MDCA3-12HRDN1, MDTB1-12HWDN1 and MDFA-12HRFN1, it is 7s) later..
For MDOZU-12HDN1-Q:
For MDOU-12HDN1
Electrical Control Function
Electrical Control System
185
1. Electrical Control Function
1.1 Definition
T1: Indoor room temperature
T2: Coil temperature of indoor heat exchanger middle.
T2B: Coil temperature of indoor heat exchanger outlet.
T3: Coil temperature of condenser
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
Td: Target temperature
1.2 Main Protection
1.2.1 Time delay at restart for compressor.
1.2.2 Temperature protection of compressor top
The unit will stop working when the compressor top temp. protector cut off, and will restart after the
compressor top temp. protector restart.
1.2.3 Temperature protection of compressor discharge
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules:
:
---Compressor discharge temp. T5>115
℃
for 5s, compressor stops.
---108<T5<115
℃
, decrease the frequency to the lower level every 3 minutes till F1.
---90<T5<105
℃
, keep running at the current frequency.
----T5<90
℃
, no limit for frequency.
---Compressor discharge temp. T5>115
℃
for 5s, compressor stops and restarts up till T5<90
℃
---110<T5<115
℃
, decrease the frequency to the lower level every 2 minutes.
---105<T5<110
℃
, keep running at the current frequency.
----T5<105
℃
, no limit for frequency.
For other models:
----If 102
℃
<T5<115
℃
, decrease the frequency to the lower level every 2 minutes till to F1.
---If T5>115
℃
for 10 seconds, the compressor will stop and restart till T5<90
℃
.
1.2.4 Sensor protection at open circuit and breaking disconnection.
1.2.5 Indoor fan delayed open function
----When system starts up, the louver will be active immediately and the indoor fan will open 10s (for
----If the system runs in heating mode, the anti-cold wind function has priority.
1.2.6 Fan speed is out of control (Only for Console)
When Indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will display
the failure
Содержание MDCA3-12HRDN1
Страница 1: ...DC INVERTER SERIES Service Manual 2014 LIS B 1411...
Страница 5: ...Features 11...
Страница 7: ...S 14 3 ervice Space 4 Service 3 e Space...
Страница 8: ...MDCA3 12HRDN1 MDCA3 18HRDN1 Wiring Diagrams 16 4 Wiring 4 Diagram ms...
Страница 12: ...MDCA3 12HRDN1 MDCA3 18HRDN1 Field Wiring 21 1 Field 0 Wiring...
Страница 18: ...Dimensions 32 Super Slim Cassette Type 2 Dimensions Model A H 18 30 205 235 36 48 245 275 60 287 317...
Страница 19: ...Service Space Super Slim Cassette Type 33 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 26: ...Field Wiring 40 Super Slim Cassette Type 10 Field Wiring...
Страница 33: ...MDTB1 12HWDN1 MDTB1 12HWDN1 B Duct Type Duct Type 47 4 Wiring Diagrams...
Страница 34: ...MDTB 18HWDN1 MDTB 24HWDN1 MDTB 36HWDN1 MDTB 48HWDN1 MDTB 60HWDN1 Duct Type 48 Duct Type...
Страница 41: ...Duct Type 56 Duct Type For model 18 60 10 Field Wiring...
Страница 44: ...MDOU 60HDN1 MDOU 48HDN1 Dimensions Outdoor Units 125 Model Unit mm A B C D E F H 940 600 376 400 340 360 1245...
Страница 50: ...MDOU 12HDN1 Wiring Diagrams Outdoor Units 131 4 Wiring Diagrams...
Страница 51: ...MDOZU 12HDN1 MDOU 18HDN1 Wiring Diagrams 132 Outdoor Units...
Страница 52: ...MDOU 18HFN1 Wiring Diagrams Outdoor Units 133...
Страница 53: ...MDOU 24HDN1 220075301400 MDOU 24HDN1 220075302030 Wiring Diagrams 134 Outdoor Units...
Страница 54: ...MDOU 36HDN1 Wiring Diagrams Outdoor Units 137...
Страница 55: ...MDOU 48HDN1 MDOU 60HDN1 MDOU 48HDN1 MDOU 60HDN1 New Body Wiring Diagrams 138 Outdoor Units...
Страница 91: ...Refrigerant pipe installation 174 Installation...
Страница 129: ...Troubleshooting 220 Electrical Control System 2 4 4 5 E3 malfunction...
Страница 131: ...Troubleshooting 222 Electrical Control System 2 4 4 7 E5 malfunction...
Страница 132: ...Troubleshooting Electrical Control System 223 2 4 4 8 E6 malfunction Only for 36K 48K with 1 phase...
Страница 133: ...Troubleshooting 224 Electrical Control System 2 4 4 9 P0 malfunction...
Страница 134: ...Troubleshooting Electrical Control System 225 2 4 4 10 P1 malfunction Only for 30K 60K...
Страница 140: ...Troubleshooting Electrical Control System 231 2 4 4 16 P7 malfunction...