Technical Manual

 

 

MDT Universal Interfaces

 

 

 

 

BE – 02001.01 

 

BE – 04001.01

 

 

BE – 06001.01 

 
 

 

 

 

 

 

 

 

 

 
 
 

Содержание BE-02001.01

Страница 1: ...MDT technologies GmbH 51766 Engelskirchen Papiermühle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 1 07 2013 Technical Manual MDT Universal Interfaces BE 02001 01 BE 04001 01 BE 06001 01 ...

Страница 2: ...cation objects per channel 10 3 2 Communication objects logic 12 3 3 Default settings of the communication objects 13 4 Reference ETS Parameter 14 4 1 General Settings 14 4 2 Configuration 16 4 3 Identical parameter 17 4 3 1 Blocking object 17 4 4 Parameter Channels grouped 17 4 4 1 Dimming 18 4 4 2 Shutter 20 4 4 3 Switch 21 4 5 Parameters channels unique 22 4 5 1 Switch 22 4 5 2 Scene 32 4 5 3 C...

Страница 3: ...skirchen Papiermühle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 3 5 Index 47 5 1 Register of illustrations 47 5 2 List of tables 48 6 Attachment 49 6 1 Statutory requirements 49 6 2 Routine disposal 49 6 3 Assemblage 49 6 4 4 Bit Dim command 50 6 5 Datasheet 51 ...

Страница 4: ... you the following universal interfaces Order Code respectively printed in bold type BE 06001 01 Input 6 fold o 6 Inputs for floating contacts LEDs 4 Logic blocks LED Outputs parameterize able BE 04001 01 Input 4 fold o 4 Inputs for floating contacts LEDs 4 Logic blocks LED Outputs parameterize able BE 0200 01 Input 2 fold o 2 Inputs for floating contacts LEDs 4 Logic blocks LED Outputs parameteri...

Страница 5: ...l Manual Universal Interface BE MDT technologies GmbH 51766 Engelskirchen Papiermühle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 5 Figure 2 Exemplary circuit diagram BE0200 01 Model with 2 inputs ...

Страница 6: ...l of a parameterize able LED output The single Inputs and outputs passed out by individual connection cables 2 4 Structure Handling The universal interfaces contain of individual connection cables for the each inputs and outputs The single connection cables are color marked have a look at the assignment plan at the next page The programming function can be activated by the programming button The p...

Страница 7: ...ns of two or four channels based on the hardware design The designation of the channels is always in a consecutive alphabetic order There are three possible functionalities for each channel Disabled No function is set to the channel so that this channel does not contain of any communication objects Channels grouped If you select a pair of channel as channels grouped you will be able to parameteriz...

Страница 8: ...ue Switching function switching function toggle function status function time functions o switch on off delay edge evaluation forced settings sending of byte values Scene function memory function selection of different scenes Counter function counting function edge evaluation counting steps can be chosen freely Switch short long On Off toggle function short long independent parameterize able One b...

Страница 9: ...the used type e g BE 0400 01 2 7 Starting up After wiring the allocation of the physical address and the parameterization of every channel follow 1 Connect the interface with the bus e g MDT USB interface 2 set bus power up 3 Press the programming button at the device red programming LED lights 4 Loading of the physical address out of the ETS Software by using the interface red LED goes out as wel...

Страница 10: ...is first in the alphabet will become the first 5 numbers and the other one will become the following five numbers e g channel A 0 4 and channel B 5 9 The numeration of the channels is always the same even if some channels are disabled Exceptions of this order are the communication objects for the LED outputs These communication objects have the numbers behind the logic blocks Also here the first n...

Страница 11: ...Out Read 0 Reset counter reset the counter value DPT 1 001 In Write 0 Send value sends the parameterized value DPT 5 001 Out Read 0 push button short sends action for short keystroke DPT 1 001 Out Read 1 Value for toggle edge control with toggle function DPT 1 001 In Write 1 Stop Blinds open close driving of the blinds stopping movement of the shutters DPT 1 009 Out Read 1 Dimming dimming DPT 3 00...

Страница 12: ...put from 10 to 12 and at a 4 fold input from 20 to 22 Every following block increases the numbers by 3 The addressing can be made by using the communication objects for the logic analogous to the addressing by the channels The following communication objects for the logic can be shown Figure 5 communication objects logic If a logic block is disabled there will no communication objects be shown The...

Страница 13: ...Low X X X 1 Input A B Dimming 4 Bit Low X X X 1 Input A B Stop Blinds open close 1 Bit Low X X X 2 Input A Scene 1 Byte Low X X X 2 Input A Value for change of direction 1 Bit Low X X X X 2 Input A Value for toggle 1 Bit Low X X X X 2 Input A Push button long 1 Bit Low X X X 2 Input A Push button long 1 Bit Low X X X 3 Input A Counter 4 Byte Low X X X 4 Input A Blocking object 1 Bit Low X X X 5 ne...

Страница 14: ...gure 6 General settings The following chart shows the dynamic range for the general settings ETS text Dynamic range default value comment Debounce time 10 120 ms 10 The inputs are debounced with this time Time for keystroke long 0 1 30 sec 0 8 sec releases the time when the ETS recognizes a long keystroke Behavior at bus power up No read value for toggle Read value for toggle activates the reading...

Страница 15: ...ke 3 The parameter Behavior at bus power up defines the behavior of the universal interface at a bus power return The setting Read value for toggle effects that all communication objects value for toggle are read So the Input knows the current status of the objects If you choose the setting no read value for toggle the input will not know the current status of the actor So the input assumes an unc...

Страница 16: ...hannels ETS text Dynamic range default value comment Function Input A B O P disabled Channels grouped Channels unique Operating mode of the channels Table 6 Parameter channel configuration There are 3 different operating modes for every channel have a look at chart 6 The followig options to parameterize the channels are dependent to the choosen operating mode If you disable the channel there will ...

Страница 17: ...7 Communication object blocking object 4 4 Parameter Channels grouped The chart shows the setting options for grouped channels ETS text Dynamic range default value comment Input A B Dimming Shutter Switch Operating mode of the channel Dimming function A B Brighter Darker Darker Brighter Defines which channel should dim up and which should dim down Shutter function A B Up Down Down Up Defines which...

Страница 18: ... keystroke the dimming object dimming It is possible to parameterize this function as brighter darker or as darker brighter The first function belongs always to the first input If you switch this parameter the function will be switched automatically By choosing the dimming function channel A B as brighter darker the function reacts in this way A short keystroke at input A switches the lights on Th...

Страница 19: ...mdt de 19 The chart shows the correlations between the dimming and the switching object Table 10 Dimming function The following diagram shows the dual surface dimming function Function Brighter Darker Function Darker Brighter Input Input A Input B Input A Input B Dimming function Brighter Darker Darker Brighter Switching function On Off Off On ...

Страница 20: ...ct called Shutter Down Up which responds to a long keystroke The driving object is for moving the shutters up and down The stop blind adjustment object is for the adjustment of the blinds and additional it stops a running movement of the shutter Every shutter actuator controls with a 0 signal the up movement and with a 1 signal the down movement So the universal interface sends these signals to th...

Страница 21: ...function Simple functions like an alternating circuit can be programmed easily by using the grouped switch function The 1 bit communication object sends in dependence of the parameterization a 0 or a 1 signal for the first input and the inverted signal for the second channel So you can chose which channel should switch off and which should switch on The following chart shows the corresponding comm...

Страница 22: ... channel is selected as inactive no further parameterization will be possible 4 5 1 Switch The switching function is for switching the corresponding output on off and toggling it There is a multitude of sub functions at the switching function which enables the user to evaluate edges and integrate times to the switching process The following parameters are shown when the channel is selected as swit...

Страница 23: ...h falling edge sends only a signal at the adjusted edge You can parameterize whether a 0 signal or a 1 signal should be sent There is no inverted signal at subsiding the edge This function always sends only one adjusted signal The function Switch falling and rising edge enables the sending of different values for the falling and the rising edge The following diagram shows this sub function for ris...

Страница 24: ...cess By using this function an edge based alternating circuit can be realized The following diagram describes this sub function As soon as the state changes from 1 to 0 the binary input sends the inverted signal The signal is send always as a short pulse The following chart shows the corresponding communication objects Number Name Length Usage 0 Switch 1 Bit Switching function no differences betwe...

Страница 25: ... work without an actuator the object has to be connected to the switching object switch The connection is important because the universal interface cannot invert the signal when it does not know its current state By undocking this communication object you have more choices to program the input So you can use the object Value for toggle for visualizations or additional functions and you will be mor...

Страница 26: ...amic range default value comment Value for rising edge On Off switches on off at a rising edge Value for falling edge On Off switches on off at a falling edge Send cyclic Off On switches the cyclic sending on off Time interval for send cyclic 1 3000s 1 Time between two sending processes Behavior at bus power up send nothing send status defines the behavior at a bus power up Table 17 Parameter Send...

Страница 27: ... sending causes that the state of the input is sent periodically in certain parameterize able intervals Then the input sends the parameterized value for the corresponding edge A common application for this parameter is for example the observation of windows which are equipped with window contacts So a display can for example show whether all windows are closed or not Furthermore an alarm device ca...

Страница 28: ...fault value comment Value 1 Byte forced setting 2 Bit 1 Byte Value 2 Bit Value forced setting Choice between 1 Byte and 2 Bit Value Table 19 Parameter send value If you have activated the setting 1 Byte the following settings are possible ETS text Dynamic range default value comment Value for rising falling edge 0 255 0 Assignment which value should be send for the falling rising edge Table 20 Par...

Страница 29: ...nd 3 different states Forced setting not active control 0 value 0 The forced setting object has no influence on the receiver For example at a presence detector the automatic function motion detector operation would be switched on Forced setting off control 1 value 0 The forced setting object switches the receiver unconditionally off For example a presence detector would be switched permanent off D...

Страница 30: ... value with delay The sub function Send value with on off delay allows that the binary input sends its value after a parameterized time At the on delay the time starts when the associated input was switched on and at the off delay the time starts when the associated input was switched off The universal interface sends always its current value at this function If the value changes before the time r...

Страница 31: ...de www mdt de 31 You can see the adjusted settings which were made in the ETS for this setting Figure 14 Send value with on delay The following chart shows the communication object Number Name Length Usage 0 Switch 1 Bit Switching function no differences between long and short keystroke Table 25 Communication object send value with delay ...

Страница 32: ...ction is selected ba a long keystroke Scene number 1 64 1 Scene number must be identical with the one in the actuators Blocking object Inactive Active have a look at 4 3 1 blocking object Table 26 Sub function scene The chart shows the communication objects for this parameter Number Name Length Usage 2 Scene 1 Byte calls the depending scene Table 27 Communication object Parameter scene The scene f...

Страница 33: ...3 3 0x83 131 5 0x04 4 0x84 132 6 0x05 5 0x85 133 7 0x06 6 0x86 134 8 0x07 7 0x87 135 9 0x08 8 0x88 136 10 0x09 9 0x89 137 11 0x0A 10 0x8A 138 12 0x0B 11 0x8B 139 13 0x0C 12 0x8C 140 14 0x0D 13 0x8D 141 15 0x0E 14 0x8E 142 16 0x0F 15 0x8F 143 17 0x10 16 0x90 144 18 0x11 17 0x91 145 19 0x12 18 0x92 146 20 0x13 19 0x93 147 21 0x14 20 0x94 148 22 0x15 21 0x95 149 23 0x16 22 0x96 150 24 0x17 23 0x97 15...

Страница 34: ...hart below Sub function Dynamic range default value comment Sub function Count rising Count falling Count rising and falling at count rising only the rising edges will be counted at count falling only the falling edges will be counted Sending difference 0 65535 5 the binary input sends the current value of the counter when the sending difference is reached Blocking object Inactive Active have a lo...

Страница 35: ...ng difference the counter will count every switching process but send its value only at reaching 10 The communication object reset counter sets the counter back to 0 This communication object reacts as well to a 0 as to a 1 The following diagram shows the function of the counter with the setting count rising and falling and a sending difference of 5 At this example the counter sends only a value w...

Страница 36: ...e shown in the chart below Sub function Dynamic range default value comment Value for keystroke short Object 1 On Off Toggle Send value Nothing Action for a short keystroke Value for keystroke long Object 2 On Off Toggle Send value Nothing Action for a long keystroke Blocking object Inactive Active have a look at 4 3 1 blocking object Table 31 Sub functions parameter switch short long The chart sh...

Страница 37: ...ch can be connected in any way By activating the sub function toggle an additional communication object appears called value for toggling This object is a status object for the input and must be connected to the status object of the actuator have a look at 4 5 1 Toggle The following diagram shows the behavior of this parameter Both objects push button and push button long were set to toggle The ob...

Страница 38: ...ub function Dynamic range default value comment Value for keystroke short long Send value chosen sub function Send value Send value 1 Byte Value 0 255 Scene number Selection of the value which shall be sent 1 Byte Value 0 255 0 255 0 Selection of the byte value which shall be sent if byte value is chosen Scene number 1 64 1 Selection of the scene number which shall be sent if scene number is chose...

Страница 39: ...object must be connected with the status function of the actuator for getting feedback of the current switching process Table 35 Communication objects one button dimming At the one button dimming the dimming process is executed by one single channel So it is possible to dim the lights via only one button By a long keystroke the communication Dimming is called which is responsible for the dimming p...

Страница 40: ... channel The communication object Shutter is addressed by a long keystroke and performs the up and down movement of the shutter The direction of movement depends to the last direction of movement If the shutter were driven up at the last time they will be driven down at the next time So the direction of movement changes after every movement The communication object Blinds Stop is addressed by a sh...

Страница 41: ...vers the nesseserary forward voltage as well as the contact current Voltage of the output is set fixed to 2V DC and current to 1mA Because the power supply of the LEDs is deliverd by the bus the output current is low The values are designed for the use of low current LEDs to avoid an overload of the bus system The behavior of the LED Output can be parameterized as well as the luminiscent behavior ...

Страница 42: ...rameter can be adjusted once and is valid for all of the 4 logic blocks Sub function Dynamic range default value comment Behavior at bus power up no read ext logic objects read ext logic objects sub function indicates whether the external logic objects should be read or not at a bus power up Table 40 Common Parameter logic blocks If the read of the external logic at bus power up is activated the s...

Страница 43: ...it the same like logic input 1A 82 Logic Output 1 1 Bit Output logic for switch is activated 1 signal when the logic block is true 82 Logic Output 1 Scene 1 Byte Output logic for scenes is activated 1 signal when the logic block is true Table 42 Communication objects logic The communication objects for the other 3 possible logic blocks are the same like the first one Three numbers are reserved for...

Страница 44: ...t Table 43 Logic sub function switch The sending condition adjusts when the binary input should send a signal on the bus By adjusting the sending condition change of input the binary input sends a signal at every change of any input whether that causes a change of the logic operation or not The setting change of output causes that the binary input sends only a signal when the logic changes its cur...

Страница 45: ...2263 880 Fax 49 2263 4588 knx mdt de www mdt de 45 The logic function is only satisfied when channel A and B as well as the external logic object have a 1 signal The inversion of the output causes that the output is switched on when the logic is not satisfied and switched off when the logic is satisfied ...

Страница 46: ...ction can be parameterized So you can set the logic function as an AND or an OR function and connect all inputs of the binary input and additional 2 external logic objects to the logic function 4 6 3 Logic object type byte value This logic function sends byte values when the logic function is satisfied The chart shows the possible sub functions for the logic operation byte value Sub function Dynam...

Страница 47: ...mmunication objects logic 12 Figure 6 General settings 14 Figure 7 Usage of the channels 16 Figure 8 Parameter two button dimming 18 Figure 9 Two button shutter function 20 Figure 10 Two button switching function 21 Figure 11 Parameter switch 22 Figure 12 Sub function send status 26 Figure 13 Sub function send value 28 Figure 14 Send value with on delay 31 Figure 15 Parameter Scene 32 Figure 16 Pa...

Страница 48: ...end value 28 Table 20 Parameter send value 1 Byte object 28 Table 21 Communication object Parameter Send value 1 Byte object 28 Table 22 Dynamic range send value forced setting 29 Table 23 Communication object Send value forced setting 29 Table 24 Parameter Send value with delay 30 Table 25 Communication object send value with delay 31 Table 26 Sub function scene 32 Table 27 Communication object P...

Страница 49: ... can occur danger for humans animals or material assets Do not let the packaging lying around careless plastic foil bags etc can be a dangerous toy for kids 6 2 Routine disposal Do not throw the waste equipment in the household rubbish The device contains electrical devices which must be disposed as electronic scrap The casing contains of recyclable synthetic material 6 3 Assemblage Risk for life ...

Страница 50: ...ribes the 4 Bit dimming command Decimal Hexadecimal Binaer Dim command 0 0 0000 Stop 1 1 0001 100 Darker 2 2 0010 50 Darker 3 3 0011 25 Darker 4 4 0100 12 5 Darker 5 5 0101 6 25 Darker 6 6 0110 3 13 Darker 7 7 0111 1 56 Darker 8 8 1000 Stop 9 9 1001 100 Brighter 10 A 1010 50 Brighter 11 B 1011 25 Brighter 12 C 1100 12 5 Brighter 13 D 1101 6 25 Brighter 14 E 1110 3 13 Brighter 15 F 1111 1 56 Bright...

Страница 51: ... debounce time contact typ and telegram rate limitation The command for rising and falling edge can be defined independently and with the block communication object each channel can be blocked or released The logic module can release two telegrams after receiving a trigger signal from the inputs The MDT Universal Interface is a flush mounted device to be inserted in a wiring box or behind a push but...

Страница 52: ...er consumption KNX bus typ 0 25W 0 25W 0 25W Permitted input cable length 5m 5m 5m Operation temperature range 0 to 45 C 0 to 45 C 0 to 45 C Enclosure IP 20 IP 20 IP 20 Dimensions UP W x H x D 41mm x 41mm x 12mm 41mm x 41mm x 12mm 41mm x 41mm x 12mm Examplary circuit diagram BE 02001 01 Examplary circuit diagram BE 04001 01 Examplary circuit diagram BE 06001 01 MDT technologies GmbH 51766 Engelski...