17
The graph below shows air consumption at varying inlet air pressures.
Inlet Air Pressure (psi)
Air Consumption (cfm
)
0
5
10
15
20
25
30
35
40
A20035, A24036
A20025, A24026
A20015, A24016
A20010, A24011
A20008, A21008
100
80
60
40
20
4 x High fraction generators are supplied as standard:
Yellow 10cfm (283 l/min) - Cooling capacity of 190W (650 Btu/hr)
Red 15cfm (425 l/min) – Cooling capacity of 293W (1000 Btu/hr)
Blue 25cfm (708 l/min) – Cooling capacity of 499W (1,700 Btu/hr)
Brown 35cfm (991 l/min) – Cooling capacity of 703W (2,400 Btu/hr)
A single Meech Cabinet Cooler is capable of cooling up to 703 Watts (2,400 Btu/hr).
Optimising the cooling capacity is still a vitally important factor, choosing the correct
generator will not only reduce running costs but also extend the life of the compressor.
To choose the most efficient generator you must calculate the total heat load in Watts
Btu/hr to which the enclosure is exposed. The total heat load is a combination of
the heat transfer from outside due to ambient air temperature and the heat which is
created internally.
For more information on calculating test loads refer to the Meech Air Technology
brochure, available to download from www.meech.com.