background image

13 

00243 

Warranty

 

SEC-Le 

Medem (UK) Limited 

Project House  

19 Dallimore Road 

Manchester  

M23 9NX 

 

Tel: (0) 161 233 0600 

Fax: (0) 161 233 0601 

Web: www.medem.co.uk 

E-mail: [email protected] 

Medem UK Warranty 

Terms & Conditions 

 

1. 

The warranty is a parts warranty and Medem UK Ltd will not cover or accept any labour or 
other expenses that may be incurred in the process of changing faulty product. 

 
2. 

All panels and sender units are covered by a five year warranty. 

 
3. 

Gas detector units and other remote detectors carry a two year warranty. Installation of the 
detectors should not be undertaken until all building and construction work is completed. 

 
4. 

Gas solenoid valves carry the original manufacturers warranty, though as the supplier 
Medem UK will exchange faulty valves for return to the manufacturer. 

 
5. 

Where a Medem UK engineer (or another company appointed by Medem UK) commission 
and installed system then that system will carry a ten year warranty. This applies to the 
main panel and the sender unit. At the time of commissioning a security label with a serial 
number will be attached to the main panel box. photographs and a comprehensive record 
of the installation will be held by Medem UK. 

 
6. 

Where a warranty claim is made then, where appropriate, a written order to attend site 
must be provided to Medem UK A cost for labour and travel to site will be prepared as a 
quote. The cost must be included in the order. 

 

7. 

Where it is found that the installation and/or the quality of workmanship has contributed to 
or wholly caused the failure of the product then we reserve the right to charge the whole or 
a proportion of the cost of the faulty item.

 

Содержание SEC-Le V4

Страница 1: ...safety system is installed and commissioned to the satisfaction of the manufacturer A commissioning certificate must be issued to the end user along with instructions for the operation of the equipme...

Страница 2: ...buttons A and B for engineer functions LED indications Power On green A blind button for displaying gas pressures on the LCD screen Gas Electric red when active to warn of live service Fans running li...

Страница 3: ...age 4 for full details 16 OPTA Over pressure check will isolate gas supply if pressure exceeds 70 mbar 17 Fill prove time for gas pressure proving see page 5 18 Timer adjustment for fan commissioning...

Страница 4: ...Max switching 48 volts 1 amp 15 BMS Relay PCB Press button A To display the gas pressures and view the set pressure proving set times Press button B To display the gas installed gas detectors 1 8 pre...

Страница 5: ...1 Option Headers 18 19 21 20 Fan comm To enable the commissioning of the gas portion of the system before the ventilation interlock is completed you may temporarily disable the interlocking by pressin...

Страница 6: ...e the gas detectors own instructions for more guidance SEC Le Detector Information VE supply Comm s From either the main panel or an extender Detectors are wired in parallel and can be connected to on...

Страница 7: ...een 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilation For additional information or...

Страница 8: ...nnel current Monitor fans Fan speed controls Fan live Supply Fire Alarm Requires a volt free NC contact Where using 3 phase fans interlock on a single phase See page nine Earth Connections not shown 0...

Страница 9: ...sent within the panel IMPORTANT If wired this way a warning notice must be attached to the panel to indicate that there are two separate mains feeds Contactor coil Live feed through switched relay To...

Страница 10: ...s fitted the correct way round Note there is no flow through the pressure sender unit it is purely reading the pressures either side of the valve Correct Pressur e Solenoid Never mount the valve such...

Страница 11: ...Solenoid coil of the valve should never be mounted below the horizontal Pressure sender unit should never be mounted upside down to protect from water ingress Approx 400mm length INLET PORT OUTLET PO...

Страница 12: ...ld be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indicat...

Страница 13: ...er Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will carry...

Страница 14: ...CD display that all the detectors have been recognised by the panel A recognised detector will appear as CO Carbon Monoxide CM combustible CH Carbon Dioxide OX Oxygen depletion and TP Temperature Coun...

Страница 15: ...ssure test If at any point the fans stop running opening the S1 or E1 contact the system will isolate the gas and report fans not running Check that the fans are not only switched on but actually runn...

Отзывы: