22
10. Troubleshooting
Air flow
Problems with compressed air flow can be caused by:
1. Air pressure too low – increase air pressure at the relevant regulator
2. Undersized compressed air lines – replace pipes with correct sizes, see
section 5
3. Blocked compressed air line – remove blockage
4.
Insufficient compressor size – Check compressor size for fitting Cabinet
Cooler
Air Temperature
Problems with air temperature can be caused by:
1.
Incorrect generator fitted – Check and replace generator, see section 7
2. Ambient compressed air temperature too high – Check compressed air
temperature and use cooler if necessary
3. Loose/missing parts – Check all Cabinet Cooler parts are screwed in tightly
and there are no missing parts.
4. Water vapour in the compressed air supply – Check compressed air supply
5. Air pressure too low – increase air pressure at the relevant regulator