Technical Manual Glass Push Button II Smart BE-GT2xx.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 •
Fax: +49-2263-4588
• [email protected] • www.mdt.de
63
If the function has been parameterized as "Send values", the following settings are possible.
The presentation of the function "send values" depends on the selected datapoint type. Depending
on the selected datapoint type, 1-4 different symbols and their color can be selected.
The following table provides an overview of the settings for the various datapoint types:
Dataponit type
adjustable symbols
Comment
2 Bit Switch control, DPT 2.001
4 symbols can be set: 1 symbol
for each possible state
1 Byte Percent, DPT 5.001
3 symbols can be set for the
ranges 0, 1 to 229 and larger
229. Therefore, the button
evaluates the information of the
"Status for display" object
Special presentation possible!
Additionally it is possible to
display the status value below
the symbol.
1 Byte Decimal fator, DPT 5.005 Three icons can be set for the
ranges 0%, 1% to 90% and
greater than 90%. Therefore the
button evaluates the
information of the "Status for
display" object
Special presentation possible!
Additionally it is possible to
display the status value below
the symbol.
1 Byte Scene Number, DPT
17.001
1 fixed symbol can be set
2 Byte Temperature, DPT 9.001
1 fixed symbol can be set
Special presentation possible!
2 Byte Brightness, DPT 9.004
1 fixed symbol can be set
3 Byte RGB value, DPT 232.600
1 fixed symbol can be set
Table 42: Presentation - send values
Special presentation:
For certain data point types, a special presentation (see table above) is possible. In this presentation,
the status is shown on a larger scale on the display.
The following presentations are possible:
ETS-Text
Dynamic range
[Default value]
Comment
Special display (DPT 5.001, DPT
5.005)
bar symbol
bar symbol with fan
value as text (0-100%)
value as text (0-255)
At the settings
ar s
ol
a d ar s
ol ith fa , the
corresponding symbol is
displayed and the bar is filled
according to the current status.
With the settings "value as
text" the text is displayed large
on the display.
Special display (DPT 9.001)
value as symbol
+ °C
value as symbol without
unit
alue as s
ol + K
With the settings "value as
symbol" the text is displayed
large on the display.
Table 43: Send values - Special display