Hydraulic Module 50Hz                                                                                                                                            MCAC-ATSM-2014-11

 

18 

Attention! 

Frequently start-up would impact the lifespan of unit. Strongly recommend: When the units started up, don

’t frequently start or 

stop the units. Don

’t dump directly if it's out of necessary. 

14.7   Commissioning 

(1). Check whether the unit is well earthed.   

(2). Check whether the air-conditioning and earth source recycle system are filled with water, whether the pipeline is emptied, the 

replenishing water valve is on or not.   

(3). Check whether all valves of pipeline are on correct status. 

(4). Check whether the voltage of power supply is correct. 

(5). Check whether the main pressure gauge is normal. 

(6). Check whether the terminal equipment operate normally. 

(7). Start up the water pump and confirm its running direction firstly. Check whether the water flow switch is normal. Check the 

replenishing water source and turn on the exhausting valve to empty air in pipeline. 

(8).  After  finished  checking  water  pump  and  water  system,  start  to  the  running  testing.  Before  starting  the  unit,  please  check 

whether the power supply is normal. After that, please record the temperature and pressure from all points pipeline

14.8   Safety in use 

(1). Should close down immediately, dump, checkup and repair, if find following conditions: 

A. Electrical machine current exceed 10% or above of rated current for a long time. 

B. Machine set automatic stop and cannot automatic recovery operation. 

C. Machine set start difficulty or cannot start. 

(2). When machine set leave factory, paste different label at relevant position, please follow close to the line of rated regulations. 

(3). Strictly prohibit operate each switch frequently. 

(4). Main circuit power supply not be allowed break at the period of machine set normal use. 

14.9 Maintenance

 

(1).  All the  devices  have  passed strict  test in the  company and they are  in  the  best  working state, so  users  need  not  adjust it 

again. 

(2). After 24hours' test run, you must clean the filter at water inlet end of water pump. 

(3). Please do not operate each switch too frequently. 

(4). Please cut off the power supply of device if you will not use it for a long time. 

(5). When the device is running in winner, please pay special attention to the information below: If the temperature is below or 

equal to 0

, you shall check the thermal insulation effect of water pipes periodically and please do not cut off the power supply of 

device. If you will not use the device for a long time in winner, please empty all of the water or the pipes may burst. 

Содержание HM/II-130S

Страница 1: ...Application range 4 7 Specifications 4 8 Dimensions 5 9 Wiring Diagram 6 10 Exploded views 7 11 Selection 11 12 Key components configuration parameter 11 13 Trouble shooting 12 14 Installation 13 Manu...

Страница 2: ...e control cabinet can achieve linkage control with any formal air condition mainframe through active or passive junction 2 4 Easy installation and maintenance The unit can be installed indoor or outdo...

Страница 3: ...motor safety class is IP24 insulation class is F 3 External appearance 4 Nomenclature HM V II 65 S Power Supply S 380V 50Hz 3Ph D 220V 60Hz 3Ph Rated cooling capacity kW Water pump quantity I one pum...

Страница 4: ...25 Power supply frequency 2 Three phase current imbalance 5 7 Specifications Content Unit HM II 65S HM II 130S Recommended cooling capacity corresponding to the range selection kW 65 130 Water flow m...

Страница 5: ...MCAC ATSM 2014 11 Hydraulic Module 50Hz 5 8 Dimensions Unit mm HM II 65S HM II 130S...

Страница 6: ...Hydraulic Module 50Hz MCAC ATSM 2014 11 6 9 Wiring Diagram HM II 65S HM II 130S...

Страница 7: ...MCAC ATSM 2014 11 Hydraulic Module 50Hz 7 10 Exploded views HM II 65S...

Страница 8: ...0 1 Welded parts of electric control box 1 29 Water baffle II 1 10 2 Outdoor main control board ass y 1 30 Connection pipe of expansion tank 1 10 3 AC contactor 2 31 Right side board 1 10 4 Transforme...

Страница 9: ...MCAC ATSM 2014 11 Hydraulic Module 50Hz 9 HM II 130S...

Страница 10: ...ectric control box 1 29 Water baffle II 1 10 2 Outdoor main control board ass y 1 30 Connection pipe of expansion tank 1 10 3 AC contactor 2 31 Right side board 1 10 4 Transformer 1 32 Expansion tank...

Страница 11: ...oor unit combined quantity and type 3 Each water system design of pump head please refer to flow head curve 12 Key components configuration parameter No Name Connection dimension Parameter 1 Fixed pre...

Страница 12: ...t by linkage and manual the coil voltage is normal Cut off power supply press on contactor by hand the contactor is broken if don t press down Replace contactor Relay failure Normally start pump by ma...

Страница 13: ...e orifice and water pipe joint respectively in order to avoid the module set water pipe be damaged by large torque result in water pipe cracking and leakage 3 In order to improve the efficiency of wat...

Страница 14: ...it it must change the by pass valve of pressure difference to the position displays in the figure 5 If the module operates at lower temperature environment or don t use it for a long time please add e...

Страница 15: ...liding 4 Pipe installation Provide pipe installation schematic drawing and the name of connection orifice should be shown at the position of waterpower module orifice convenient to connect system pipe...

Страница 16: ...dismantled Lifting should be done as the packing direction and added two guard plates in case of damage or deformation 4 When suspension module to moving please use the flexible sling in order to avoi...

Страница 17: ...it nameplates is the quantitative value under standard running conditions The selection of miniature circuit breaker AC contactor wiring capacity and so on has been considered while the module is oper...

Страница 18: ...s pipeline 14 8 Safety in use 1 Should close down immediately dump checkup and repair if find following conditions A Electrical machine current exceed 10 or above of rated current for a long time B Ma...

Отзывы: