19

5. UART Communication Function(U version only)

2

The

various fault signals, power supply working status, single

LAD

battery voltage, main voltage, output voltage and output current to the

controller through the UART, and changes the power supply working

status according to the controller instructions. For details. please refer

to the 5.4.

5.2.1Forced Start & Remote UPS Control(U version only)

BAT. CHARGER

+V

BAT+

-V

BAT-

UPS

FUNCTION

Remote UPS Control

Force Start
UPS Mode

RELAY

S.W

~

Both "forced start" and "

"can force the power

remote UPS control

supply

(

)

. Both can be used

to operate in battery back UPS mode

separately or simultaneously. When

at the same time,

implemented

the priority of "Forced Start" is higher than "

UPS Control"

remote

.

5.2.1.1 Force start UPS mode:

According to fire safety regulation, UPS power supply must equip with
force start UPS function. In case of emergency, maintenance or testing,
Operators can active the UPS mode  by shorting PIN1 and PIN2 of LAD-
360/600xU to ensure

supply to the loads. When

battery power

operating under UPS mode, the BAT. UVP alarm is still active, but the
BAT. UVP protection

invalid, therefore, the battery will be fully dis

is

charged until system shuts down.

16

15

2

1

PIN1 2

&

5

Short

Open

Status

Forced start

Normal

20

Description of orce

f

start UPS mode

(1) In the case of no AC input power supply, when the backup power

switch is OFF, PIN 1 and 2 need to be short-circuited all the time, to

force the UPS function to start, and keep the battery powered; when

PIN 1, 2 is open, the battery power supply is disconnected.
(2) In the case of no AC input power supply, when the backup power

switch is ON, PIN 1 and 2 need to be short-circuited , to force the UPS

function to start, powered by battery. When PIN1, 2 are shorted and

disconnected after a few seconds, the battery power is still maintained.

5.2.1. Remote UPS mode

2

PIN3 4

&

Short

Open

Status

Romote UPS control

Normal

Remote UPS mode:

According to fire safety regulation, UPS power supply must equip with

remote UPS function. So the power supply unit can be linked to the fire

alarm system, user's system will be able to detect the status of PIN3 and

PIN4 LAD-360xU with UART communication. When PIN 3 and PIN 4 is

shorted, the power supply will enter remote UPS mode. Therefore, the

UPS mode will be active and the status signal will also send to the fire

alarm system for indication. Personal or the system can use the signal as

trigger threshold for other alarm systems to decide when and how to

enter the emergency sequence. Under this condition, BAT. UVP alarm

and protection are still active.

Pin 5 & 6

Short

Open

Battery Type

Li-ion batteries

Lead-acid (Pb) batteries

5.2. Charging curves of different batteries

2

4

3

16

15

16

15

6

5

5

Two different charging curves can be determined through the short

circuit and open circuit of pin 5&6.

Содержание LAD Series

Страница 1: ...LAD Series Economical Security Fire Alarm PSU with Battery Charger UPS User Manual Back up Charger Power Supply LAD 120 240 360 600 Series AC Grid Load Battery Pack UART RTU DATA PROTOCOL AC DC...

Страница 2: ...dc and 55 2Vdc With high efficiency up to 86 5 and built in AC battery switch for easy maintenance In addition LAD 600 series not only provide TTL signals for AC OK battery disconnect battery reverse...

Страница 3: ...case 3 3 Wiring use 3 4 Installation steps 3 5 Instructions for battery serial and parallel use 4 User Interface Panel 4 1 Panel description 4 2 Pin assignment 5 Function Description 5 1 DC UPS funct...

Страница 4: ...en power supply and battery should be kept as short as possible to prevent excessive voltage drop suggested cable length 50cm 1000cm Too much voltage drop will lead to longer charging period d The pow...

Страница 5: ...elcordia SR 332 Bellcore 209 4K hrs min MIL HDBK 217F 25 1A Battery Charger 1A Battery Charger 1A Battery Charger 4 2 MODEL DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER OUTPUT VOLTAGE ADJ RANGE...

Страница 6: ...ery for protection 1 5A Battery Charger 1 5A Battery Charger 1 5A Battery Charger LAD 360xU Series UART Communication Function Model U Version 6 2 DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER VO...

Страница 7: ...62368 1 AS NZS62368 1 EAC TP TC 004 approved Design refer to GB 17945 2010 GB4717 LAD 600xU Series UART Communication Function Model U Version 8 2 DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER VO...

Страница 8: ...264 90 100 80 70 60 50 40 180 264VAC 90 132VAC 90 100 115 110 160 140 200 180 240 220 264 90 100 80 70 120 LAD 120 Series LOAD LAD 0 Series 24 360 LOAD INPUT VOLTAGE VAC 60Hz 2 10 LAD 600 Series TB1 7...

Страница 9: ...ws and internal components of power supplies Please refer to case drawing on specifications to receive the maximum length of mounting screw Mounting orientations other than standard orientation or ope...

Страница 10: ...nected Disconnected S W AC ON OFF S W 3 4 2 Make sure all cables are well connected then feeds the AC to power the supply and turn the main power and backup power switches to the ON position 5 11 gf c...

Страница 11: ...rminal contacts It is used control and status monitoring etc For details to please refer to Chapter 4 2 1 It is used control and status monitoring etc For details to please refer to Chapter 4 2 2 4 2...

Страница 12: ...l AC OK battery unconnected reverse connection battery undervoltage full linkage control battery selection buzzer alarm battery detection forced start of battery power supply etc 5 1 DC UPS function L...

Страница 13: ...no AC input power supply when the backup power switch is OFF PIN 1 and 2 need to be short circuited all the time to force the UPS function to start and keep the battery powered when PIN 1 2 is open t...

Страница 14: ...y is reversely connected and the output is overloaded the buzzer will alarm Pin 7 8 Short Open Fire alarm system Evacuation system Open Short BU CU DU Evacuation system Fire alarm system Status 5 2 Ba...

Страница 15: ...oltage 50V max Low High or open Description R V 4 5 24 5 3 Battery disconnected reverse TTL signal battery detection status 2 When the battery is not connected or reversely connected the state is high...

Страница 16: ...LAD 360 600U can be set and read through communication and multiple parallel connections cannot be used in the configuration 5 4 1 1 UART specification Protocol adopts UART interface This device adop...

Страница 17: ...ition of data types The data transmission patterns of this agreement are defined as follows 5 4 1 5 Scratchpad Address Data Description Controller PC to LAD datasheet Data type Narrate Bytes Range U1...

Страница 18: ...a total of 4 bytes LAD_STATUS_H at the high level and LAD_STATUS_L at the low level 5 30 LAD_STATUS_H Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 High byte Reserved Reserved Reserved Reserved Reserved Re...

Страница 19: ...es of Communications The following provides an example of reading and writing to t UART he communication protocol Note 5 4 2 1 5 4 2 6 provides an example for reading instructions 5 4 2 7 5 4 2 9 is a...

Страница 20: ...1 battery is normal 0 Battery balanced state Standby OVP protection status Linkage control status display System power supply status Standby UTP protection status Main discharge OLP status Standby sta...

Страница 21: ...ion is 0x9F CRC 8 5 4 1 3 the 5 Response R W byte Data Length Data address bytes Data bytes CRC 8 0x55 0x05 0x00 30 0x02 91 0xBD 36 5 4 2 4 Battery voltage Brief description Battery voltage read instr...

Страница 22: ...refer to the description of in CRC 8 5 4 1 3 The error detection code for the response is calculated by the CRC 8 LAD LAD s own MCU 5 4 2 6 Battery undervoltage protection points Brief description Bat...

Страница 23: ...his command is 0 01V transmitted that is the decimal number of the data to be is 43 2 0 01 4320 and the corresponding hexadecimal number is 0x0E E8 0x0D CRC 8 Transmit data error detection code refer...

Страница 24: ...t the power supply turns off the output Recycle AC power to recover the output Once the LAD 600 triggers the protection the output recovers after recycling AC power and 3 minutes of cold standby 6 42...

Страница 25: ...al Please refer to the latest version of our manual on our website www meanwell com https MEAN WELL WEB User s Manual This product provides three years warranty under normal usage Do not replace parts...

Страница 26: ......

Отзывы: