VENT-FREE PROPANE/LP GAS HEATER

BLUE-FLAME MBP20LB

Figure 13 - Gas Connection

*  A CSA/AGA design certified equipment shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional CSA/AGA design-certified
equipment shutoff valve from your dealer. See Accessories, page 17.

Install sediment trap in supply line as shown
in Figure 13. Locate sediment trap where it
is within reach for cleaning. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into heater controls. If sediment trap
is not installed or is installed wrong, heater
may not run properly.

IMPORTANT: 

Hold pressure regulator with

wrench when connecting it to gas piping
and/or fittings.

  CAUTION: Use pipe joint seal-

ant that is resistant to liquid pe-
troleum (LP) gas.

Installation must include an equipment
shutoff valve, union, and plugged 1/8" NPT
tap. Locate NPT tap within reach for test
gauge hook up. NPT tap must be upstream
from heater (see Figure 13).

IMPORTANT:

 Install an equipment shutoff

valve in an accessible location. The equip-
ment shutoff valve is for turning on or
shutting off the gas to the appliance.

Typical Inlet Pipe Diameters

20,000 Btu/Hr models    3/8" or greater

30,000 Btu/Hr models    1/2" or greater

 CAUTION: Use only new,

black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of 1/2"
diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur.

INSTALLATION

Continued

3" Minimum

Tee Joint

Reducer Bushing
to 1/8" NPT

1/8" NPT Plug
Tap

Test
Gauge
Connection *

Tee Joint

Pipe Nipple

Cap

Heater
Cabinet

Pressure
Regulator

3/8" NPT
Pipe
Nipple

Ground Joint
Union

Equipment
Shutoff
Valve *

Typical Inlet
Pipe From
External Regulator
(11" W.C. to 14"
W.C. Pressure)

Sediment
Trap

Note: Burner bracket
not shown for clarity

CONNECTING TO GAS
SUPPLY

The installer must supply an external regu-
lator. The external regulator will reduce
incoming gas pressure. You must reduce
incoming gas pressure to between 11 and 14
inches of water. If you do not reduce incom-
ing gas pressure, heater regulator damage
could occur. Install external regulator with
the vent pointing down as shown in Figure
12. Pointing the vent down protects it from
freezing rain or sleet.

 WARNING:  A qualified ser-

vice person must connect heater
to gas supply. Follow all local
codes.

 CAUTION: Never connect heater

directly to the propane/LP supply.
This heater requires an external
regulator (not supplied). Install the
external regulator between the
heater and propane/LP supply.

Figure 12 - External Regulator with Vent
Pointing Down

External
Regulator

Propane/
LP Supply
Tank

Vent
Pointing
Down

 WARNING: This appliance re-

quires a 3/8" NPT (National Pipe
Thread) inlet connection to the
pressure regulator.

Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.

Содержание MBP20LB

Страница 1: ...uali fied installer service agency or the gas supplier WARNING Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manualforcorrectinst...

Страница 2: ...sh outside air ven tilation to run properly This heater has an oxygen depletion sensor ODS pi lot light safety system The ODS shuts down the heater if not enough fresh air is available See Air for Com...

Страница 3: ...o light heater UNPACKING 1 Remove heater from carton 2 Remove all protective packaging ap plied to heater for shipment 3 Check heater for any shipping damage If heater is damaged promptly inform deale...

Страница 4: ...h a rating of one perm 6 x 10 11 kg per pa sec m2 or less with open ings gasketed or sealed and b weather stripping has been added on openable windows and doors and c caulking or sealants are applied...

Страница 5: ...appliances in the space Vent free heater ______________________ Btu Hr Gas water heater ______________________ Btu Hr Gas furnace ______________________ Btu Hr Vented gas heater _____________________...

Страница 6: ...willactivatethepowervent WARNING Rework work sheet adding the space of the adjoining unconfined space The combined spaces must have enough fresh air to supply all appliances in both spaces VENTILATION...

Страница 7: ...ATER This heater is designed to be mounted on a wall Continued WARNING Maintain the mini mumclearancesshowninFigure 4 Ifyoucan providegreaterclear ancesfromfloor ceiling andjoin ing wall You can locat...

Страница 8: ...acket to wall These two holes are 16 inches apart from their centers Attach mounting bracket to wall in one of two ways 1 Attaching to wall stud 2 Attaching to wall anchor Attaching to Wall Stud This...

Страница 9: ...y For thick walls over 1 2 thick or solid walls do not pop open wings 5 Place mounting bracket onto wall Line up last hole on each end of bracket with wall anchors 6 Insert mounting screws through bra...

Страница 10: ...Check your local codes Use pipe of 1 2 diameter or greater to allow proper gas volume to heater If pipe is too small undue loss of pressure will occur INSTALLATION Continued 3 Minimum Tee Joint Reduc...

Страница 11: ...es form ing show a leak 5 Correct all leaks at once 6 Reconnect heater and equipment shutoff valve to gas supply Check re connected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5...

Страница 12: ...ure 7 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob Note If pilot goes out repeat steps 3 through 7 8 Turn control knob counterclockwise to the...

Страница 13: ...re cleaning CAUTION You must keep control areas burner and circu lating air passageways of heater clean Inspect these areas of heater before each use Have heaterinspectedyearlybyaquali fied service pe...

Страница 14: ...ctionlooseatcon trol valve 5 Pilotflamenottouchingthermocouple which allows thermocouple to cool causing pilot flame to go out This problemcouldbecausedbyoneorboth of the following A Low gas pressure...

Страница 15: ...e 1 When heated vapors from furniture polish was carpet cleaners etc turn into white powder residue REMEDY 1 Contactlocalpropane LPgascompany 2 Clean burner see Cleaning and Main tenance page 13 or re...

Страница 16: ...artially clogged 1 Gas leak See Warning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement at top of page 1 Not enoug...

Страница 17: ...ane LP Only Ignition Piezo Pressure Regulator Setting 8 W C Inlet Gas Pressure inches of water Maximum 14 Minimum 11 Dimensions Inches H x W x D Heater 23 5 x 18 5 x 8 0 Carton 26 x 20 5 x 9 63 Weight...

Страница 18: ...18 105736 VENT FREE PROPANE LP GAS HEATER BLUE FLAME MBP20LB ODS PILOT 12 1 12 2 1 2 3 4 5 6 8 8 9 10 10 11 12 13 14 17 19 25 21 23 24 7 22 27 26 20 16 18 15 ILLUSTRATED PARTS BREAKDOWN MBP20LB...

Страница 19: ...able 1 11 098249 01 Nut M5 2 12 103594 04 ODS Pilot Assembly 1 12 1 098514 01 Thermocouple 1 12 2 106842 01 Ignitor Electrode 1 13 103446 01 Burner 1 14 099387 05 3 16 Pilot Tubing 1 15 103845 05 Inje...

Страница 20: ...nished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack...

Отзывы: