background image

                             

Installation Manual

 

 

 

B Recommend t

orque for iron

 

Size of screw (

Imperial units

Recommend torque (kgf-cm) 

3-56 
4-40 
4-48 
5-40 
5-44 
6-32 
6-40 
8-32 
8-36 

5.0±20% 
6.9±20% 
7.0±20% 
9.4±20% 
9.9±20% 

12.0±20% 
13.4±20% 
21.8±20% 

   23.0±20% 

 

Size of screw (

Metric Units

Recommend torque (kgf-cm) 

M2.5 

M3 

M3.5 

M4 
M5 
M6 
M7 
M8 

4.6±20% 
8.8±20% 

13.7±20% 
20.4±20% 
41.1±10% 
69.1±10% 

117.5±10% 

   169.4±10% 

If above mentioned is not enough due to special application

Nylok Blue Patch screw is recommend, and extra 

torque can be added if needed.

 

7

Recommended wires are shown as below. 

AWG 

18 16 14 12 10  8 

Rated Current of 
Equipment (Amp) 

6A 

6-10A  10-16A 16-25A 25-32A 32-40A 

Cross-section of 
Lead(mm

2

 ) 

0.75 1.00  1.5  2.5  4 

Note: Current each wire carries should be de-rated to 80% of the current 

suggested above when using 5 or more wires connected to the unit.

 

Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are 
securely fixed to prevent poor contact.

 

8

Wiring: The wire color will vary by country, please refer to the table below. 

 

North America 

European Harmonized 

Live and ACL 

Black 

Brown 

Neutral and ACN 

white 

Blue 

PE and FG (Class I only) 

Green 

Green/yellow 

a

Connect the FG wire (green or green/yellow) of the power supply to PE (green or green/yellow), this step 

can be skipped when the unit is marked class II, ungrounded. 

b

Connect the ACL wire (black or brown) of the power supply to Live (black or brown). 

c

Connect the ACN wire (white or blue) of the power supply to Neutral (white or blue). 

d

Make sure all wires are secured to prevent poor contact. 

 
 
 
 

Содержание HEP-1000

Страница 1: ...erature may increase the internal component temperature and will require a de rating in output current Please refer to the specification sheets to receive the optimum mounting position and information...

Страница 2: ...8kgf cm UHP 200A M3 5 13kgf cm M3 5 8kgf cm CSP 3000 M4 10 12kgf cm M6 13kgf cm UHP 500 R 750 1000 M3 5kgf cm M4 10 12kgf cm HEP 600 1000 M4 10 12kgf cm M4 10 12kgf cm 6 Torque can be various due to...

Страница 3: ...Note Current each wire carries should be de rated to 80 of the current suggested above when using 5 or more wires connected to the unit Make sure that all strands of each stranded wire enter the termi...

Страница 4: ...to earth ground 6 All MW s PSUs are designed in accordance with EMC regulations and the related test reports are available by request Since they are belong to component power supplies and will be inst...

Страница 5: ...oducts Appendix B adopting table look up to verify the Environment Friendly Use Period Names and Contents of Hazardous Substances Lists Part Name Hazardous Substances Lead Pb Mercury Hg Cadmium Cd Hex...

Страница 6: ...to China s Standardization Administration Releases VOC Standards Standard No Name of the Standard GB 30981 2020 Limit of harmful substances of industrial protective coatings GB 33372 2020 Limits for v...

Страница 7: ...eby confirms that MEAN WELL product series comply with Use and Risk Management for Five PBT Chemicals under TSCA section 6 h CAS No Substance Name 1163 19 5 Decabromodiphenyl ether DecaBDE 68937 41 7...