![Mect MPNE1001 Series Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/mect/mpne1001-series/mpne1001-series_user-manual_1759153015.webp)
Inputs/outputs modules: MPNE
Mect Srl
14
ME7087_13 04/21
3.3.3 Digital outputs power supply
The digital outputs of the MPNE1001 are powered separately (
24Vpot
)
from the
circuit electronics so that they can be cut off from the emergency chain without
disconnecting the low power part. The digital outputs can provide up to 2A maximum
current at 24V (for CODE 02) and up to 4A maximum current at 24V (for CODE 06).
The maximum allowable current per single output is 200mA (for CODE 02) and
500mA (for CODE 06). The current supplied by the outputs is supplied by the
power supply of the terminal itself: it is the
responsibility of the installer to correctly
size the power supply to guarantee the necessary current
.
In the figure below the power supply of digital outputs , of the base and of the
expansions are shown:
Fig.: Digital output connection
3.3.4 Fuses
The system has no fuses internally; however, for the protection of the input of the
MPNE1001 power supply, it is recommended to insert a 1A fuse, while for the
power it is necessary to put a 4A.