For 12k models(Excluding MDCA3-12HRDN1, MDTB1-12HWDN1,MDFA-12HRFN1):
Electrical Control Function
198
Electrical Control System
For other models:
∆
T=T1-Ts Running
mode
∆
T
≥
2
℃
Cooling
-1
≤∆
T<2
℃
Fan-only
∆
T<-1
℃
Heating
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for 15
minutes and then choose mode according to T1-Ts.
If the setting temperature is modified, the machine will choose running function again.
1.3.5 Drying mode
1.3.5.1 Indoor fan speed is fixed in low(for console, it is fixed in breeze) and can’t be changed. The louver
angle is the same as in cooling mode.
1.3.5.2 Low indoor room temperature protection
In drying mode, if room temperature is lower than 10
℃
, the compressor will stop and not resume until room
temperature exceeds 12
℃
.
1.3.5.3 Evaporator anti-freezing protection, condenser high temperature protection and outdoor unit
frequency limit are active and the same as that in cooling mode.
For other models:
Drying mode works the same as cooling mode in low speed.
All protections are active and the same as that in cooling mode.
1.3.6 Timer function
1.3.6.1 Timing range is 24 hours.
1.3.6.2 Timer on. The machine will turn on automatically when reaching the setting time.
1.3.6.3 Timer off. The machine will turn off automatically when reaching the setting time.
1.3.6.4 Timer on/off. The machine will turn on automatically when reaching the setting “on” time, and then
turn off automatically when reaching the setting “off” time.
1.3.6.5 Timer off/on. The machine will turn off automatically when reaching the setting “off” time, and then
turn on automatically when reaching the setting “on” time.
1.3.6.6
Only for MCA2-12HRDN1-Q:
The timer function will change the AC current operation mode. Suppose users set the “timer off” function and
AC is off now, the AC will turn on firstly and then turn off when reaching the setting time.
For other models:
The timer function will not change the AC current operation mode. Suppose AC is off now, it will not start up
firstly after setting the “timer off” function. And when reaching the setting time, the timer LED will be off and
the AC running mode has not been changed.
1.3.6.7 The setting time is relative time.
Содержание MDCA3-12HRDN1
Страница 1: ...DC INVERTER SERIES Service Manual 2014 LIS B 1411...
Страница 5: ...Features 11...
Страница 7: ...S 14 3 ervice Space 4 Service 3 e Space...
Страница 8: ...MDCA3 12HRDN1 MDCA3 18HRDN1 Wiring Diagrams 16 4 Wiring 4 Diagram ms...
Страница 12: ...MDCA3 12HRDN1 MDCA3 18HRDN1 Field Wiring 21 1 Field 0 Wiring...
Страница 18: ...Dimensions 32 Super Slim Cassette Type 2 Dimensions Model A H 18 30 205 235 36 48 245 275 60 287 317...
Страница 19: ...Service Space Super Slim Cassette Type 33 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 26: ...Field Wiring 40 Super Slim Cassette Type 10 Field Wiring...
Страница 33: ...MDTB1 12HWDN1 MDTB1 12HWDN1 B Duct Type Duct Type 47 4 Wiring Diagrams...
Страница 34: ...MDTB 18HWDN1 MDTB 24HWDN1 MDTB 36HWDN1 MDTB 48HWDN1 MDTB 60HWDN1 Duct Type 48 Duct Type...
Страница 41: ...Duct Type 56 Duct Type For model 18 60 10 Field Wiring...
Страница 44: ...MDOU 60HDN1 MDOU 48HDN1 Dimensions Outdoor Units 125 Model Unit mm A B C D E F H 940 600 376 400 340 360 1245...
Страница 50: ...MDOU 12HDN1 Wiring Diagrams Outdoor Units 131 4 Wiring Diagrams...
Страница 51: ...MDOZU 12HDN1 MDOU 18HDN1 Wiring Diagrams 132 Outdoor Units...
Страница 52: ...MDOU 18HFN1 Wiring Diagrams Outdoor Units 133...
Страница 53: ...MDOU 24HDN1 220075301400 MDOU 24HDN1 220075302030 Wiring Diagrams 134 Outdoor Units...
Страница 54: ...MDOU 36HDN1 Wiring Diagrams Outdoor Units 137...
Страница 55: ...MDOU 48HDN1 MDOU 60HDN1 MDOU 48HDN1 MDOU 60HDN1 New Body Wiring Diagrams 138 Outdoor Units...
Страница 91: ...Refrigerant pipe installation 174 Installation...
Страница 129: ...Troubleshooting 220 Electrical Control System 2 4 4 5 E3 malfunction...
Страница 131: ...Troubleshooting 222 Electrical Control System 2 4 4 7 E5 malfunction...
Страница 132: ...Troubleshooting Electrical Control System 223 2 4 4 8 E6 malfunction Only for 36K 48K with 1 phase...
Страница 133: ...Troubleshooting 224 Electrical Control System 2 4 4 9 P0 malfunction...
Страница 134: ...Troubleshooting Electrical Control System 225 2 4 4 10 P1 malfunction Only for 30K 60K...
Страница 140: ...Troubleshooting Electrical Control System 231 2 4 4 16 P7 malfunction...