Initial Start-up

CAUTION

I

Initial start-up must be performed by McQuayService personnel.

1.

2.

3.

Set up control as described in the initial conditions.

Turn front panel switch to Auto position (chilled water flow pump relay will energize).

If the field installed flow indicator does not indicate chilled water flow after 30 seconds, the

alarm output wi

 I l be 

energized.

4.

5.

6.

The chiller will start w hen  the leaving water temperature is 

 above the Active Setpoint.

The controller starts the compressor W ith the least starts while in auto Iead-lag setting. energizes
the liquid in_jection solenoid and motor coolin g solenoid. energizes the suction injection
solenoids. and de-energizes the crank  case heaters.

Suction injection will turn off when the following conditions have been met:
The discharge superheat drops below   “F. the Liquid Presence sensor shows liquid, and the
Absolute Pres. ratio is greater than I.2 

 Abs. 

Condenser Psia   Abs. Evaporator Psia)

7. 

The unit status moves from:

If additional cooling capacity is required then the controllers will add capacity by changing the

capacity control solenoids outputs 7. 8. and 9 and maintaining a close balance in amp capacity
between compressors after both compressor are running. The lag compressor will come on after the

lead compressor amps have exceeded the  setpoint  to turn on the lag for the defined lag time (see menu

23 on the master controller).

Load Recycle

As the load drops. the controls will unload the compressors until the compressors amps drop below
the lag cutoff point for the delay time required. The control will then shut off the lag compressor and
further reduction in load will cause the leaving water ternperature to drop 3   F below the active

setpoint which will cause the compressor to turn off on Load Recycle and the display will show
Waiting For Load and the chilled water pump will remain on.

EvapOn-Recirc  **Sec to All Systems Off to MCR Started to Pre-purge to Open
Solenoid to Running Min Amp Lim to Running:  %  Cap 50

IM 663

27

Содержание PFS-150B

Страница 1: ......

Страница 2: ......

Страница 3: ...trols are external from the electrical control center Compressors are protected by solid state overload protection and over temperature protection Field installed fused disconnect Sw itch furnished by...

Страница 4: ...embers It is not necessary to bolt the unit to the mounting slab or frame work although mounting holes are provided in the unit support at the four corners Compressor Condensation Condensation occurs...

Страница 5: ......

Страница 6: ......

Страница 7: ...heads When water pump noise is objectionable use rubber isolation sections at both the inlet and outlet of the pump Vibration eliminator sections in the condenser inlet and outlet water lines are not...

Страница 8: ...enser waterside drying and accelerates fouling If a valve is not used Figure 7 illustrates the recommendation of a loop at the outlet Size the loop height H to offset the negative pressure caused by t...

Страница 9: ...um design ambient temperature Note Freeze damage is not considered a warranty failure and is not the responsibility of McQuay International 3 Insulate field water piping especially on the chilled wate...

Страница 10: ...itable for 23 VAC low current Ibma Table 5 Flow Switch Minimum Flow Rates Nominal Pipe Size Min Required Flow to inches Activate Switch GPM L s 5 58 7 3 7 6 79 2 5 Glycol Solutions Use industrial grad...

Страница 11: ...wer consumption multiply the unit kW TR with water by the kW TR factor Test coolant with a clean accurate glycol solution hydrometer similar to that found in service stations to determine the freezing...

Страница 12: ...es exceeding the maximum values shown can cause erosion on the evaporator water connections and tubes Measure the chilled water pressure drop through the evaporator at field installed pressure taps It...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ...lter the wiring to the MotorSaver General Information Wiring must comply with all applicable codes and ordinances Warranty is void if wiring is not in accordance with specifications Copper wire must b...

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ...ater system piping Open all water tlow valves and start chilled water pump Check all piping for leaks Flush the evaporator and condenser system piping Sequence of Operation The following sequence of o...

Страница 26: ...onditions With power to the controller there are several off states as follows Off Manual When the setpoint in menu I I Control Mode is set to the Mode Manual Off to change set the Mode Auto Network o...

Страница 27: ...ater than I 2 Abs Condenser Psia i Abs Evaporator Psia 7 The unit status moves from If additional cooling capacity is required then the controllers will add capacity by changing the capacity control s...

Отзывы: