59
00:00
dT min
3K
Timeframe 1(2,3): Start for the
collector function
0:00 - 23:59
06:00
max
23:59
1(2,3)
Timeframe 1(2,3): Stop
0:00 - 23:59
20:00
max
20:00
4
Timeframe 1(2,3):
Stop for the collector function
0:00 - 23:59
23:59
min
06:00
4
Meaning
Value range
Typical
adjustment
Indication
Fig. 30
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Figure 25
Indication
27
© Baxi Heating UK 2012
11.0
Commissioning of solar controller
11.4
Menu “Programming”
1.All adjustable parameters can be checked in this menu and, if
necessary, changed. The default factory setting will usually give
efficient and problem free operation. However Baxi recommend
the following parameters marked * must be left at the default
settings. Any change to the Baxi recommended settings will
invalidate the warranty.
2. For more information or guidance please contact the Technical
Enquiries.
Press or to scroll
up or down to the required sub function.
The icon will flash, press to
select the function. Reset by pressing
or for
increase/decrease values. Press
and appears,
press to confirm and
disappears.
ok?
ok?
13:21
Time
0:00 - 23:59
12:00
dT max
7K
Min
100
Storage tank
Maximum permissible
temperature
40 °C
Meaning
dT
10 K
3 - 40K
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Storage tank
switch-off differential (dToff)
2 - 35K
Adjustment of pump rotational
speed.
100% = rotational speed
regulation set to 'off'
7K
1 - 30K
Switch-on temperature for
Heating/Cooling function
Hysteresis for Heating/Cooling
function
10K
30% - 100%
Value range
20 - 90°C
Typical
adjustment
3 - 40K
7K
3K
15 - 65°C
Indication
dT min
3 K
dT max
7 K
max
65 °C
65°C*
MAX
Storage tank
switch-on differential (dTon)
100%
40°C
2
2 - 35K
3K
min
00:00
1(2,3)
Timeframe 1(2,3): Start
0:00 - 23:59
00:00
dT min
3K
Timeframe 1(2,3): Start for the
collector function
0:00 - 23:59
06:00
max
23:59
1(2,3)
Timeframe 1(2,3): Stop
0:00 - 23:59
20:00
max
20:00
4
Timeframe 1(2,3):
Stop for the collector function
0:00 - 23:59
23:59
min
06:00
4
Meaning
Value range
Typical
adjustment
Indication
Fig. 30
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Meaning
Value range
Typical
adjustment
max. 65ºC
27
© Baxi Heating UK 2012
11.0
Commissioning of solar controller
11.4
Menu “Programming”
1.All adjustable parameters can be checked in this menu and, if
necessary, changed. The default factory setting will usually give
efficient and problem free operation. However Baxi recommend
the following parameters marked * must be left at the default
settings. Any change to the Baxi recommended settings will
invalidate the warranty.
2. For more information or guidance please contact the Technical
Enquiries.
Press or to scroll
up or down to the required sub function.
The icon will flash, press to
select the function. Reset by pressing
or for
increase/decrease values. Press
and appears,
press to confirm and
disappears.
ok?
ok?
13:21
Time
0:00 - 23:59
12:00
dT max
7K
Min
100
Storage tank
Maximum permissible
temperature
40 °C
Meaning
dT
10 K
3 - 40K
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Storage tank
switch-off differential (dToff)
2 - 35K
Adjustment of pump rotational
speed.
100% = rotational speed
regulation set to 'off'
7K
1 - 30K
Switch-on temperature for
Heating/Cooling function
Hysteresis for Heating/Cooling
function
10K
30% - 100%
Value range
20 - 90°C
Typical
adjustment
3 - 40K
7K
3K
15 - 65°C
Indication
dT min
3 K
dT max
7 K
max
65 °C
65°C*
MAX
Storage tank
switch-on differential (dTon)
100%
40°C
2
2 - 35K
3K
min
00:00
1(2,3)
Timeframe 1(2,3): Start
0:00 - 23:59
00:00
dT min
3K
Timeframe 1(2,3): Start for the
collector function
0:00 - 23:59
06:00
max
23:59
1(2,3)
Timeframe 1(2,3): Stop
0:00 - 23:59
20:00
max
20:00
4
Timeframe 1(2,3):
Stop for the collector function
0:00 - 23:59
23:59
min
06:00
4
Meaning
Value range
Typical
adjustment
Indication
Fig. 30
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Storage tank – max.
permissable temperature.
15-65ºC
65ºC* MAX
dT max. 7K
27
© Baxi Heating UK 2012
11.0
Commissioning of solar controller
11.4
Menu “Programming”
1.All adjustable parameters can be checked in this menu and, if
necessary, changed. The default factory setting will usually give
efficient and problem free operation. However Baxi recommend
the following parameters marked * must be left at the default
settings. Any change to the Baxi recommended settings will
invalidate the warranty.
2. For more information or guidance please contact the Technical
Enquiries.
Press or to scroll
up or down to the required sub function.
The icon will flash, press to
select the function. Reset by pressing
or for
increase/decrease values. Press
and appears,
press to confirm and
disappears.
ok?
ok?
13:21
Time
0:00 - 23:59
12:00
dT max
7K
Min
100
Storage tank
Maximum permissible
temperature
40 °C
Meaning
dT
10 K
3 - 40K
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Storage tank
switch-off differential (dToff)
2 - 35K
Adjustment of pump rotational
speed.
100% = rotational speed
regulation set to 'off'
7K
1 - 30K
Switch-on temperature for
Heating/Cooling function
Hysteresis for Heating/Cooling
function
10K
30% - 100%
Value range
20 - 90°C
Typical
adjustment
3 - 40K
7K
3K
15 - 65°C
Indication
dT min
3 K
dT max
7 K
max
65 °C
65°C*
MAX
Storage tank
switch-on differential (dTon)
100%
40°C
2
2 - 35K
3K
min
00:00
1(2,3)
Timeframe 1(2,3): Start
0:00 - 23:59
00:00
dT min
3K
Timeframe 1(2,3): Start for the
collector function
0:00 - 23:59
06:00
max
23:59
1(2,3)
Timeframe 1(2,3): Stop
0:00 - 23:59
20:00
max
20:00
4
Timeframe 1(2,3):
Stop for the collector function
0:00 - 23:59
23:59
min
06:00
4
Meaning
Value range
Typical
adjustment
Indication
Fig. 30
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Storage tank – switch-on
differential (dTon).
3-40K
7K
dT min. 3K
27
© Baxi Heating UK 2012
11.0
Commissioning of solar controller
11.4
Menu “Programming”
1.All adjustable parameters can be checked in this menu and, if
necessary, changed. The default factory setting will usually give
efficient and problem free operation. However Baxi recommend
the following parameters marked * must be left at the default
settings. Any change to the Baxi recommended settings will
invalidate the warranty.
2. For more information or guidance please contact the Technical
Enquiries.
Press or to scroll
up or down to the required sub function.
The icon will flash, press to
select the function. Reset by pressing
or for
increase/decrease values. Press
and appears,
press to confirm and
disappears.
ok?
ok?
13:21
Time
0:00 - 23:59
12:00
dT max
7K
Min
100
Storage tank
Maximum permissible
temperature
40 °C
Meaning
dT
10 K
3 - 40K
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Storage tank
switch-off differential (dToff)
2 - 35K
Adjustment of pump rotational
speed.
100% = rotational speed
regulation set to 'off'
7K
1 - 30K
Switch-on temperature for
Heating/Cooling function
Hysteresis for Heating/Cooling
function
10K
30% - 100%
Value range
20 - 90°C
Typical
adjustment
3 - 40K
7K
3K
15 - 65°C
Indication
dT min
3 K
dT max
7 K
max
65 °C
65°C*
MAX
Storage tank
switch-on differential (dTon)
100%
40°C
2
2 - 35K
3K
min
00:00
1(2,3)
Timeframe 1(2,3): Start
0:00 - 23:59
00:00
dT min
3K
Timeframe 1(2,3): Start for the
collector function
0:00 - 23:59
06:00
max
23:59
1(2,3)
Timeframe 1(2,3): Stop
0:00 - 23:59
20:00
max
20:00
4
Timeframe 1(2,3):
Stop for the collector function
0:00 - 23:59
23:59
min
06:00
4
Meaning
Value range
Typical
adjustment
Indication
Fig. 30
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Storage tank – switch-off
differential (dToff).
2-35K
3K
min. 100
27
© Baxi Heating UK 2012
11.0
Commissioning of solar controller
11.4
Menu “Programming”
1.All adjustable parameters can be checked in this menu and, if
necessary, changed. The default factory setting will usually give
efficient and problem free operation. However Baxi recommend
the following parameters marked * must be left at the default
settings. Any change to the Baxi recommended settings will
invalidate the warranty.
2. For more information or guidance please contact the Technical
Enquiries.
Press or to scroll
up or down to the required sub function.
The icon will flash, press to
select the function. Reset by pressing
or for
increase/decrease values. Press
and appears,
press to confirm and
disappears.
ok?
ok?
13:21
Time
0:00 - 23:59
12:00
dT max
7K
Min
100
Storage tank
Maximum permissible
temperature
40 °C
Meaning
dT
10 K
3 - 40K
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Storage tank
switch-off differential (dToff)
2 - 35K
Adjustment of pump rotational
speed.
100% = rotational speed
regulation set to 'off'
7K
1 - 30K
Switch-on temperature for
Heating/Cooling function
Hysteresis for Heating/Cooling
function
10K
30% - 100%
Value range
20 - 90°C
Typical
adjustment
3 - 40K
7K
3K
15 - 65°C
Indication
dT min
3 K
dT max
7 K
max
65 °C
65°C*
MAX
Storage tank
switch-on differential (dTon)
100%
40°C
2
2 - 35K
3K
min
00:00
1(2,3)
Timeframe 1(2,3): Start
0:00 - 23:59
00:00
dT min
3K
Timeframe 1(2,3): Start for the
collector function
0:00 - 23:59
06:00
max
23:59
1(2,3)
Timeframe 1(2,3): Stop
0:00 - 23:59
20:00
max
20:00
4
Timeframe 1(2,3):
Stop for the collector function
0:00 - 23:59
23:59
min
06:00
4
Meaning
Value range
Typical
adjustment
Indication
Fig. 30
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Adjustment of pump
rotational speed.
100% = rotational speed
regulation set to "off."
30-100%
100%
13:21
Time
0:00-23:59
12:00
40ºC
27
© Baxi Heating UK 2012
11.0
Commissioning of solar controller
11.4
Menu “Programming”
1.All adjustable parameters can be checked in this menu and, if
necessary, changed. The default factory setting will usually give
efficient and problem free operation. However Baxi recommend
the following parameters marked * must be left at the default
settings. Any change to the Baxi recommended settings will
invalidate the warranty.
2. For more information or guidance please contact the Technical
Enquiries.
Press or to scroll
up or down to the required sub function.
The icon will flash, press to
select the function. Reset by pressing
or for
increase/decrease values. Press
and appears,
press to confirm and
disappears.
ok?
ok?
13:21
Time
0:00 - 23:59
12:00
dT max
7K
Min
100
Storage tank
Maximum permissible
temperature
40 °C
Meaning
dT
10 K
3 - 40K
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Storage tank
switch-off differential (dToff)
2 - 35K
Adjustment of pump rotational
speed.
100% = rotational speed
regulation set to 'off'
7K
1 - 30K
Switch-on temperature for
Heating/Cooling function
Hysteresis for Heating/Cooling
function
10K
30% - 100%
Value range
20 - 90°C
Typical
adjustment
3 - 40K
7K
3K
15 - 65°C
Indication
dT min
3 K
dT max
7 K
max
65 °C
65°C*
MAX
Storage tank
switch-on differential (dTon)
100%
40°C
2
2 - 35K
3K
min
00:00
1(2,3)
Timeframe 1(2,3): Start
0:00 - 23:59
00:00
dT min
3K
Timeframe 1(2,3): Start for the
collector function
0:00 - 23:59
06:00
max
23:59
1(2,3)
Timeframe 1(2,3): Stop
0:00 - 23:59
20:00
max
20:00
4
Timeframe 1(2,3):
Stop for the collector function
0:00 - 23:59
23:59
min
06:00
4
Meaning
Value range
Typical
adjustment
Indication
Fig. 30
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Switch-on temperature
for heating / cooling
function.
20-90ºC
40ºC
dT 10 K
27
© Baxi Heating UK 2012
11.0
Commissioning of solar controller
11.4
Menu “Programming”
1.All adjustable parameters can be checked in this menu and, if
necessary, changed. The default factory setting will usually give
efficient and problem free operation. However Baxi recommend
the following parameters marked * must be left at the default
settings. Any change to the Baxi recommended settings will
invalidate the warranty.
2. For more information or guidance please contact the Technical
Enquiries.
Press or to scroll
up or down to the required sub function.
The icon will flash, press to
select the function. Reset by pressing
or for
increase/decrease values. Press
and appears,
press to confirm and
disappears.
ok?
ok?
13:21
Time
0:00 - 23:59
12:00
dT max
7K
Min
100
Storage tank
Maximum permissible
temperature
40 °C
Meaning
dT
10 K
3 - 40K
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Storage tank
switch-off differential (dToff)
2 - 35K
Adjustment of pump rotational
speed.
100% = rotational speed
regulation set to 'off'
7K
1 - 30K
Switch-on temperature for
Heating/Cooling function
Hysteresis for Heating/Cooling
function
10K
30% - 100%
Value range
20 - 90°C
Typical
adjustment
3 - 40K
7K
3K
15 - 65°C
Indication
dT min
3 K
dT max
7 K
max
65 °C
65°C*
MAX
Storage tank
switch-on differential (dTon)
100%
40°C
2
2 - 35K
3K
min
00:00
1(2,3)
Timeframe 1(2,3): Start
0:00 - 23:59
00:00
dT min
3K
Timeframe 1(2,3): Start for the
collector function
0:00 - 23:59
06:00
max
23:59
1(2,3)
Timeframe 1(2,3): Stop
0:00 - 23:59
20:00
max
20:00
4
Timeframe 1(2,3):
Stop for the collector function
0:00 - 23:59
23:59
min
06:00
4
Meaning
Value range
Typical
adjustment
Indication
Fig. 30
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Hysteresis for heating /
cooling function.
1-30K
10K
dT max. 7K
27
© Baxi Heating UK 2012
11.0
Commissioning of solar controller
11.4
Menu “Programming”
1.All adjustable parameters can be checked in this menu and, if
necessary, changed. The default factory setting will usually give
efficient and problem free operation. However Baxi recommend
the following parameters marked * must be left at the default
settings. Any change to the Baxi recommended settings will
invalidate the warranty.
2. For more information or guidance please contact the Technical
Enquiries.
Press or to scroll
up or down to the required sub function.
The icon will flash, press to
select the function. Reset by pressing
or for
increase/decrease values. Press
and appears,
press to confirm and
disappears.
ok?
ok?
13:21
Time
0:00 - 23:59
12:00
dT max
7K
Min
100
Storage tank
Maximum permissible
temperature
40 °C
Meaning
dT
10 K
3 - 40K
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Storage tank
switch-off differential (dToff)
2 - 35K
Adjustment of pump rotational
speed.
100% = rotational speed
regulation set to 'off'
7K
1 - 30K
Switch-on temperature for
Heating/Cooling function
Hysteresis for Heating/Cooling
function
10K
30% - 100%
Value range
20 - 90°C
Typical
adjustment
3 - 40K
7K
3K
15 - 65°C
Indication
dT min
3 K
dT max
7 K
max
65 °C
65°C*
MAX
Storage tank
switch-on differential (dTon)
100%
40°C
2
2 - 35K
3K
min
00:00
1(2,3)
Timeframe 1(2,3): Start
0:00 - 23:59
00:00
dT min
3K
Timeframe 1(2,3): Start for the
collector function
0:00 - 23:59
06:00
max
23:59
1(2,3)
Timeframe 1(2,3): Stop
0:00 - 23:59
20:00
max
20:00
4
Timeframe 1(2,3):
Stop for the collector function
0:00 - 23:59
23:59
min
06:00
4
Meaning
Value range
Typical
adjustment
Indication
Fig. 30
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Temperature difference
controller – hysteresis
dT max. Not used in this
configuration.
3-40K
7K
dT min. 3K
27
© Baxi Heating UK 2012
11.0
Commissioning of solar controller
11.4
Menu “Programming”
1.All adjustable parameters can be checked in this menu and, if
necessary, changed. The default factory setting will usually give
efficient and problem free operation. However Baxi recommend
the following parameters marked * must be left at the default
settings. Any change to the Baxi recommended settings will
invalidate the warranty.
2. For more information or guidance please contact the Technical
Enquiries.
Press or to scroll
up or down to the required sub function.
The icon will flash, press to
select the function. Reset by pressing
or for
increase/decrease values. Press
and appears,
press to confirm and
disappears.
ok?
ok?
13:21
Time
0:00 - 23:59
12:00
dT max
7K
Min
100
Storage tank
Maximum permissible
temperature
40 °C
Meaning
dT
10 K
3 - 40K
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Storage tank
switch-off differential (dToff)
2 - 35K
Adjustment of pump rotational
speed.
100% = rotational speed
regulation set to 'off'
7K
1 - 30K
Switch-on temperature for
Heating/Cooling function
Hysteresis for Heating/Cooling
function
10K
30% - 100%
Value range
20 - 90°C
Typical
adjustment
3 - 40K
7K
3K
15 - 65°C
Indication
dT min
3 K
dT max
7 K
max
65 °C
65°C*
MAX
Storage tank
switch-on differential (dTon)
100%
40°C
2
2 - 35K
3K
min
00:00
1(2,3)
Timeframe 1(2,3): Start
0:00 - 23:59
00:00
dT min
3K
Timeframe 1(2,3): Start for the
collector function
0:00 - 23:59
06:00
max
23:59
1(2,3)
Timeframe 1(2,3): Stop
0:00 - 23:59
20:00
max
20:00
4
Timeframe 1(2,3):
Stop for the collector function
0:00 - 23:59
23:59
min
06:00
4
Meaning
Value range
Typical
adjustment
Indication
Fig. 30
Temperature difference
controller. Hysteresis dT max
Not used in this configuration
Temperature difference
controller – hysteresis
dT min. Not used in this
configuration.
2-35K
3K
min. 00:00
1(2,3)
Timeframe 1(2,3): Start.
0:00-23:59
00:00
max. 23:59
1(2,3)
Timeframe 1(2,3): Stop
0:00-23:59
23:59
min.
06:00 4
Timeframe 1(2,3): Start
for the collector function.
0:00-23:59
06:00
max.
20:00 4
Timeframe 1(2,3):
Stop for the controller
function.
0:00-23:59
20:00
Содержание Eco SolaReady
Страница 1: ...Hot Water Cylinders MEGAFLO Eco SolaReady Unvented MEGAFLO Eco SolaReady Product Guide...
Страница 48: ...SERVICING 48...
Страница 50: ...SERVICING 50...
Страница 51: ...SERVICING 51 Notes...