For MDCA3-12HRDN1, MDTB1-12HWDN1, MDFA-12HRFN1:
For 12k models(Excluding MDCA3-12HRDN1, MDTB1-12HWDN1, MDFA-12HRFN1)
Electrical Control Function
190
Electrical Control System
---0
℃
≤
T2<4
℃
, the compressor frequency will be limited and decreased to the lower level every 1 minute till
off.
---4
℃
≤
T2
≤
7
℃
, the compressor will keep the current frequency.
---T2>7
℃
, the compressor frequency will not be limited.
For other models:
When T2<2
℃
and lasts for 3 minutes, the indoor has no capacity demand and resume
till T2
≥
7
℃
.
1.3.2.4 Condenser high temperature T3 protection
:
---55
℃
<T3<60
℃
, the compressor frequency will decrease to the lower level every 3 minutes till F1 and then
runs at F1.If T3<54
℃
, the compressor will keep running at the current frequency.
---T3<52
℃
, the compressor will not limit the frequency and resume to the former frequency.
---T3>60
℃
for 5 seconds, the compressor will stop until T3<52
℃
.
--- 61<T3< 66, the compressor frequency will decrease to the lower level until to F1 and then runs at F1 per
minute. If T3<61, the compressor will keep running at the current frequency.
---T3< 58, the compressor will not limit the frequency and resume to the former frequency.
---T3> 66 for 5 seconds, the compressor will stop until T3< TP3-3.
For other models:
When T3
≥
65
℃
for 3 seconds, the compressor will shut off. When T3
<
52,the
compressor will restart.
1.3.3 Heating Mode
1.3.3.1 Outdoor fan running rules:
For 12k models:
17
15
Low
High
MOZU-18HFN1-QRC8:
Содержание MDCA3-12HRDN1
Страница 1: ...DC INVERTER SERIES Service Manual 2014 LIS B 1411...
Страница 5: ...Features 11...
Страница 7: ...S 14 3 ervice Space 4 Service 3 e Space...
Страница 8: ...MDCA3 12HRDN1 MDCA3 18HRDN1 Wiring Diagrams 16 4 Wiring 4 Diagram ms...
Страница 12: ...MDCA3 12HRDN1 MDCA3 18HRDN1 Field Wiring 21 1 Field 0 Wiring...
Страница 18: ...Dimensions 32 Super Slim Cassette Type 2 Dimensions Model A H 18 30 205 235 36 48 245 275 60 287 317...
Страница 19: ...Service Space Super Slim Cassette Type 33 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 26: ...Field Wiring 40 Super Slim Cassette Type 10 Field Wiring...
Страница 33: ...MDTB1 12HWDN1 MDTB1 12HWDN1 B Duct Type Duct Type 47 4 Wiring Diagrams...
Страница 34: ...MDTB 18HWDN1 MDTB 24HWDN1 MDTB 36HWDN1 MDTB 48HWDN1 MDTB 60HWDN1 Duct Type 48 Duct Type...
Страница 41: ...Duct Type 56 Duct Type For model 18 60 10 Field Wiring...
Страница 44: ...MDOU 60HDN1 MDOU 48HDN1 Dimensions Outdoor Units 125 Model Unit mm A B C D E F H 940 600 376 400 340 360 1245...
Страница 50: ...MDOU 12HDN1 Wiring Diagrams Outdoor Units 131 4 Wiring Diagrams...
Страница 51: ...MDOZU 12HDN1 MDOU 18HDN1 Wiring Diagrams 132 Outdoor Units...
Страница 52: ...MDOU 18HFN1 Wiring Diagrams Outdoor Units 133...
Страница 53: ...MDOU 24HDN1 220075301400 MDOU 24HDN1 220075302030 Wiring Diagrams 134 Outdoor Units...
Страница 54: ...MDOU 36HDN1 Wiring Diagrams Outdoor Units 137...
Страница 55: ...MDOU 48HDN1 MDOU 60HDN1 MDOU 48HDN1 MDOU 60HDN1 New Body Wiring Diagrams 138 Outdoor Units...
Страница 91: ...Refrigerant pipe installation 174 Installation...
Страница 129: ...Troubleshooting 220 Electrical Control System 2 4 4 5 E3 malfunction...
Страница 131: ...Troubleshooting 222 Electrical Control System 2 4 4 7 E5 malfunction...
Страница 132: ...Troubleshooting Electrical Control System 223 2 4 4 8 E6 malfunction Only for 36K 48K with 1 phase...
Страница 133: ...Troubleshooting 224 Electrical Control System 2 4 4 9 P0 malfunction...
Страница 134: ...Troubleshooting Electrical Control System 225 2 4 4 10 P1 malfunction Only for 30K 60K...
Страница 140: ...Troubleshooting Electrical Control System 231 2 4 4 16 P7 malfunction...