background image

Evaporator and Condenser Water Piping

PFS evaporators and condensers are equipped with either victaulic or flange connections. The
installing contractor must provide matching connections.

Remove the solid-state temperature sensor and thermostat bulbs from the wells to prevent

damage to those components when welding on the victaulic or flange connections.

Connect the condenser with the inlet water entering at the bottom to maximize subcooling. The

condenser water will discharge from the top connection.

Support piping to reduce weight and strain on the fittings and connections. Be sure piping is

adequately insulated. Install a cleanable 20-mesh water strainer in evaporator and condenser water
piping. install enough 

shutoff 

valves 

to permit draining water from the evaporator or condenser

without draining the complete system.

Freeze Notice: Neither the evaporator nor the condenser is self-draining. Both must be
blown out.

Include thermometers at the inlet and outlet connections and air vents at the high points of piping.

The water heads can be interchanged (end for end) allowing water connections to be made at either
end of the unit. Use new head gaskets when interchanging water heads. When water pump noise is
objectionable, use rubber isolation sections at both the inlet and outlet of the pump. Vibration
eliminator sections in the condenser inlet and outlet water lines are not normally required. Where
noise and vibration are critical, and unit is mounted on spring isolators, flexible piping connections
are necessary.

Water treatment

If unit is operating with a cooling tower, clean and flush cooling tower. Make sure tower “blowdown”

or bleedoff  is operating. Atmospheric air contains many contaminants which increases the need for
water treatment. The use of untreated water may result in corrosion, erosion, sliming, scaling, or
algae formation. A water treatment service is recommended. McQuay  International is not
responsible for damage or faulty operation from untreated or improperly treated water.

Head pressure control, tower system

The minimum entering water temperature to the condenser must not be lower than 70°F (2 

 

 

Use a three-way bypass valve around the tower to modulate the condenser water flow. Figure 6 shows

a three-way pressure actuator water regulating valve used for cooling applications. This regulating
valve will assure an adequate condensing pressure if the inlet condenser water temperature falls below
70°F). An optional AOX-4 board located in the MicroTech  panel will control a cooling tower bypass
valve or a varible speed condenser pump.

IM

 663 7

Содержание PFS-150B

Страница 1: ......

Страница 2: ......

Страница 3: ...trols are external from the electrical control center Compressors are protected by solid state overload protection and over temperature protection Field installed fused disconnect Sw itch furnished by...

Страница 4: ...embers It is not necessary to bolt the unit to the mounting slab or frame work although mounting holes are provided in the unit support at the four corners Compressor Condensation Condensation occurs...

Страница 5: ......

Страница 6: ......

Страница 7: ...heads When water pump noise is objectionable use rubber isolation sections at both the inlet and outlet of the pump Vibration eliminator sections in the condenser inlet and outlet water lines are not...

Страница 8: ...enser waterside drying and accelerates fouling If a valve is not used Figure 7 illustrates the recommendation of a loop at the outlet Size the loop height H to offset the negative pressure caused by t...

Страница 9: ...um design ambient temperature Note Freeze damage is not considered a warranty failure and is not the responsibility of McQuay International 3 Insulate field water piping especially on the chilled wate...

Страница 10: ...itable for 23 VAC low current Ibma Table 5 Flow Switch Minimum Flow Rates Nominal Pipe Size Min Required Flow to inches Activate Switch GPM L s 5 58 7 3 7 6 79 2 5 Glycol Solutions Use industrial grad...

Страница 11: ...wer consumption multiply the unit kW TR with water by the kW TR factor Test coolant with a clean accurate glycol solution hydrometer similar to that found in service stations to determine the freezing...

Страница 12: ...es exceeding the maximum values shown can cause erosion on the evaporator water connections and tubes Measure the chilled water pressure drop through the evaporator at field installed pressure taps It...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ...lter the wiring to the MotorSaver General Information Wiring must comply with all applicable codes and ordinances Warranty is void if wiring is not in accordance with specifications Copper wire must b...

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ...ater system piping Open all water tlow valves and start chilled water pump Check all piping for leaks Flush the evaporator and condenser system piping Sequence of Operation The following sequence of o...

Страница 26: ...onditions With power to the controller there are several off states as follows Off Manual When the setpoint in menu I I Control Mode is set to the Mode Manual Off to change set the Mode Auto Network o...

Страница 27: ...ater than I 2 Abs Condenser Psia i Abs Evaporator Psia 7 The unit status moves from If additional cooling capacity is required then the controllers will add capacity by changing the capacity control s...

Отзывы: