The graph below shows air consumption at varying inlet air pressures. 

Inlet Air Pressure (psi)

Air Consumption (cfm

)

0

5

10

15

20

25

30

35

40

A20035, A24036
A20025, A24026
A20015, A24016
A20010, A24011
A20008, A21008

100

80

60

40

20

4 x High fraction generators are supplied as standard:

Yellow 10cfm (283 l/min) - Cooling capacity of 190W (650 Btu/hr)
Red 15cfm (425 l/min) – Cooling capacity of 293W (1000 Btu/hr)
Blue 25cfm (708 l/min) – Cooling capacity of 499W (1,700 Btu/hr)
Brown 35cfm (991 l/min) – Cooling capacity of 703W (2,400 Btu/hr) 

A single Meech Cabinet Cooler is capable of cooling up to 703 Watts (2,400 Btu/hr). 
Optimising the cooling capacity is still a vitally important factor, choosing the correct 
generator will not only reduce running costs but also extend the life of the compressor. 

To choose the most efficient generator you must calculate the total heat load in Watts 

Btu/hr to which the enclosure is exposed. The total heat load is a combination of 
the heat transfer from outside due to ambient air temperature and the heat which is 
created internally.  

For more information on calculating test loads refer to the Meech Air Technology 
brochure, available to download from www.meech.com.

 

Содержание A70000

Страница 1: ...1 Cabinet Cooler Cabinet Cooler System Operating Manual...

Страница 2: ......

Страница 3: ...ion please refer to our Head Office or visit www meech com Meech Static Eliminators Ltd Contents Section Page 1 Introduction 5 2 Safety and Inspection 6 3 Maintenance 7 4 Compressed Air Supply 9 5 Com...

Страница 4: ......

Страница 5: ...and Thermostat is intrinsically safe and requires virtually no maintenance They have no moving parts making them ideal for harsh environments Cabinet Coolers can be used with or without electrical the...

Страница 6: ...th side shields or goggles and ear protectors Before attempting to disconnect a hose from an air line the air should be cut off and the remaining air bled from the line Keep air hoses off the floor wh...

Страница 7: ...the compressed air supply This could hinder the performance If this happens simply take the unit apart clean the parts with soapy water allow drying time and then reassemble When reassembling ensure y...

Страница 8: ...D50088 Silencer Spring 1 8 A D50040 Silencer Foam 1 9 A D50094 Plastic Insert 1 10 D50153 Star Washer 1 11 A D50036 Bulk Head Washer 1 12 B D50033 Bulkhead Nut 33mm 1 13 A D50075 O Ring 17x3mm 1 17 A...

Страница 9: ...ure to use a filter may cause clogging and freezing of the compressed air line and the components within the Cabinet Cooler When the temperature of the compressed air within the Cabinet Cooler reaches...

Страница 10: ...ere is any doubt that a pipe size may create a pressure drop use the next largest size Remember that an oversize pipe compensates for possible scale build up and provides for future expansion of the o...

Страница 11: ...nd use this number to determine the PIPE SIZE you need Specific Cabinet Cooler Pipe Size To obtain maximum performance from the Cabinet Cooler accurate measures of air pressure and air volume must be...

Страница 12: ...2 1 1 2 2 2 2 2 225 1 1 2 1 1 2 1 1 2 1 1 2 2 2 2 2 250 2 2 2 2 2 2 2 2 275 2 2 2 2 2 2 2 1 2 2 1 2 300 2 2 2 2 2 2 2 1 2 2 1 2 350 2 2 2 2 2 1 2 2 1 2 2 1 2 2 1 2 400 2 2 2 2 2 1 2 2 1 2 2 1 2 2 1 2...

Страница 13: ...t Cooler To fit the Cabinet Cooler follow the steps below A Drill Hole Drill 1 02 26 mm hole in the position you would like to fit the Cabinet Cooler Please be aware that 200mm of the Cabinet Cooler w...

Страница 14: ...Refrig 15cfm 293W 1000 Btu hr generator To change the generator simply unscrew the bulk head fitting and replace the generator with another colour Please remember to re fit the o ring and screw bulk h...

Страница 15: ...the cold air ducting can be directed to particularly hot areas of the enclosure Alternatively you can drill holes in the cold air ducting and allow air to be distributed to several areas If you choos...

Страница 16: ...temperatures and should only be used as a guide The Cabinet Cooler will perform differently when used in other environments Inlet air pressure Product Code Generator Colour Consumption in CFM l min 6...

Страница 17: ...pacity of 703W 2 400 Btu hr A single Meech Cabinet Cooler is capable of cooling up to 703 Watts 2 400 Btu hr Optimising the cooling capacity is still a vitally important factor choosing the correct ge...

Страница 18: ...ly 45 To prevent condensation forming on the cold air pipe close off any vents or fan outlets on the outside wall of the enclosure This reduces the ambient air from circulating within the cabinet pane...

Страница 19: ...stment of Meech Factory settings The thermostat is password protected to stop adjustment of the parameters The following 3 steps explain how to unlock the thermostat for parameter adjustment 1 Power u...

Страница 20: ...e main toggle menu 4 Using the 2 arrow buttons toggle through the parameters until you reach HSEt 5 When you have reached HSEt press the P button once This allows you to adjust the differential of coo...

Страница 21: ...er is IP56 Nema 4 12 The Cabinet Cooler unit is issued in accordance with Directive 94 9 EC ATEX Equipment and protective Systems Intended for use in Potentially Explosive Atmospheres A Declaration of...

Страница 22: ...or size for fitting Cabinet Cooler Air Temperature Problems with air temperature can be caused by 1 Incorrect generator fitted Check and replace generator see section 7 2 Ambient compressed air temper...

Страница 23: ......

Страница 24: ...H 44203 USA Tel 1 330 564 2000 1 800 232 4210 Fax 1 330 564 2005 email info meech com Meech Static Eliminators Shanghai Co Ltd 7G 7F LP Tower 25 Xiangfeng Road 201103 Shanghai China Tel 86 400 820 010...

Отзывы: