Technical
Manual
Shutter
actuator
JAL
‐
0X10X.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
35
4.8.1
Order
of
alarms
The
parameter
“order
of
alarms”
describes
the
priority
of
the
several
alarms.
The
following
chart
shows
the
setting
options
for
this
parameter:
ETS
‐
text
Dynamic
range
[default
value]
comment
Order
of
alarms
Wind,
Rain,
Frost,
Block
Wind,
Rain,
Block,
Frost
Wind,
Block,
Rain,
Frost
Block,
Rain,
Wind,
Frost
sets
the
priority
of
the
alarms
Chart
21:
Order
of
alarms
If
there
are
two
or
more
alarms
activate
to
the
same
time,
the
shutter
actuator
will
evaluate
the
alarms
according
to
the
appointed
order
of
alarms.
The
shutter
actuator
implements
only
the
function
of
the
alarm
with
the
highest
priority.
The
function
for
the
alarm
with
the
lower
priority
does
not
implement,
as
far
the
alarm
with
the
higher
priority
is
active.
When
the
alarm
with
the
higher
priority
is
deactivated
and
the
alarm
with
the
lower
priority
is
still
active,
the
function
for
the
alarm
with
the
lower
priority
is
activated
afterwards.