LED Status
When the equipment powers on, the LED will show green whilst the system monitors
the bars performance. If it then starts to flash red or go solid red, check the ion level
with the BarMaster.
Solid Green
indicates there is no BarMaster connected.
Flashing Green
indicates the BarMaster has been connected.
Flashing Red
indicates more cleaning required.
Solid Red
indicates the ion level has dropped well below the alarm setting, prompting
a serious fault warning. Check installation for metallic objects on the emitter pins.
If the Output voltage was reduced for example from 7500V to 4000V and the Ion level
was not reset. This will affect the calibration and the bar will alarm repeatedly after a
short period. Adjust the output voltage to 7500V and ensure the ion level reads 99%
and the LED is green.
A.
If Ion level is 0% bar is faulty.
B.
If 10-59% with a 60% alarm setting, return to the clean bar section.
If after cleaning an Ion level of 80-99% is reached, you should then reduce the output
voltage to the required level. Only then can you reset the Ion Ref.
If the Ion level is well below the alarm level % the Ion output, it will shut down and a
solid red LED will show. Should the solid red LED persist, connect your BarMaster and
follow the Troubleshooting section or contact your local Meech distributor.