IM 671 / Page 7 of 28
Installation of cabinet/wall sleeve for thick walls require spe-
cial consideration. Table 1 should be used to determine the
maximum wall thickness allowed for standard cabinet wall
sleeve. For thicker walls, cabinet/wall sleeve extensions are
available from your representative. Refer to pages 8 for proper
installation of cabinet/wall sleeve extensions.
Cabinet/wall sleeve installation in thick walls is similar to
frame and brick installation. The wall sleeve is not intended to
replace the lintel. Install as follows:
1.
Clean the opening of all debris that may interfere with
installation.
2.
If the unit is to be supplied with a subbase, refer to page
9 for installation procedure. Install subbase before install-
ing cabinet/wall sleeve.
3.
If the optional drain kit is to be employed, refer to page
10 before proceeding.
4.
If wall thickness exceeds dimensions shown in table 1 a
cabinet/wall sleeve extension must be used. Install the
extension as described on page 8. Once the extension is
attached to the cabinet/wall sleeve, place a thin pad of
soft mortar on bottom of the opening and slide in the wall/
sleeve extension assembly. Be sure to recess the wall/
sleeve enough to accommodate outside louver. This re-
cess is
3
/
8
"(9.5mm) for stamped louvers and 1
1
/
8
"(32mm)
for architecture louvers. Louvers should be flush to exte-
rior surface when completed. Note : Do not recess the
sleeve if using the external drain kit - see pg. 10.
5.
Level cabinet /wall sleeve in both directions and secure
by anchoring with appropriate fasteners, (as shown in fig-
ure C page 8), or drill additional holes as required to se-
cure firmly. Caution: Do not drill holes in the subbase
of the cabinet/wall sleeve. Where a subbase is used,
secure wall sleeve to subbase with clips provided.
Wall Sleeve Installation – Thick Wall Construction
Figure 9. Thick Wall Construction with Standard
Electrical Subbase
Figure 11. Thick Wall Installation with Hydronic Subbase
Figure 10. Thick Wall Construction with Cord Connection
Note:
a. Standard Subbase is available in 3" (76mm) or 4" (102mm) height.
Leveling legs provide adjustment of 1" (25.4mm).
b. Wall Sleeve extension is available in various depths and supplied
as required.
Table 1. Maximum Wall Thickness without Sleeve
Extensions
6.
Caulk the cabinet/wall sleeve to the wall opening on both
inside and outside perimeter. Be careful not to plug the
weep holes. Caulking should be resilient, non hardening
type such as silicone.
Floor
16" (406mm)
17"
(406mm)
Caulk
Perimeter
Outdoor
Louver
Steel Lintel (by Others)
Mounting
Screws
by
Installer
Room
Cabinet
8
1
⁄
4
"
(203mm)
Hydronic Subbase & Adjustable
Legs w/1" Adjustment
Wall Sleeve
Wall Receptacle
(by Others)
3" (76mm)
13
3
⁄
4
"
(349mm)
See
Table 1
Floor
16" (406mm)
17"
(406mm)
Caulk
Perimeter
Outdoor
Louver
Steel Lintel (by Others)
Mounting
Screws
by
Installer
8
1
⁄
4
"
(203mm)
Wall Sleeve
13
3
⁄
4
"
(349mm)
1" (25.4mm)
See
Table 1
8
1
⁄
4
" (203mm)
Hydronic
Heating
Coil
Electrical Subbase
Floor
16" (406mm)
17"
(406mm)
Caulk
Perimeter
Both
Indoors &
Outdoors
Outdoor
Louver
Steel Lintel (by Others)
Mounting
Screws
by
Installer
8
1
⁄
4
"
(203mm)
Wall Sleeve
13
3
⁄
4
"
(349mm)
4
3
⁄
8
" Min. (111mm)
See
Table 1
See Note a.
Wall
Sleeve
Extension
See
Note b.
Maximum Wall Thickness
Louver
No
Standard
Hydronic
Type
Subbase
Subbase
Subbase
Stamped
14" (356mm)
9
1
⁄
2
" (241mm)
13
1
⁄
8
" (333mm)
Architectural
14
7
⁄
8
" (378mm)
10
3
⁄
8
" (264mm)
14" (356mm)
NOTE: Wall sleeve to be
flush (Min.) with inside
finished wall.
Wall Sleeve
Extension
Wall Sleeve
Extension