Technical Manual Glass Push Button II Smart BE-GT2xx.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 •
Fax: +49-2263-4588
• [email protected] • www.mdt.de
68
Since shutter actuators always use a 1 signal for the down movement and a 0 signal for the up
movement, the button also emits this. It is also possible to change the action for long and short
keystrokes. It is thus possible to select whether to move via a long or a short keystroke. The
stop/step object then adopts the other operating concept.
The following table shows the available communication objects:
Number Name
Length Usage
0
Push button 1
–
blind up/down 1 Bit
Up/Down command for the shutter actuator
1
Push button 1
–
Slats/Stop
1 Bit
Slats open/close; Stop-command
2
Push button 1
–
value for
change of direction
1 Bit
only for single-button function
Receiving the status with current information
about the direction of the shutter actuator
2
Push button 1/2
–
State of slat
for display
1 Byte
only for two-button function
Receiving the status of the current slat
position
3
Push button 1
–
State of blind
for display
1 Byte
Receiving the status of the current
blind/shutter position
Table 49: Communication objects - blind
Presentation:
;
Single-button function
;
Two-button function
The blind function can be displayed with 3 freely selectable symbols and freely selectable color. The
button evaluates the information of the "Object 3 - State of blind for display". In addition, the current
status can be displayed as text under the symbol:
Figure 33: Presentation - Blind function