MCZ Veld Скачать руководство пользователя страница 20

Chapter 5

 

USE AND MAINTENANCE MANUAL 

page

 20  

 

Operation 

Technical dept. - All rights reserved by MCZ GROUP S.p.A. - Reproduction 

prohibited 

 

SECONDARY AIR:

  

The introduction of secondary air is predetermined, and is used for the 

partial cleaning of the glass and allows the completion of the 

combustion process. Consequently, if it is well calibrated, the efficiency 

and heating performance of the stove are higher. 
 

5.3.2.1.  

VELD stove air control  

Move the control lever towards the right if you want more combustion 

air to enter the combustion chamber. Vice versa move the lever 

towards the left if your want less air inlet. 
The primary and secondary air inlet is predetermined; move the lever 

to dose the quantity of primary and secondary inlet air. 
 

1

2

3

 

 
 
 
PRIMARY AIR LEVER (TURNED TOWARDS THE RIGHT) 

The lever turned towards the right (pos.1) is designed to bring a large 

quantity of primary air beneath the combustion chamber fire plane, to 

allow rapid and effective ignition of the fire (Fig.4).  
 

SECONDARY AIR LEVER (TURNED DOWN) 

Secondary air, as mentioned above, allows the completion of 

combustion and increases the efficiency (lever in pos.2 - fig.5). 
The position of the lever in fig.5 determines the nominal output, 

minimizing primary air and the secondary air inlet. 

 
LEVER TURNED TOWARDS THE LEFT 

From this point, turn the lever clockwise to decrease the quantity of air 

in the combustion chamber until position 3 is reached, where only a 

minimum quantity of primary air is present (fig.6). 
This position is used to prolong combustion (for instance, at night, or 

when you are not at home) so that the stove is set to minimum for 

auto-combustion, to save on fuel and keep the flame burning. 
 

Fig.4

 Primary air inlet 

Start-up 

Fig.5

 Secondary air inlet 

 

Fig.6

 Minimum primary air inlet 

Содержание Veld

Страница 1: ...0 USE AND INSTALLATION MANUAL EN NuTech Renewables Ltd Unit 11 Warrenpoint Enterprise Centre Newry Road Warrenpoint Co Down BT34 3LA Tel 44 28 417 53031 Email info nutechrenewables com www NuTechrenew...

Страница 2: ...LUE PIPE 10 2 6 1 Flue pipe examples 11 2 7 CHIMNEY 12 3 DIMENSIONS AND TECHNICAL SPECIFICATIONS 13 3 1 VELD STOVE 13 3 1 1 Technical specifications 14 4 INSTALLATION AND ASSEMBLY 15 4 1 PREPARATION A...

Страница 3: ...in the event of faults or if in doubt please contact your retailer who will provide all the necessary assistance Document revisions In order to improve the product and to update this document the Manu...

Страница 4: ...ilation ducts If Oyster technology is not implemented Avoid having several operational flue ducts in the room or the proximity of a stair well and make sure that there are no appliances in adjacent co...

Страница 5: ...tly or indirectly be caused to property or personal injury or harm to animals ensuing from failure to observe all the instructions provided herein and specifically concerning the warnings regarding in...

Страница 6: ...al air inlet and that they are not used as a bedroom or bathroom or where there is no fire hazard such as garages timber storerooms warehouses of flammable materials observing under all circumstances...

Страница 7: ...stove in rooms with an explosive atmosphere The floor of the room where the stove is installed must be suitably sized to withstand its weight 2 2 1 Safe distances If particularly delicate objects are...

Страница 8: ...oes not reduce the minimum cross section be positioned in such a way as to not be obstructed the maximum length permitted for ducting is 6 m with two 90 elbows The stove must be connected to the exter...

Страница 9: ...illes always feature an indication of the useful cross section in cm2 on one side When choosing the grille and hole size check that the useful cross section of the grille is larger or the same as the...

Страница 10: ...fibre cement pipes is forbidden The smoke pipe must not cross rooms in which it is forbidden to install combustion appliances The use of counter sloping pipes is forbidden 2 6 FLUE PIPE The flue pipe...

Страница 11: ...ngular cross section the ratio between the internal dimensions should be 1 5 The sections lengths of the flue pipe shown in the technical data table are guidelines for correct installation Any alterna...

Страница 12: ...ze Steel flue pipe chimney with internal smoke deflector cone Allows excellent smoke disposal The chimney must Have an inner section equal to that of the flue Have a working outlet section of at least...

Страница 13: ...age 13 Dimensions and technical specifications Technical dept All rights reserved by MCZ GROUP S p A Reproduction prohibited 3 DIMENSIONS AND TECHNICAL SPECIFICATIONS 3 1 VELD STOVE 218 267 5 8 0 1124...

Страница 14: ...output Min KW 3 5 Kcal 3010 Efficiency 84 7 Heatable volume m3 151 40 172 35 201 30 Recommended draught 12 Pa 0 12 mbar Smoke temperature 240 C Particulate 30 mg Nm3 13 O2 17 mg MJ Smoke outlet 15 cm...

Страница 15: ...n chamber We recommend you reposition each element correctly 4 1 PREPARATION AND UNPACKING The Veld stove is delivered with three different packagings one contains the stove figure 1 one contains the...

Страница 16: ...of the structure and they can be installed as illustrated in the figure and adjusted with a screwdriver inserting it into the tip of the feet 4 3 CERAMIC CLADDING ASSEMBLY The installation of the cera...

Страница 17: ...Chapter 4 USE AND MAINTENANCE MANUAL page 17 Installation and assembly Technical dept All rights reserved by MCZ GROUP S p A Reproduction prohibited G F SPINE H I D L E C C B A B PINS...

Страница 18: ...smoke and paint smells If necessary touch up the paint with the spray can of the dedicated colour see Stove accessories Do not stand close to the stove and as mentioned air the room The smoke and pai...

Страница 19: ...ot burn waste The gases produced by combustion resulting from the use of unsuitable fuel could damage the stove the flue pipe pollute and compromise your health 5 3 USING THE STOVE 5 3 1 FUEL LOADING...

Страница 20: ...THE RIGHT The lever turned towards the right pos 1 is designed to bring a large quantity of primary air beneath the combustion chamber fire plane to allow rapid and effective ignition of the fire Fig...

Страница 21: ...of wood Open the combustion air damper completely right hand lever Light the paper and if necessary keep the door open a few minutes until the combustion chamber and the flue pipe begin to warm up On...

Страница 22: ...to contact with hot parts In the event of poor weather conditions for the operation of the stove low pressure external temperatures not particularly harsh windy day this may lead to inverse draught i...

Страница 23: ...sable to handle the door carefully without slamming it or forcing it open or shut Since it is not a flexible element the glazing may break In addition this type of glazing does not shatter or burst an...

Страница 24: ...hich the appliance should operate correctly have been reached and consequently we recommend the use of the quantity of fuel specified in the technical tables 6 1 6 Cleaning the flue pipe We recommend...

Страница 25: ...MCZ GROUP S p A Via La Croce 8 33074 Vigonovo di Fontanafredda PN ITALY Telephone 39 0434 599599 PBX Fax 39 0434 599598 Internet www mcz it e mail mcz mcz it 8901142800 Rev 1 12 2011...

Отзывы: